MLC Connectivity to SLC 500 via DeviceNet

Loading in 2 Seconds...

play fullscreen
1 / 36

MLC Connectivity to SLC 500 via DeviceNet - PowerPoint PPT Presentation


  • 256 Views
  • Uploaded on

MLC Connectivity to SLC 500 via DeviceNet. Equipment Needed for Connecting. MLC 9000 BCM Allen-Bradley SLC 500 CPU 5/02 or higher 5/02 smallest CPU to support M0/M1 File Transfer Allen-Bradley 1747-SDN DeviceNet Scanner Allen-Bradley RSNetworx or DeviceNet Manager Software

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

MLC Connectivity to SLC 500 via DeviceNet


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
equipment needed for connecting
Equipment Needed for Connecting
  • MLC 9000 BCM
  • Allen-Bradley SLC 500 CPU 5/02 or higher
    • 5/02 smallest CPU to support M0/M1 File Transfer
  • Allen-Bradley 1747-SDN DeviceNet Scanner
  • Allen-Bradley RSNetworx or DeviceNet Manager Software
  • RSLogix PLC Programming Software
  • PC Interface(i.e 1770-KFD for programming)
  • DeviceNet Cabling
    • Thick Trunk Cable with Mini-Connectors
    • Thin Drop Cable with Micro or Mini-Connectors
    • T-Connectors
    • Terminating connectors(110 Ohms)
how slc500 communicates with 1747 sdn
How SLC500 Communicates with 1747-SDN
  • Two methods used
    • I/O Transfer
      • 1747 occupies 32 Input Words and 32 Output Words
        • 1 word of input, 1 word of output used for module status and command
        • 62 words available for devices
      • Intended for devices transmitting small blocks of information
        • Proximity and Photoelectric Switches
        • “Slice” I/O
        • Valves
how slc 500 communicates with 1747 sdn
How SLC 500 Communicates with 1747-SDN
  • Block Transfer via M0/M1 Files
    • M1 File
      • 150 Words Available for Input from Network Devices (M1:1.0-M1:1.149)
      • 74 Diagnostic Words (M1:1.150-M1:1.223)
      • 32 Words for Inbound Explicit Message Control (M1:1.224-M1:1.255)
how slc 500 communicates to 1747 sdn
How SLC 500 Communicates to 1747-SDN
  • Block Transfer via M0/M1 Files
    • M0 File
      • 150 Words of data used for output to network devices (M0:1.0-M0:1.149)
      • 74 Words Reserved/Unused (M0:1.150-M0:1.223)
      • 32 Words used for outgoing explicit message control (M0:1.224-M0:1.255)
how mlc 9000 communicates with 1747 sdn
How MLC 9000 Communicates with 1747-SDN
  • MLC 9000 Gateway
    • Converts DeviceNet Messages from Scanner into Modbus Messages to Bus Control Module
  • Uses Polled Messaging for Implicit I/O Connection
    • One Loop Control Module takes up 16 Bytes of Input and 6 Bytes of Output
  • Uses Explicit Messaging to gain access to parameters not supported through implicit connection
setting up pc to communicate via devicenet
Setting Up PC to Communicate via DeviceNet

In RSLinx, Select Communications and Configure driver

setting up pc to communicate via devicenet9
Setting Up PC to Communicate via DeviceNet

Under Available Driver Types, select DeviceNet Drivers and select Add new

setting up pc to communicate via devicenet11
Setting Up PC to Communicate via DeviceNet

Select Processor to Connect to and slot where 1747-SDN resides

setting up pc to communicate via devicenet12
Setting Up PC to Communicate via DeviceNet

1747-SDNPT-1 should be seen running

setting up slc500 to pull information from 1747 sdn15
Setting Up SLC500 to Pull Information from 1747-SDN

From Menu Tree, Select IO Configuration then add 1747-SDN into Slot 1 of Rack

setting up slc500 to pull information from 1747 sdn16
Setting Up SLC500 to Pull Information from 1747-SDN

Highlight on Rung in Ladder Window

setting up slc500 to pull information from 1747 sdn17
Setting Up SLC500 to Pull Information from 1747-SDN
  • Insert one Normally Closed Contact and Two Copy Instructions into Rung 1
  • Copy Instructions move data from M0/M1 Files to usable data areas
setting up slc500 to pull information from 1747 sdn18
Setting Up SLC500 to Pull Information from 1747-SDN
  • Last Rung Energizes Output Run coil and disables in event of error in module
  • Download to PLC and place in Run Mode
configuring the devicenet network
Configuring the DeviceNet Network
  • To Configure Network, Gateway EDS file must be installed
  • EDS (Electronic Data Sheet) carries configuration properties for DeviceNet products
  • Start RSNetworx then select Tools-EDS Wizard
configuring the devicenet network20
Configuring the DeviceNet Network

Select Register EDS File then select Choose File

configuring the devicenet network21
Configuring the DeviceNet Network
  • Select A: Drive then select West0456
  • Click Open
configuring the devicenet network22
Configuring the DeviceNet Network

Wizard will run test on EDS

configuring the devicenet network23
Configuring the DeviceNet Network

Wizard will prompt you to associate a graphic icon with EDS

configuring the devicenet network24
Configuring the DeviceNet Network

This will finish the EDS Installation

configuring the devicenet network25
Configuring the DeviceNet Network

Select 1747-SDN from Device List

configuring the devicenet network26
Configuring the DeviceNet Network

Insert MLC 9000 Gateway form Device List

configuring the devicenet network27
Configuring the DeviceNet Network

Double Click on 1747-SDN and select Scanlist

configuring the devicenet network28
Configuring the DeviceNet Network
  • Click on arrow to add Gateway to 1747-SDN’s scanlist
  • Select edit I/O parameters
configuring the devicenet network29
Configuring the DeviceNet Network
  • Adjust the Polled Rx and Tx parameters to match the number of I/O taken up by LCM’s
  • 16 bytes of Rx and 6 bytes Tx for every LCM (up to 8 LCM’s)
configuring the devicenet network30
Configuring the DeviceNet Network
  • Select Input
  • Select Memory Type M file
  • Select AutoMap
configuring the devicenet network31
Configuring the DeviceNet Network
  • Select Output
  • Select Memory Type M file
  • Select AutoMap
configuring the devicenet network32
Configuring the DeviceNet Network
  • From Main Screen, select Tools then Node Commissioning
  • Nodes must be commissioned with proper baud rate and node address before the configuration can be downloaded to network
  • Select Browse
configuring the devicenet network33
Configuring the DeviceNet Network
  • Select 1747-SDNPT from list of drivers
  • RSNetworx will detect connected devices
  • Select Node to adjust
configuring the devicenet network34
Configuring the DeviceNet Network

Change Node Address and click Apply if changes are needed

configuring the devicenet network35
Configuring the DeviceNet Network
  • To prepare for download, network connection must be established online first
  • Click Network, then Online
configuring the devicenet network36
Configuring the DeviceNet Network

After Online connection established, select network-download to network to send configuration