1 / 13

Integrated Controller V series model 1000 & LC500 Introduction

Model 3000. Model 1 000. Model 2 000. Integrated Controller V series model 1000 & LC500 Introduction. Flexible modular-based solution for small applications. Automation Group August 2002. Rev.1 on Aug 1 2002. I/O: Analog input: 4 points Digital input: 3 points

gil
Download Presentation

Integrated Controller V series model 1000 & LC500 Introduction

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Model 3000 Model 1000 Model 2000 Integrated Controller V series model 1000& LC500 Introduction Flexible modular-based solution for small applications Automation Group August 2002 Rev.1 on Aug 1 2002

  2. I/O: • Analog input: 4 points • Digital input: 3 points • MV output: 1 point • Analog output: 2 points • Digital output: 3 points New One-loop controller LC500 • A unified display function and Intelligent I/O based on model 1000 • IEC61131-3 V-Series engineering tool • High-speed redundant optical loop TOSLINE-S20LP One loop controller LC500 2 / Integrated Controller V series model 1000

  3. Max. 8 loops RS485 RS485 RS485 LC511/512 LC511/512 5 5 5 1 1 1 2 2 2 H H H 5 5 5 1 1 1 2 2 2 H H H 5 5 5 1 1 1 2 2 2 H H H 5 5 5 1 1 1 2 2 2 H H H 5 5 5 1 1 1 2 2 2 H H H 5 5 5 1 1 1 2 2 2 H H H 5 5 5 1 1 1 2 2 2 H H H L L L o o o o o o p p p 2 2 2 L L L o o o o o o p p p 3 3 3 L L L o o o o o o p p p 4 4 4 L L L o o o o o o p p p 5 5 5 L L L o o o o o o p p p 6 6 6 L L L o o o o o o p p p 7 7 7 L L L o o o o o o p p p 8 8 8 IOBUS IOBUS RS485 RS485 Intelligent PI/O Max. 15 modules Multi-loops system Side keyboard I/O terminal block Side keyboard New One-loop controller LC500 • Flexible addition and integration of loops • Max. 8 PID loop control • Multi -loops system • Display unit and I/O can be extended • Side keyboard • Parameter display and setup on the site • New Instrument Function Block and Model Driven - PID Control • Supported 3 / Integrated Controller V series model 1000

  4. Model 1000 Summary • Entry model for V series product line. • Offers variety of solutions • Loop-controller solution for up to 8 physical PID loops • Data logging solution for up to 128 analogs • Inputs - 4-20mA, 1-5V, mV, Thermocouple, RTD, pulse • Sequence control for up to 96DI plus 96DO • Combination of loop, monitoring and sequence. • Remote I/O up to 1km (3,280 feet) • Traditional Loop Display available • Tag-based Process-Control-like Engineering • Common engineering tool over the whole V series product line • Function block and ladder diagram available • Tag-based I/O database configuration 4 / Integrated Controller V series model 1000

  5. Conventional panel-instrumentation-based operation One loop display shared by multiple loops Model 1000 with Loop Display Interface PS591 PS591 PS591 PS591 PS591 L1PU11 L1PU11 L1PU11 L1PU11 L1PU11 V V V V V 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 100.0 C C C C C C C C C C C C A A A A A A A A A A A A M M M M M M M M M M M M One loop configuration per each unit Up to 8 loop display units connected to CPU for operation in parallel. One loop display unit can switch indication among up to 8 loops in CPU 5 / Integrated Controller V series model 1000

  6. LCD Touch Panel for graphically aided operation Network among Graphic Display Integration with PC package Model 1000 with Touch Panel Graphic Display DATA LOGGER Ethernet LOCAL OPERATOR INTERFACE PROGRAMMABLE OPERATOR INTERFACE PROFACE GP377 http://www.pro-face.com/product/gp/gp377/gp377.htm FURNACE TEMP. CONTROL SV2 400 SV1 600 PV2 401 PV1 597 L1PU11 L1PU11 PS591 PS591 V V Network via Touch panel with PC LCD touch panel display for GUI (Graphical User Interface) based operation 6 / Integrated Controller V series model 1000

  7. Model 1000 with Human Interface Integration Real DCS-oriented Human Interface Remote I/O up to 1km(3,280 Feet). Integration with model 2000 and/or model 3000 OIS-DS OIS-DS L1PU11 L1PU11 L1PU11 PS591 PS591 PS591 EN531 EN531 EN531 PS692 DI635 EN631 S2PU72 DI635 DO635 DO635 V V V V Model 2000 Model 1000 100.0 Model 1000 C 1km (3,280 Feet) A M Model 1000 Remote I/O Ethernet 7 / Integrated Controller V series model 1000

  8. Model1000 vs EC321 loop controller Model 1000 has more flexibility in configuration and maintenance. 8 / Integrated Controller V series model 1000

  9. Configuration 001: Remote Hybrid I/O Application Remote I/O connection up to 1km(3,280 Feet). Hybrid I/O module to handle a variety of signals at every location. Ethernet link to HMI package L1PU11 EN531 V Ethernet link For HMI linkage Remote Hybrid I/O 4 1-5V in 1 4-20mA out 2 1-5V out 3 digital in 3 digital out Ethernet Model 1000 Twisted pair Cable up to 1km (3,280 Feet) Total 9 / Integrated Controller V series model 1000

  10. Configuration 002: Remote Temperature Data Logging Remote I/O connection up to 3,280 Feet. Intelligent RTD I/O module configurable on engineering tool RS-485 computer link for economical solution L1PU11 V RS-485 link For HMI connection Intelligent RTD I/O For Scaling& Linearization 4 RTD inputs Model 1000 Twisted pair Cable up to 1km (3,280 Feet) Total 10 / Integrated Controller V series model 1000

  11. 8 RTD inputs, 8 1-5Vdc inputs, 8 4-20mA output, 32 DIs, 32DOs on a DIN-rail controlled by one CPU. Integration with multiple control stations. HMI connection via Ethernet. Configuration 003: Hybrid Control Station L1PU11 L1PU11 PS591 PS591 EN531 EN531 PS692 DI635 EN631 S2PU72 DI635 DO635 DO635 V V V Ethernet Model 2000 Model 1000 Model 1000 11 / Integrated Controller V series model 1000

  12. Configuration 004: Pipeline Instrumentation Hybrid input/output module for signals around pump station. Conventional loop display for local monitoring & operation User-defined function block for ease of ‘repeat configuration’ L1PU11 V 100.0 C A M 12 / Integrated Controller V series model 1000

  13. Model 1000 Options PS591 100.0 C A M 24Vdc power supply Loop display Engineering Tool 13 / Integrated Controller V series model 1000