SERVICIO AL CLIENTE PARA CENTROS DE ATENCIÓN TELEFONICA

MANUAL DE USUARIO SERVICIO A LA CLIENTE. SERVICIO AL CLIENTE PARA CENTROS DE ATENCIÓN TELEFONICA. Capitulo 2 Normatividad DIA 6. MANUAL DE USUARIO SERVICIO A LA CLIENTE. CAPITULO 2.6 2.6.- Especificación de Acometidas DIA 6 2.7.- Sistemas Fotovoltaicos

Download Presentation

SERVICIO AL CLIENTE PARA CENTROS DE ATENCIÓN TELEFONICA

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. MANUAL DE USUARIO SERVICIO A LA CLIENTE SERVICIO AL CLIENTE PARA CENTROS DE ATENCIÓN TELEFONICA Capitulo 2 Normatividad DIA 6

  2. MANUAL DE USUARIO SERVICIO A LA CLIENTE • CAPITULO 2.6 • 2.6.- Especificación de Acometidas DIA 6 • 2.7.- Sistemas Fotovoltaicos • Leyes y Reglamentos • 2.8.-Ley de Servicio Público de Energía Eléctrica. • 2.9.-Ley de Servicio Público en Aportaciones. • pagina 2-39 • ESPECIFICACIÓN DE ACÓMETIDAS

  3. MANUAL DE USUARIO SERVICIO A LA CLIENTE 2.6.- ESPECIFICACIÓN DE ACOMETIDASOBJETIVO:Al término de este tema el participante conocerá los diferentes tipos de conexiones utilizados en contrataciones de Baja Tensión, aéreos y subterráneos.

  4. MANUAL DE USUARIO SERVICIO A LA CLIENTE • CFE EA-BT101 ACOMETIDA PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA. • CFE EA-BT102 ACOMETIDA PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, CON CONECTOR A COMPRESION. • CFE EA-BT103 ACOMETIDA PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED SUBTERRANEA. • CFE EA-BT201 ACOMETIDA PARA SERVICIO BIFASICO CON CARGA HASTA 10 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA. • CFE EA-BT202 ACOMETIDA PARA SERVICIO BIFASICO CON CARGA HASTA 10 kW EN BAJA TENSION, RED AEREA, CON CONECTOR A COMPRESION. • CFE EA-BT203 ACOMETIDA PARA SERVICIO BIFASICO CON CARGA HASTA 10 kW EN BAJA TENSION, RED SUBTERRANEA. • CFE EA-BT301 ACOMETIDA PARA SERVICIO TRIFASICO CON CARGA HASTA 15 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA. • CFE EA-BT302 ACOMETIDA PARA SERVICIO TRIFASICO CON CARGA HASTA 15 kW EN BAJA TENSION, RED AEREA, CON CONECTOR A COMPRESION. • CFE EA-BT303 ACOMETIDA PARA SERVICIO TRIFASICO CON CARGA HASTA 15 kW EN BAJA TENSION, RED SUBTERRANEA. • |

  5. A A' ACOMETIDA PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA CFE EA-BT101 1 DE 2 VISTA DE CONJUNTO ACOMETIDA CONDUCTOR MULTIPLE CONDUCTORESDE ENTRADA 4800 4800 MEDIDOR MEDIDOR C A L L E LADO USUARIO LADO POSTE AMARRE DEL NEUTRO DE ACOMETIDA ( 3 VUELTAS) CONECTOR TIPO CUÑA 150 CONDUCTOR MULTIPLE CONECTOR TIPO CUÑA 3 VUELTAS DETALLE ”A" VISTA LATERAL DETALLE A ABRASADERA 1BD BASTIDOR B1 CORTE A-A` CONDUCTOR MULTIPLE AISLADOR CARRETE 1C CONECTOR TIPO CUÑA ACOTACIONES EN mm SIN ESCALA

