ACCIDENTS D’ORIGINE ELECTRIQUE EN FRANCE

ACCIDENTS D’ORIGINE ELECTRIQUE EN FRANCE. ACCIDENTS DU TRAVAIL MORTELS D’ORIGINE ELECTRIQUE EN FRANCE. PH. N. FR É QUENT. TRES FR É QUENT. Terre. FORMES D’ ÉLECTRISATION CONTACT DIRECT Cas d'un régime TT. PH. N. Très rare. Relativement fréquent. Terre.

gizela
Download Presentation

ACCIDENTS D’ORIGINE ELECTRIQUE EN FRANCE

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ACCIDENTS D’ORIGINE ELECTRIQUE EN FRANCE

  2. ACCIDENTS DU TRAVAIL MORTELS D’ORIGINE ELECTRIQUE EN FRANCE

  3. PH N FRÉQUENT TRES FRÉQUENT Terre FORMES D’ ÉLECTRISATIONCONTACT DIRECTCas d'un régime TT

  4. PH N Très rare Relativement fréquent Terre FORMES D’ ÉLECTRISATIONCONTACT INDIRECT Cas d'un régime TT

  5. T Phase critique Diastole Systole Cycle cardiaque CYCLE CARDIAQUE

  6. EFFETS DU COURANT SUR LE CORPS HUMAIN EFFET DU COURANT CONTINU Fibrilation cardiaque 130mA Seuil de non lâcher ? mA Seuil de perception 2 mA

  7. TENSION PEAU PEAU PEAU PEAU DE SECHE HUMIDE MOUILLEE IMMERGEE CONTACT 25 v 5000 2500 1000 500 50 v 4000 2000 875 440 250 v 1500 1000 650 325 >250 v 1000 1000 650 325 Variation de la résistance du corps humain en fonction de la tension de contact et de l’état de la peau R (k ) 5 Peau sèche Peau humide 4 Peau mouillée 3 Peau immergée 2 1 250 380 Uc(V) 25 50 Article 322-2 de la norme NFC 15-100 de 1977

  8. SCA ELOIGNEMENT d ISOLATION PROTECTION DES CÂBLES PAR GAINES ISOLANTES PROTECTION SURVEILLANT ELECTRIQUE

  9. ~ DEGRES DE PROTECTION bille d= 12,5mm Doigt d’épreuve articulé d= 12mm longueur 80 mm IP2x Fil d’acier d=2,5mm IP3x IP2x en BT et IP3x en HT

  10. CLASSES DE MATERIELNorme NF C 20-030 Classe 0 :Matériel dans lequel la protection contre les chocs électriques repose sur l’isolation principale. Ceci implique qu’aucune dispoisition n’est prévue pour le raccordement des parties conductricesaccessibles( masses ) Classe I : Matériel dans lequel la protection contre les chocs électriques ne repose pas uniquement sur l’isolation principale mais qui comporte une mesure de sécurité supplémentaire sous forme de moyens de raccordement des parties conductrices accessibles ( masses ) Classe II :Matériel dans lequel la protection contre les chocs électriques ne repose pas uniquement sur l’isolation principale mais qui comporte des mesures supplémentaires de sécurité telles que la double isolation ou l’isolation renforcée . Ces mesures ne comportent pas de moyen de mise à la terre et ne dépendent pas des conditions d’installation Les appareils de classe II peuvent être : - Totalement isolés: l’envellope durable et pratiquement continue en matière isolante enferme toutes les parties métalliques. - Sous enveloppe métallique : l’enveloppe métallique est pratiquement continue . L’enveloppe métallique accessible n’est pas considérée comme étant une masse Classe III : Matériel dans lequel la protection contre les chocs électriques repose sur l’alimentation sous très basse tension de sécurité TBTS.

  11. MESURES DE PROTECTIONLe matériel est classé en fonction de sa conception et de la tension d’alimentation

  12. Clac NON ! OUI ! Disjoncteur Disjoncteur différentiel TERRE MOYENS DE PROTECTION

  13. DOMAINES DE TENSIONDécret n° 88-1056 DOMAINE COURANT COURANT DE TENSION ALTERNATIF CONTINU U  50 Volts U  120Volts TBT 50 < U  500 V 120 < U  750V BTA 500 < U  1000V 750 < U  1500V BTB 1000 < U  50kV 1500 < U  75kV HTA U > 50kV U > 75kV HTB

  14. TENSION DE SECURITE EN ALTERNATIF : INFERIEUR A 50 V MAINS SECHES MAINS MOUILLEES 48 Volts 24 Volts   MAINS SECHES MAINS SECHES 240 Volts 400 Volts EFFETS DU COURANT ELECTRIQUE

  15. LES TEXTES REGLEMENTAIRES TEXTES LEGISLATIFS Fixent les buts TEXTES NORMATIFS Apportent les solutions Ministère de l’industrie et de la recherche LOIS Prescriptions administratives Commissariat à la normalisation - décrets - arrêtés - circulaires - notes techniques - fiches techniques - avis AFNOR Bureaux de normalisation Electricité-UTE

  16. CLASSIFICATION DU PERSONNELDécret 88-1056 Article 46 • Deux catégories de travailleurs • 1- Travailleurs utilisant des installations électriques • 2- Travailleurs effectuant des opérations

  17. TRAVAILLEURS UTILISANT DES INSTALLATIONS ÉLECTRIQUESDécret 88-1056 Article 46 • Aucun accès à des pièces nues sous tension • Les armoires électriques doivent être fermées à clef et celle-ci doit être retirée. • Ces travailleurs sont autorisés à manoeuvrer ou à couper le fonctionnement d'un système • Ces travailleurs sont autorisés à remplacer une lampe ou un fusible débrochable

  18. TRAVAILLEURS EFFECTUANT DES OPÉRATIONSDécret 88-1056 Article 46 • Cette catégorie de personnel, comprend des électriciens et des non électriciens • L'employeur doit s'assurer que l'aptitude médicale de son personnel est compatible avec les opérations effectuées sur un ouvrage électrique • Le chef d’établissement est tenu d’assurer une formation spécifique au poste de travail.

  19. ORGANISATION Décret 88-1056 Article 47 • Les travailleurs doivent signaler les défectuosités et anomalies constatées • Ces constatations doivent être connues le plus rapidement par le chef d'établissement

  20. MANOEUVRES OPERATIONS conduisant à un changement de la configuration électrique : - d’un réseau , d’une installation ou de l’alimentation d’un équipement Manoeuvres de consignation Manoeuvres d’exploitation Manoeuvres d’urgence Opérations effectuées dans le cadre du fonctionnement normal des réseaux et des équipements Opérations coordonnées aboutissant à la consignation ou à la déconsignation Imposées par les circonstances pour la sauvegarde des personnes et des biens Peuvent être réalisées LOCALEMENT ou à DISTANCE Les manoeuvres des appareils de COUPURE D’URGENCE peuvent être effectuées par toute personne

  21. OUI MANOEUVRES DE CONSIGNATION OUVRAGES ELECTRIQUES TRAVAUX ELECTRIQUES OU NON TRAVAUX SUR PARTIES NON ELECTRIQUESDE MACHINE OU APPAREILS Manoeuvres complexes Succession rigoureuse de l’ordre des manoeuvres OUI NON OUI Local d’accès réservé aux électriciens NON OUI Voisinage de pièces nues sous tension ( Appareillage non IP 2x en BT ) NON CHARGE DE CONSIGNATION HABILITATION MINIMUM B1V PERSONNELNON HABILITE