1 / 9

Bulk liquid CO 2 Release Incident

This incident report covers a CO2 leak from a bulk liquid tank at a McDonald's restaurant, including information on CO2 properties, leak detection, emergency shut-off valves, and operational considerations.

Download Presentation

Bulk liquid CO 2 Release Incident

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Bulk liquid CO2 Release Incident McDonald’s Restaurant Incident 12-26-2018 07:59:02 3316 132nd St SE / Mill Creek WA 98012 31D07 2018-00011012 – Carbon Monoxide Alarm (COA)

  2. 3316 132nd St SE, Mill Creek

  3. Door that leads to the CO2 tank.

  4. CO2 properties • Heavier than air: vapor density of 1.53 • Boiling point: -109°F • Simple asphyxiant: displaces oxygen • 1lb of liquid CO2 makes 8.7719 ft3 of gaseous CO2 • OSHA PEL: 5,000 PPM • OSHA IDLH: 40,000 PPM

  5. Bulk liquid tank located inside of McDonald’s • 750 lbs. of liquid CO2 stored in tank • 750lb. x 8.7719 (ft3 /lb.) = 6578 ft3 of 100% CO2 • IDLH is 40,000 PPM or 4% CO2 • Just a 2% CO2 concentration can RR 50% • This tank has the ability to fill store with CO2 above the IDLH.

  6. Leak Detection • Bulk liquid CO2 tanks above 100 lbs. shall have: • approved continuous ventilation; or • approved emergency gas detection alarm system.* • Gas detector requirements: • Local alarm to activate at 5,000 PPM • Detector is mounted near tank at floor level, (<12 inches) • CO2 is 50% heavier than air

  7. Emergency gas detection alarm system Frost on tank indicates system leak or heavy usage.

  8. Emergency shut-off valves • Located on the top of the tank (yellow valves). • Shut valves and ventilate building. • Natural ventilation can be considered due to the gas being heavier than air. • With the doors open, CO2 will flow out of the building. • Below grade leaks: use different tactics.

  9. Operational Considerations • Not all carbon dioxide leaks will be properly reported or dispatched • Full PPE with SCBA required until proven unnecessary • Inspector 31 has a Draeger CO2 detector for definitive evaluation (OK to add Inspector 31 to the incident