  6. CFE EA-BT101 ACOMETIDA PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA 2 DE 2 MATERIALES NOTAS: a.- LA ACOMETIDA DE LADO POSTE, SE DEBE REMATAR EN EL AISLADOR 1C DEL BASTIDOR B1, INSTALADO EN LA PARTE SUPERIOR DE LA RED. b.- SE DEBE EVITAR QUE LA ACOMETIDA CRUCE TERRENOS O CONSTRUCCIONES. c.- LA ACOMETIDA DEBE TENER UNA LONGITUD MAXIMA DE 35 METROS EN AREA URBANA, Y DE 50 METROS EN EL AREA SUBURBANA Y RURAL, DISTANCIA MEDIDA EN LINEA RECTA RESPECTO AL POSTE, DE ACUERDO CON LAS ESPECIFICACIONES PARA EL SUMINISTRO DEL SERVICIO. d.- LA ACOMETIDA DE LADO USUARIO DEBE REMATAR DIRECTAMENTE EN EL TUBO DE LA PREPARACION DEL USUARIO A UNA ALTURA NO MENOR DE 4.80 METROS SOBRE EL NIVEL DE PISO. e.- EL CONDUCTOR DE COBRE SE DEBE DEJAR EN EL NIVEL INFERIOR.

  7. A A' 4800 CFE EA-BT201 ACOMETIDA PARA SERVICIO BIFASICO CON CARGA HASTA 10 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA 1 DE 2 VISTA DE CONJUNTO ACOMETIDA CONDUCTOR MULTIPLE CONDUCTORESDE ENTRADA 4800 MEDIDOR MEDIDOR C A L L E LADO USUARIO LADO POSTE AMARRE DEL NEUTRO DE ACOMETIDA ( 3 VUELTAS) CONECTOR TIPO CUÑA 150 CONDUCTOR MULTIPLE CONECTOR TIPO CUÑA 3 VUELTAS DETALLE ”A" VISTA LATERAL ABRASADERA 1BD BASTIDOR B1 DETALLE A CONDUCTOR MULTIPLE CORTE A-A` AISLADOR CARRETE 1C CONECTOR TIPO CUÑA ACOTACIONES EN mm SIN ESCALA

  8. CFE EA-BT201 ACOMETIDA PARA SERVICIO BIFASICO CON CARGA HASTA 10 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA 2 DE 2 MATERIALES NOTAS: a.- LA ACOMETIDA DE LADO POSTE, SE DEBE REMATAR EN EL AISLADOR 1C DEL BASTIDOR B1, INSTALADO EN LA PARTE SUPERIOR DE LA RED. b.- SE DEBE EVITAR QUE LA ACOMETIDA CRUCE TERRENOS O CONSTRUCCIONES. c.- LA ACOMETIDA DEBE TENER UNA LONGITUD MAXIMA DE 35 METROS EN AREA URBANA, Y DE 50 METROS EN EL AREA SUBURBANA Y RURAL, DISTANCIA MEDIDA EN LINEA RECTA RESPECTO AL POSTE, DE ACUERDO CON LAS ESPECIFICACIONES PARA EL SUMINISTRO DEL SERVICIO. d.- LA ACOMETIDA DE LADO USUARIO DEBE REMATAR DIRECTAMENTE EN EL TUBO DE LA PREPARACION DEL USUARIO A UNA ALTURA NO MENOR DE 4.80 METROS SOBRE EL NIVEL DE PISO. e.- EL CONDUCTOR DE COBRE SE DEBE DEJAR EN EL NIVEL INFERIOR.

  9. A A' 4800 CFE EA-BT301 ACOMETIDA PARA SERVICIO TRIFASICO CON CARGA HASTA 15 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA 1 DE 2 VISTA DE CONJUNTO ACOMETIDA CONDUCTORESDE ENTRADA CONDUCTOR MULTIPLE 4800 MEDIDOR MEDIDOR C A L L E AMARRE DEL NEUTRO DE ACOMETIDA ( 3 VUELTAS) LADO POSTE LADO USUARIO CONECTOR TIPO CUÑA CONDUCTOR MULTIPLE 150 CONECTOR TIPO CUÑA 3 VUELTAS DETALLE ”A" VISTA LATERAL ABRASADERA 1BD BASTIDOR B1 CONDUCTOR MULTIPLE DETALLE A CORTE A-A` AISLADOR CARRETE 1C CONECTOR TIPO CUÑA ACOTACIONES EN mm SIN ESCALA

