An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. DISTRELAY Modeling in PowerWorld Simulator Angel Aquino, PhDWECC MVWGJune 25-26, 2014 angel@powerworld.com 217-384-6330 ext. 21

  2. Announcements • Version 18.0 released last month

  3. DISTRELAY Model • DISTRELAY will have the following functionalities to simplify and increase functionality of the distance relay model • Zone Definition / Description • Blinder Definition • Transfer Trip Scheme functionality • A separate model will exist called LOADENCROACHMENT • LOADENCROACHMENT defines the Load Encroachment region which can be used as a type of “blinder” to instruct a relay not to function

  4. Device Specification • DistRelay is assigned to a particular end of a particular Branch (line or transformer) • DeviceEndcorresponds to the bus where the relay is located at. • FarBus corresponds to the end of series of branches that this impedance relay is looking toward. • FarLineis end of series branch and is the branch where a second relay may be placed and used in the different Transfer Trip schemes. • If no FarLinedefined then FarLinewill be the branch to which the relay is assigned and FarBuswill be the terminal opposite of DeviceEnd

  5. What to Trip • Trip1, Trip2, Trip3, Trip4, Trip5 (Also a bus with each) • List of up to 5 separate branches are specified. • List a terminal bus with each branch too. • If specified only that end of the line will be opened. • If unspecified, we’ll just open both ends of the branch • NumDirect: defines which are considered a direct trip • Example: • A = Trip1; B = Trip2; C = Trip3; D = Trip4 • Number of Direct = 2 • This means that A and B are opened for a “Direct Trip” and C and D are opened for a “Transfer Trip” FarLine Branch A C B D DeviceEnd FarBus

  6. Zone Shapes • There are 3 zones. Each zone is described by 8 parameters • Shape Definitions (6 parameters) • Zone Shape: integer 0, 1, 2, or 3 • 0 = circle, lens, or tomato • 1 = rectangle • 2 = reactance distance • 3 = impedance distance • Angle : Angle • Wt: Total Width (Primary Ohms) • Rr: Reverse Reach (Primary Ohms) • InternalAngle : (Degrees: used with Shape = 0) • Rb (Primary Ohms: Only used with Shape = 1) • Time: seconds the apparent impedance must remain in zone for the zone to return TRUE • Ithres: A current threshold in single line current specified in amps.

  7. DISTRELAY Zone Shapes • 4 separate blinders are available and act to block all zones.

  8. Transfer Trip Scheme • TransferType: Integer Parameter specifying hard-coded logic on transfer trip. • All relays will operate for Zone 1 logic • For transfer trip to work, you MUST have one DISTRELAY assigned to the from bus and a second DISTRELAY assigned the other side • Tripping logic then operates on the two relay’s zones DistRelayB DistRelayA

  9. Transfer Trip Scheme • Trip Logic for DistRelayA • 1 = DUTT: ZA1 • 2 = POTT: ZA2 and ZB2 • 3 = PUTT: ZA2 and ZB1 • 4 = DCB: ZA1 and [ZA2 and (not ZB3)] DistRelayA DistRelayB ZA1 ZB1 ZB3 ZA3 ZB2 ZA2

  10. DISTRELAY Input Data

  11. DIFFRLYS Model • ASPECIFIC current differential relay model to detect a fault that sits within the zone of protection • During a dynamic simulation, the fault is applied by the user of the software so detection of the fault is not necessary which simplifies the model. • DIFFRLYScan be applied to specific branch(es) (lines and transformers) defined by the bus numbers. • The branch/es are opened accordingly with the correct timings (taken into account breaker opening times / communication delay/ detection delay) without any additional user input.

  12. DIFFRLYS Model Specific Cases

  13. DIFFRLYS Model in PowerWorld • PowerWorld will read the specified data as proposed: • Will also let the user specified up to N branches in which the relay will operate • Will write-out the data of the model as specified. • The only configurations that will be allowed are the presented in the previous slides • Ex: Branch7 Branch6 Branch4 Branch5 Branch1 Branch2 Branch3 Branch8

  14. DIFFRLYS Model in PowerWorld Branches and Buses

  15. DIFFRLYG Model • AGENERIC current differential relay model to detect a fault that sits within the zone of protection • DIFFRLYG can be applied to a set of branches (lines or transformers) that belong to a zone / area / kV range / owner. • DIFFRLYG will have the following priority when multiple area / zone / owners need to be entered but have separate timings: Priority List (from Highest to Lowest): • Area(Flag1) / Zone(Flag2) / Owner(Flag3) all specified • Zone(Flag2) / Owner(Flag3) specified • Area(Flag1) / Owner(Flag3) specified • Area(Flag1) / Zone(Flag2) specified • Owner(Flag3) specified • Zone (Flag2) specified • Area (Flag1) specified

  16. DIFFRLYG Model • Model Parameters:

  17. DIFFRLYG Model • Will be applied to the System, similar to the load models: • Ex. WSCC Load Characteristic load Model Area, Zones and Owners System-Specific relay models