Seismic Considerations & Power Bushings

ABB Components USA. Seismic Considerations & Power Bushings. Using IEEE Standards. IEEE 693 - 1997. IEEE Recommended Practice for Seismic Design of Substations. IEEE Std 693 - 1997. Electrical Equipment for Sub Stations Based on IEEE 693-1984 Very major revision Basically a new standard

Download Presentation

Seismic Considerations & Power Bushings

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ABBComponents USA Seismic Considerations &Power Bushings Using IEEE Standards

  2. IEEE 693 - 1997 IEEE Recommended Practice for Seismic Design of Substations

  3. IEEE Std 693 - 1997 • Electrical Equipment for Sub Stations • Based on IEEE 693-1984 • Very major revision • Basically a new standard • Three Qualification Levels • Low, Moderate & High • User determines Qualification Levels djr 2/00

  4. European Standards IEC Technical Report 1463

  5. IEC Technical Report 1463 • Covers seismic qualification of power bushings • Based on static coefficient calculations • Based on cantilever withstand of bushing • Not widely accepted in North America djr 2/00

  6. IEEE 693-1997 • Performance Levels • Selection of performance Level • Requirements for bushings • Test Methods • Qualification of bushings < 161 kV • Qualification of bushings  161 kV djr 2/00

  7. Performance Levels (ground acceleration) • Low = 0.1 g, horizontal acceleration peak • Moderate = 0.5 g, horizontal acceleration peak • High = 1.0 g, horizontal acceleration peak • Vertical acceleration = 0.8 x horizontal djr 2/00

  8. Selection of Performance Level • By User of equipment • Expected ground acceleration by earthquake hazard method or … • … by seismic exposure maps and site conditions • Select Performance Level to match the expected ground acceleration djr 2/00

  9. General Requirements for Bushings • Bushings as components of larger equipment • Annex D of IEEE 693 - Transformers • Requirements depend on system voltage djr 2/00

  10. Testing for Seismic Performance Levels • Low: 0.1g, horizontal • Equipment testing not required • Moderate: 0.5 g, horizontal • Testing required (when practical with equipment size) • High: 1.0 g, horizontal • Testing required (when practical with equipment size) djr 2/00

  11. Less than 161 kV Static Pull Test Force = 2 x weight Applied horizontally at top of bushing Duration = 2 seconds 161 kV and Higher Shake Table test Time history method Test by design family Test most seismically vulnerable family member Pass = no damage & no leaking Qualification of Bushings djr 2/00

  12. Bushing Seismic Considerations • Bushing is not at ground level • Bushing acceleration is amplified by transformer structure • Bushing acceleration = 2x ground acceleration • Transformer tank: • Amplification factor = 2, or • Super Elevation factor (IEC) = 1.5 djr 2/00

  13. 2.0 g Transformer Tank Amplification Factor = 2 1.0 g djr 2/00

  14. Shake Table Testing of Bushings • Method 1 • Test at 1/2 level and • Calculate to demonstrate a 2x safety factor • Method 2 • Test at full level djr 2/00

  15. Shake Table Testing of Bushings 1/2 Test + Calculation Method • Only practical method for some large equipment • Good when structure behaves in linear fashion and is predictable • Not good for bushings because of the non-linearity of the bushing’s mechanical system, ie, gasket + porcelain + spring clamps djr 2/00

  16. Shake Table Testing of BushingsUsing 1/2 Level Test Method • For large equipment where not practical to test at full level. • Must demonstrate by calculation that equipment can withstand forces 2 times as great as test values djr 2/00

  17. Example of 1/2 Test Method(Power Transformer) • Purpose of test: demonstrate that transformer is qualified for the High Performance Level where ground acceleration = 1.0 g • Shake Table set-up at 1/2 value = 0.5 g • Use calculations to show that the test results at 0.5 g can be extended to 1.0 g djr 2/00

  18. Example of 1/2 Test Method(Transformer Bushings) • Purpose of test: • demonstrate qualification at High Performance Level • ground acceleration = 1.0 g • Bushing acceleration is 2 times ground acceleration because of tank effect • Bushing must withstand 2 x 1.0 g = 2.0 g • Shake Table set-up at 1/2 value = 1.0 g • Use calculations to show that the test results at 1.0 g can be extended to 2.0 g djr 2/00

  19. Shake Table Testing of BushingsUsing Full Test Method(Full Performance Level Test) • Purpose of test: • demonstrate qualification at High Performance Level • ground acceleration = 1.0 g • Bushing acceleration is 2 times ground acceleration because of tank effect • Bushing must withstand 2 x 1.0 g = 2.0 g • Shake Table set-up at full value = 2.0 g • Bushing directly qualified by Test • Calculations not required djr 2/00

  20. Shake Table Testing of BushingsUsing Full Test Method(Full Performance Level Test) • Moderate Level (0.5 g) • Bushing tested at 1.0 g • High Level (1.0 g) • Bushing tested at 2.0 g djr 2/00

  21. Bushing Qualification @High Level by Direct Testing 2 g djr 2/00

  22. Bushing Qualification @ ModerateLevel by Direct Testing 1 g djr 2/00

  23. Shake TableTest Set-up djr 2/00

  24. ABB Components USA • Qualify bushings based on IEEE 693-1997 • Actual shake table test used for higher voltage bushings • ABB full line of ANSI/IEEE bushings has been tested and qualified according to IEEE 693-1997 djr 2/00

  25. ABBBushing Qualification Summary • Qualified @ High - Static Pull Test • Bushings 25 kV through 138 kV • Qualified @ High - Shake Table • Bushings 161 kV through 196 kV • full test of seismically worse bushing in family • Qualified @ Moderate - Shake Table • Bushings 362 kV • full test of seismically worse bushing in family djr 2/00

  26. ABBBushing Qualification Summary • 500 kV bushing • not qualified at moderate • passed 0.45 g at flange • equivalent to 0.22 g, ground acceleration • (with tank amplification factor = 2) • failure mode (@ 0.50 g at flange) • slight leak at flange during shake test • re-sealed after test • no worse after second test djr 2/00

  27. ABB Components USA djr 2/00