diversified air systems inc firetrace technology n.
Download
Skip this Video
Loading SlideShow in 5 Seconds..
Diversified Air Systems,Inc. Firetrace Technology PowerPoint Presentation
Download Presentation
Diversified Air Systems,Inc. Firetrace Technology

Loading in 2 Seconds...

play fullscreen
1 / 9

Diversified Air Systems,Inc. Firetrace Technology - PowerPoint PPT Presentation


  • 109 Views
  • Uploaded on

Diversified Air Systems,Inc. Firetrace Technology. Call today: 800-264-8958. What is Firetrace?. Suppression for the “micro-environment” Pneumatic heat detection Fire suppression system “Total flooding” OR “Local application” Detection and suppression at the ignition point.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'Diversified Air Systems,Inc. Firetrace Technology' - satinka-herrera


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
what is firetrace
What is Firetrace?
  • Suppression for the “micro-environment”
  • Pneumatic heat detection
  • Fire suppression system
  • “Total flooding” OR “Local application”
  • Detection and suppression at the ignition point
it s all about the tube
“It’s All About the ………………TUBE”
  • Linear, pneumatic flame detection
  • Bursts at 212°F (100°C)
  • Tubing can be the detector & the piping network
  • Tubing is durable and flexible
  • Tubing is notconductive or corrosive
  • Good for harsh chemical environments
direct system
Direct System

Direct Low Pressure System

characteristics of the firetrace detection tubing
Characteristics of the Firetrace Detection Tubing
  • Commercial Name : FT 1992 Thermoplas
  • Physical Appearance: 6mm OD red tube
  • Change in Physical state: Melts @ 194 C (381.2 F)
  • Bulk Density : 17g / meter (5.18g/ft)
  • Dielectric Strength: (DIN 53481)kV/mm dry 40
  • Thermal Decomposition: Above 300 C (572 F)
  • Temperature at Burst: 100-115 C @ 150 psi
  • (212-239 F @ 150 psi)
direct low pressure dlp system
Direct Low Pressure (DLP) System
  • Tubing is used as a detector and delivery of agent from cylinder
  • Valve is a X-over only to allow for connection of the tubing to cylinder
  • 4 ports on this valve for gauge, P/S, Ball Valve and cylinder

Max 3.3 ft / layer

  • Discharge time is limited due to the x-sectional area of the ball valve orifice.
options
OPTIONS

PRESSURE SWITCH

  • Monitors pressure in the tubing and in cylinder
  • Can use one on cylinder and as many as needed on tubing network
  • Used for:
    • Building alarm tie-in
    • Power lock-out or shunt trip
    • Fan/damper control
    • Auxiliary controls