  10. CFE EA-BT301 ACOMETIDA PARA SERVICIO TRIFASICO CON CARGA HASTA 15 kW EN BAJA TENSION, RED AEREA, CON CONECTOR TIPO CUÑA 2 DE 2 MATERIALES NOTAS: a.- LA ACOMETIDA DE LADO POSTE, SE DEBE REMATAR EN EL AISLADOR 1C DEL BASTIDOR B1, INSTALADO EN LA PARTE SUPERIOR DE LA RED. b.- SE DEBE EVITAR QUE LA ACOMETIDA CRUCE TERRENOS O CONSTRUCCIONES. c.- LA ACOMETIDA DEBE TENER UNA LONGITUD MAXIMA DE 35 METROS EN AREA URBANA, Y DE 50 METROS EN EL AREA SUBURBANA Y RURAL, DISTANCIA MEDIDA EN LINEA RECTA RESPECTO AL POSTE, DE ACUERDO CON LAS ESPECIFICACIONES PARA EL SUMINISTRO DEL SERVICIO. d.- LA ACOMETIDA DE LADO USUARIO DEBE REMATAR DIRECTAMENTE EN EL TUBO DE LA PREPARACION DEL USUARIO A UNA ALTURA NO MENOR DE 4.80 METROS SOBRE EL NIVEL DE PISO. e.- EL CONDUCTOR DE COBRE SE DEBE DEJAR EN EL NIVEL INFERIOR.

  11. 4800 CFE EA-BT102 ACOMETIDA PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, CON CONECTOR A COMPRESION 1 DE 2 VISTA DE CONJUNTO ACOMETIDA CONDUCTOR MULTIPLE CONDUCTORESDE ENTRADA 4800 MEDIDOR MEDIDOR C A L L E LADO POSTE LADO USUARIO AMARRE DEL NEUTRO DE ACOMETIDA ( 3 VUELTAS) CONECTOR A COMPRESION 150 CONDUCTOR MULTIPLE CONECTOR A COMPRESION DETALLE "A" 3 VUELTAS VISTA LATERAL DETALLE A ABRASADERA 1BD CONDUCTOR DE ALUMINIO(ACOMETIDA) BASTIDOR B1 CONDUCTOR MULTIPLE CONECTOR A COMPRESION DE TENSION MINIMA AISLADOR CARRETE 1C CONDUCTOR DE COBRE USUARIO (A LA BASE ENCHUFE) ACOTACIONES EN mm SIN ESCALA CONECTOR DE COMPRESION

  12. CFE EA-BT102 ACOMETIDA PARA SERVICIO MONOFASICO CON CARGA HASTA 5 kW EN BAJA TENSION, RED AEREA, CON CONECTOR A COMPRESION 2 DE 2 MATERIALES NOTAS: a.- LA ACOMETIDA DE LADO POSTE, SE DEBE REMATAR EN EL AISLADOR 1C DEL BASTIDOR B1, INSTALADO EN LA PARTE SUPERIOR DE LA RED. b.- SE DEBE EVITAR QUE LA ACOMETIDA CRUCE TERRENOS O CONSTRUCCIONES. c.- LA ACOMETIDA DEBE TENER UNA LONGITUD MAXIMA DE 35 METROS EN AREA URBANA, Y DE 50 METROS EN EL AREA SUBURBANA Y RURAL, DISTANCIA MEDIDA EN LINEA RECTA RESPECTO AL POSTE, DE ACUERDO CON LAS ESPECIFICACIONES PARA EL SUMINISTRO DEL SERVICIO. d.- LA ACOMETIDA DE LADO USUARIO DEBE REMATAR DIRECTAMENTE EN EL TUBO DE LA PREPARACION DEL USUARIO A UNA ALTURA NO MENOR DE 4.80 METROS SOBRE EL NIVEL DE PISO. e.- EL CONDUCTOR DE COBRE SE DEBE DEJAR EN EL NIVEL INFERIOR.