html5-img
1 / 17

MDS COMMISSIONING

MDS COMMISSIONING. COMMISSIONING. Address Setting. DIP switch S2. A-series outdoor unit PCB. K1, K2 Button. Press K2 for 5 seconds to enter parameter set mode LCD display “- - - -” Enter the password, 0755 Set the no. of indoor units. DIP switch S1. COMMISSIONING. ON (1)

jess
Download Presentation

MDS COMMISSIONING

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. MDS COMMISSIONING

  2. COMMISSIONING Address Setting DIP switch S2 A-series outdoor unit PCB K1, K2 Button • Press K2 for 5 seconds to enter parameter set mode • LCD display “- - - -” • Enter the password, 0755 • Set the no. of indoor units DIP switch S1

  3. COMMISSIONING ON (1) OFF (0) ON (1) OFF (0) S2 S1 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 Reserved Capacity Outdoor Address Reserved EXV Initial Opening A-series outdoor unit PCB

  4. COMMISSIONING Address Setting B-series outdoor unit PCB DIP switch S1,S2

  5. COMMISSIONING B-series outdoor unit PCB S1 S2 S3 ON (1) OFF (0) 1 2 3 4 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 Outdoor unit capacity No. of indoor units Outdoor address EXV initial opening Cooling / Heating Master / Slave MDS _A/B

  6. COMMISSIONING Address Setting Indoor unit PCB DIP switch S2

  7. COMMISSIONING Indoor unit PCB ON (1) OFF (0) ON (1) OFF (0) 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 7 8 Auxiliary Heater 1 Auxiliary Heater 2 Reserved Address Capacity Model Water Pump

  8. COMMISSIONING LCD Display Receiver ON / OFF Temperature Up / Down Fan Mode Heater / Swing Sleep Timer Setting SLM Controller

  9. COMMISSIONING Handset Setting SLM Controller Real Timer Setting Press “CLK” Day Setting CLK * Press “Δ” or “▽” to change the day setting (Monday ~ Sunday) Press “CLK” again to confirm *Note: If no action within 5s, it will return to main page

  10. COMMISSIONING Handset Setting SLM Controller Real Timer Setting After day setting is confirmed LCD real time blink CLK * Press “Δ” to increase 1 hour Press “▽” to increase 1 minute Press “CLK” again to confirm *Note: If no action within 5s, it will return to main page

  11. COMMISSIONING Handset Setting SLM Controller • DIP1 – Temperature Unit Setting • ON - °F • OFF - °C • DIP2 – Auto Start Setting • ON - Available • OFF - N/A DIP switch

  12. COMMISSIONING Test Run • Check the power supply between outdoor unit and switch board. • 1. 220V power supply (L / N) • 2. 380V power supply • – make sure the phase sequence are correct, L1(R) L2(S) L3(T) • Outdoor unit powered ON 6 hours in advance to preheat the crankcase heater. • If main power is turned OFF for a long time, the system cannot run immediately after power resume. (Need to wait for 2.5 hours)

  13. COMMISSIONING Test Run Continue… • Indoor unit checking:- • 1. Check the power supply wiring and signal wiring in each indoor unit. • 2. If the signal wire and power wire are cross-connected, all PCB will burn. • 3. The signal wires must be in different colour for different terminal in order to avoid misconnection of polarity. • 4. Check the address setting of the indoor unit:- • – Make sure the address settings are correct. • – Each indoor unit should have different address. • Outdoor unit checking:- • 1. Check the no. of indoor unit settings are correct. • 2. Make sure the capacity settings are correct. • 3. Make sure the Master and Slave unit setting are correct (if applicable).

  14. Thank you

More Related