Intelligent Control Panel SLC

Intelligent Control Panel SLC. Branch Line Resistor from End of Line to FACP Shall Not Over 50 ohms per Branch. M. M. M. M. M. M. M. M. M. FACP. NFPA Style 4 SLC. 5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG). Twisted Unshielded Pair 12 to 18 AWG SLC Distance

Download Presentation

Intelligent Control Panel SLC

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Intelligent Control Panel SLC

  2. Branch Line Resistor from End of Line to FACP Shall Not Over 50 ohms per Branch M M M M M M M M M FACP NFPA Style 4 SLC 5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG) Twisted Unshielded Pair 12 to 18 AWG SLC Distance 12 AWG 3810 M 16 AWG 1828 M 14 AWG 2895.6 M 18 AWG 1127 M

  3. Isolator Application - Style 4 Riser Max 25 standard devices between Isolators

  4. M M M M M M M M M NFPA Style 6 SLC Loop Resistor from End of Line to FACP Shall Not Over 50 ohms 5000 ft ( 1500 M) for Shield Twisted Pair Cable (12 to 18 AWG) Twisted Unshielded Pair 12 to 18 AWG SLC Distance 12 AWG 3810 M 16 AWG 1828 M 14 AWG 2895.6 M 18 AWG 1127 M

  5. Isolator Application - Style 6 Max 25 standard devices between Isolators

  6. M M M M M M M M M Style 6 with Isolators

  7. (+) SLC Channel A no connection (-) SLC Channel A NFS-320 / 640 / 3030 / NFS2-640 / NFS2-3030 Floating Shield

  8. SLC Data Formats FlashScan is an algorithm that greatly enhances the speed of communication between the Analog intelligent devices. If one of the devices within a single group has new information, The panel CPU stops the group poll and concentrates on single points. The net effect is a response speed greater than five times that of earlier designs.

  9. LED Operation

  10. A Signaling Line Circuit can contain a variety of devices, each with a specific function to perform. Intelligent Detectors to identify a variety of threat conditions – various smoke levels, heat, etc. Addressable Modules to interface the system to conventional input/output circuits and devices – notification appliances, smoke detectors, waterflow and supervisory devices, etc. Addressable Pull Stations for manual alarm activation. These devices actually contain an Addressable Module inside. Loop Isolators to prevent total loop failure from a SLC short. SLC Loop Devices

  11. FlashScan Intelligent Detectors • FSP-851 Intelligent Photoelectric Detector. • FSP-851T Intelligent Photo/Thermal Detector. • FAPT-851 Acclimate™ Intelligent Photoelectric/Thermal Detector. • FSI-851 Intelligent Ionization Detector. • FST-851 Intelligent Thermal Detector. • FST-851R Intelligent Rate-of-Rise Thermal Detector. • FST-851H Intelligent High-Temperature Thermal Detector. • FSD-751PL Intelligent Duct Photo Detector - Low-Flow • FSD-751RPL Intelligent Duct Photo Detector with Relay - Low-Flow • FSH-751 Intelligent HARSH (Hostile Area Smoke Head) Detector. • FSL-751 Intelligent Laser Detector, low profile. • Base Options: • B501 Intelligent Detector Base without flange. • B501BP Intelligent Detector Bases, without flange – 10 pack. • B710LP Intelligent Detector Base with flange. • B710LPBP Intelligent Detector bases with flange – 10 pack. • B501BH Intelligent Sounder Base/Assembly. • B501BHT Intelligent Temporal Sounder/Base Assembly. • B224BI Intelligent Isolator base. • B224RB Intelligent Relay base. • B710HD Intelligent Base for the HARSH Detector.

  12. FlashScan Monitor Modules • FMM-1 Addressable Monitor Module. Monitors normally-open contact type devices on either a Class A or Class B circuit. • FDM-1 Addressable Dual Monitor Module, 2 Class B circuits for normally-open contact type devices. • FZM-1 Addressable Monitor Module for compatible two-wire conventional smoke detectors. • FMM-101 Addressable Mini Module. Monitors a single normally-open contact type device on a Class B connection. FMM-1 The FMM-101 can be mounted inside the enclosure of a single monitored device.

  13. FlashScan Control Modules • FCM-1 Addressable Control Module. Configured for one NFPA Style Y (Class B) or Style Z (Class A) circuit. 24 VDC power must be supplied. 3-amps max. • FRM-1 Addressable Relay Module. Provides two Form-C dry contacts that switch together (DPDT). Use for elevator recall, damper control, door holding, auxiliary control functions, etc. • FTM-1 Addressable Firephone Control Module.**Compatible with NFS-3030 and NFS-640 with FlashScan Software Ver. 2.0, Ver. 3.0 respectively. FCM-1

  14. XP10-M - 10 Class B or Five Class-A Initiating Device Circuits for normally open alarm contact devices. XP6-MA - Six Class B or Three Class A Initiating Device Circuit Module for Monitoring UL Listed two-wire smoke detectors (requires filtered, resettable 24 volts.) Mounts in BB-XP backboxes – two modules, surface mount. Mount up to six modules on a CHS-6 chassis. Addressable Multiple Input Modules XP6-MA

  15. XP6-C Transponder Control Module. six Notification Appliance Circuits, Class A or B. SYNC-1 Synchronization daughter module for XP6-C using System Sensor appliances. XP6-R Transponder Relay Module. Six Form-C Dry Contact Relays. Mounts inBB-XPbackboxes – two modules, surface mount. Addressable Multiple Output Modules XP6-C

  16. Key Resettable Dual Action. Can be opened without initiating an alarm condition! Addressable Mini-Module mounted inside station. Polling LED viewable through front handle. NBG-12LX Addressable Pull Station Addressable FlashScan Module

  17. Isolator Modules • ISO-X SLC Loop Isolator Module. Isolates against short circuits on the SLC.

  18. 9 0 8 7 9 6 10 5 11 8 4 1 12 3 13 2 7 1 14 2 0 15 TENS 8 7 9 6 5 6 3 4 3 2 5 4 1 0 ONES ADDRESS LOOP FlashScan Modules Break-off address stop for panels with FlashScan Mode.

  19. 1 2 3 4 Devices - Modules • Isolator Module (ISO-X) • Supervises loop wiring for short circuit conditions • Allows critical component functions • Required for Style 7 operation • Supported by FlashScan and CLIP systems

  20. 9 0 8 1 7 2 8 7 9 6 8 10 6 5 6 3 11 4 4 12 3 2 5 13 4 2 0 1 14 ONES 0 15 TENS ADDRESS LOOP FDM-1 Wiring Class B Style B The circuit connected to terminals 6 & 7 are assigned the base address. The circuit connected to terminals 8 & 9 are assigned the base address plus 1. RED LED lights for either circuit 1 or circuit 2 alarm.

  21. Wiring an NBG-12LX Pull Station + SLC - + SLC -

  22. Building 2 Building 1 P P P = Primary S= Secondary S P S P Wiring Surge Suppressor

  23. Any Questions?