1 / 20

SLAC MMF PROJECT

SLAC MMF PROJECT. MECHANICAL SYSTEM DESCRIPTION. October 14, 2004. Ben Entezam. SLAC MMF Mechanical System. Ben.Entezam@Jacobs.com. SAFETY?. SLAC FLOOR LAYOUT W/ DESIGN TEMP. PARAMETERS. MMF ±0.1°C. CMM ±1.0°C. STORAGE ± 2.5°C. MECHANICAL ROOM UNIT LAYOUT. AHU-3. AHU-2. AHU-1.

astro
Download Presentation

SLAC MMF PROJECT

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SLAC MMF PROJECT MECHANICAL SYSTEM DESCRIPTION October 14, 2004 Ben Entezam SLAC MMF Mechanical System Ben.Entezam@Jacobs.com

  2. SAFETY?

  3. SLAC FLOOR LAYOUT W/ DESIGN TEMP. PARAMETERS MMF ±0.1°C CMM ±1.0°C STORAGE ± 2.5°C

  4. MECHANICAL ROOM UNIT LAYOUT AHU-3 AHU-2 AHU-1 MAU-1 AHU-1 AND MAU-1 SERVING MMF AHU-2 SERVING CMM AHU-3 SERVING LOAD DOCK

  5. ITEM NO. 1 2 3 4 5 6A 6B 7 8A 8B 9 10 11 12 13 HEAT SOURCE POWER SUPPLY MAGNET ELECTRONICS RACK COMPUTER (2) TWO ELECTRONIC RACKS LINEAR MOTOR X-Y STAGES (2) TWO ELECTRONIC RACKS LINEAR MOTOR X-Y STAGES COMPUTER COMPUTER PRINTER ELECTRONIC RACK COMPUTER (3) THREE PEOPLE TOTAL COOLING LOADS (BTU/HR) LCW WATER LCW WATER 5,115 1,705 10,230 3,410 3,410 10,230 1,783 3,410 1,705 1,705 1,705 5,115 1,705 1,023 = 52,251 1 2 3 4 6A/6B 5 5 9 7 7 8A/8B 10 12 13 MMF HEAT SOURCE LOCATION 11

  6. SUPPLY AIR TO AHU-1 OUTSIDE AIR FILTER SECTION FILTER SECTION 30% PREHEATING COIL FILTER SECTION 65% SUPPLY FAN COOLING COIL HEATING COIL HUMIDIFIER MAKE-UP AIR UNIT (MAU-1)

  7. 99,360 85,440 2,000*60*54 CFM*60*ΔG 10,000 5,000 13.5*7,000 13.5*7,000 MAKE-UP AIR UNIT (MAU-1) SUPPLY AIR 70°F 2,000 CFM OUTSIDE AIR 26°F WINTER 95°F SUMMER 2,000 CFM Q1= 1.08 * CFM * ΔT Q1 = SENSIBLE HEAT (BTU/HR) CFM = CUBIC FEET PER MINUTE ΔT = TEMPERATURE DIFFERENCE (°F) Q2= 0.68 * CFM * ΔG Q2 = LATENT HEAT (BTU/HR) CFM = CUBIC FEET PER MINUTE ΔG = GRAIN/LB DIFFERENCE (°F) PREHEATING COIL (PREHEAT) = 1.08 * 2,000 * 10 = 21,600 BTU/HR HEATING COIL = 1.08 * 2,000 * 36 = 77,760 BTU/HR COOLING COIL (Q1) = 1.08 * 2,000 * 32 = 69,120 BTU/HR (7 DEGREE MOTOR LOAD) COOLING COIL (Q2) (DEHUMIDIFICATION) = 0.68 * 2,000 * 12 = 16,320 BTU/HR (ΔG = 12) TOTAL COOLING = 69,120 + 16,320 = 85,440 BTU/HR = APPROX. 7½ TONS COOLING HUMIDIFICATION = = = 69 LBS/HR HOT WATER GPM = = 9.9 GPM ~ 10 GPM CHILLED WATER GPM = = 17 GPM

  8. AIR HANDLING UNIT (AHU-1) RETURN AIR FILTER SECTION SUPPLY FAN TEMPERED CHILLED WATER COIL TEMPERED HOT WATER COIL MAKE-UP AIR 70°F SUPPLY AIR 69.85°F

  9. 4,539 = 23,348 CFM ~ 24,000 CFM CFM = 1.08*0.18 AIR HANDLING UNIT (AHU-1) RETURN AIR 73°F 22,000 CFM MAKE-UP AIR 70°F 55%RH 2,000 CFM SUPPLY AIR 69.82°F 24,000 CFM AIR FLOW CALCULATION (INTERIOR LOADS) LIGHTING = 3,410 BTU/HR PEOPLE = 454 BTU/HR ROOF = 675 BTU/HR TOTAL = 4,539 BTU/HR SURROUNDING AREA EQUIPMENT LOADS EQUIPMENT = 52,251 BTU/HR LIGHTING = 8,000 BTU/HR ROOF = 1,000 BTU/HR TOTAL = 61,251 BTU/HR SURROUNDING AREA TEMPERATURE RISE 61,251 = 3°F ΔT = 1.08*0.7*24,000

  10. AIR HANDLING UNIT (AHU-1) CONT. RETURN AIR 73°F 22,000 CFM MAKE-UP AIR 70°F 55%RH 2,000 CFM SUPPLY AIR 69.82°F 24,000 CFM COOLING LOADS EQUIPMENT = 52,251 BTU/HR LIGHTING = 8,000 BTU/HR ROOF = 1,000 BTU/HR (0.033 * 25.1224 = 1,000 BTU/HR) FAN HEAT = 24,000 * 1.08 * 2.45 = 63,504 BTU/HR (20 HP) TOTAL = 124,755 BTU/HR / 12,000 = 10.4 TONS (TCW COIL) BTU/HR 124,755 = 83 GPM ΔT = 3°C GPM = = 500 * ΔT 1,500 HEATING LOADS REHEAT COIL = 24,000*1.08*3 = 77,760 BTU/HR (THW COIL) 77,760 ΔT=20°F GPM = = 7.7 GPM 500*20 77,760 ΔT=4°F GPM = = 38 GPM 500*4

  11. MMF FLOOR LAYOUT (DIFFUSERS)

  12. HOT WATER PUMPS TEMPERED HOT WATER PUMPS BOILER 300,000 BTU/HR CHILLEDWATER PUMPS HEAT EXCHANGER TEMPERED CHILLED WATER PUMPS CHILLER 45 TON HEAT EXCHANGER AHU-1 MAU-1 MMF FLOW DIAGRAM

  13. RETURN AIR OUTSIDE AIR FILTER SECTION 30% FILTER SECTION 65% VAV-1 VAV-2 VAV-3 VAV-4 SUPPLY FAN COOLING COIL HEATING COIL HUMIDIFIER AIR HANDLING UNIT (AHU-2) SUPPLY AIR

  14. RETURN AIR FILTER SECTION FILTER SECTION 30% FILTER SECTION 65% COOLING COIL HEATING COIL SUPPLY FAN AIR HANDLING UNIT (AHU-3) SUPPLY AIR OUTSIDE AIR

  15. AHU-3 AHU-2 HOT WATER PUMPS BOILER 300,000 BTUHR TEMPERED HOT WATER PUMPS HEAT EXCHANGER CHILLED WATER PUMPS CHILLER 45 TON TEMPERED CHILLED WATER PUMPS HEAT EXCHANGER FLOW DIAGRAM MAU-1 AHU-1

More Related