Topic I. 9. Water Supply Networks Dimensioning

Topic I. 9. Water Supply Networks Dimensioning. Determination of Design Water Flowrates (Water Quantities) Design Flows Division Take off (distributed) flow Crossover flow Fire flow. Determination of Design Water Flowrates (Water Quantities). Take off (Distributed) Flow

lam
Download Presentation

Topic I. 9. Water Supply Networks Dimensioning

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Topic I. 9.Water Supply Networks Dimensioning Determination of Design Water Flowrates (Water Quantities) Design Flows Division • Take off (distributed) flow • Crossover flow • Fire flow

  2. Determination of Design Water Flowrates(Water Quantities) Take off (Distributed) Flow • Specific water quantity - q0, l/s.m q0 = (Qmax,h - Qc)/  lr, l/s.m Qmax,h- total hourly maximal consumption of the settlement, l/s Qc - concentrated (big) consumption, l/s lr-reduced length of the pipe, m lr = .l , m l - real pipe length, m  - reducing coefficient;  = 1 at the pipes with bilateral take off along its length;  = 0,5 at the pipes with unilateral take off along its length

  3. Determination of Design Water Flowrates(Water Quantities) • Design water flowrate - Qd, l/s Qd = .q0.lr + Qcr,l/s Qcr - crossoverflowrate, l/s  - coefficient of equivalent distribution flowrate;  = 0,5 - 0,6 • Crossover flowrate -Qcr , l/s Qcr = q0 . lr + Qc + Qf, l/s Qf - fire flwrate, l/s

  4.  Qп.р - sum of the take off flows of all the pipes, fed by the one under consideration Qп.р - the current pipe take off (distributed) flow Qk - concentrated (big) take off flows, fed by the pipe under consideration Qпп - fire flow Qtp - the current pipe crossover flow Qop - design flowrate (water quantity) Design Flows Division

  5. Hydraulic Calculations Pressure Pipe Flow Parameters • Flowrate - Q • Velocity - v • Pipe diameter - D • Hydraulic gradient - I • Head losses - h • Coefficient of head losses - 

  6. (1) Continuity equation (2) Chezy equation (3) Collebrook - White equation (4) Darcy - Weisbah equation Hydraulics Relationships

  7. Pressure Pipe Dimensioning • Number of flow parameters - 6 • Necessary number of hydraulics equations - 6 • Available number of hydraulics equations - 4 • Number of flow parameters to be accepted - 2

  8. Branched Distribution Network DimensioningWithout (a) and with (b) fixed service reservoir positiona)

  9. Branched Distribution Network Dimensioning Accepted (Known) Flow Parameters I. Without fixed service reservoir position • Flowrate - known, calculated in advance according to the definite method • Velocity - accepted in a range, as follows: • mean economical velocities - v = 0,6 - 0,9 m/s for D < 300 mm; v = 0,9 - 1,5 m/s for D > 350 mm • low limit for the velocity - v > 0,3 m/s • upper limits for the velocity - v < 2 m/s, normally; v < 3 m/s, with fire

  10. Accepted (Known) Flow Parameters I. With fixed service reservoir position Flowrate - known, calculated in advance according to the definite method Mean hydraulic gradient - known, calculated through the service reservoir elevation and dynamic head at the critical point - M: Branched Distribution Network Dimensioning

  11. Branched Distribution Network Dimensioning Auxiliary Dimension Tools • Tables • Graphs • Equations - hydraulic, empirical

  12. Looped Distribution Network Dimensioning Main Approaches: I. Virtual transfer of the looped network into branched one • Definition of the flows directions (according to the branches lay out) • Calculation of the design flowrates for every pipe • Dimensioning of the pipes and calculation of the head losses • Determination of the dynamic hydraulic head spatial distribution and the service reservoir elevation (position) II.Considering the hydraulic connections in the real looped network • Preliminary definition (acceptation) of the flows directions in the network • Considering of the mass conservation low (continuity equation) at every node of the network • Considering of the energy conservation low (head losses balance) at every arbitrary chosen loop (ring) of the network

  13. Looped Distribution Network Dimensioning Continuity equation  Q = 0  Q - algebraic sum +Q - flows entering the node -Q - flows leaving the node Head losses balance  h = 0 or  s.Q = 0 s - head losses lump coefficient (Darcy - Weisbah coefficient, where  is a non-linear function of Q): If neglecting  dependence of Q, the following relationship is valid:  s.Q2 = 0

  14. Looped Distribution Network DimensioningHead losses balance • For the head losses balance keeping, a correction flowrate - q is introduced, according to the design method of Lobachev - Kross (Lobachov,1932; Hardy Cross, 1936): q = h / 2. s.Q , l/s h - head losses misbalance value at the relevant network loop (ring)  s.Q- head losses at the relevant network loop (ring) • The correction flowrate values - q for every pipe in the network are calculated applying the iterative calculation procedure over entire the network. Since both the mass and head losses balances have to be considered simultaneously at every node and loop of the network, respectively, calculations include simultaneous solution of system of N-number equations (N = number of nodes - 1, plus number of relevant loops) at every step of iteration. The number of unknown (searched for) water flowrates - Q is equal to the number of the pipes in the loop network and therefore is equal to N. The calculations are performed by means of computer and relevant software.

  15. Looped Distribution Network DimensioningHead losses balance (scheme)