FG with >12 Consecutive Intervals Violating

FG with >12 Consecutive Intervals Violating. 2 nd Quarter VRL Report 2012. Gentry Tubbs gtubbs@spp.org. TEMP38_17974. Violation Intervals: 4/2/2012 11:40– 4/2/2012 13:20 Cause of Violation :

aidan-king
Download Presentation

FG with >12 Consecutive Intervals Violating

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. FG with >12 Consecutive Intervals Violating 2nd Quarter VRL Report 2012 Gentry Tubbs gtubbs@spp.org

  2. TEMP38_17974 • Violation Intervals: 4/2/2012 11:40– 4/2/2012 13:20 • Cause of Violation : Loading was caused by an outage south of Kansas City. The outage lasted from 4/2/2012 – 4/20/2012. • Monitored Element:  PLTCTY – KCI 161kV     LN 11017 • Contingent Element: ST_JOE – HAWTHORN 345KV LN HAWTHO_ST_JOE1

  3. KSGHALWICREN • Violation Intervals: 4/2/2012 12:35 - 4/2/2012 14:05 • Cause of Violation: Loading was cause by an outage in the Oklahoma-Kansas area. The outage was Monday 4/2/2012 at 08:24 am during high South North flow on system.

  4. LAKALASTJHAW • Violation Intervals: 4/2/2012 13:35 – 4/2/2012 14:35 • Cause of Violation: Loading was caused by an outage south of Kansas City. The outage lasted from 4/2/2012 – 4/20/2012.

  5. TEMP03_17735 • Violation Intervals: 4/26/2012 17:45 – 4/26/2012 19:00 • Monitored Element: Flat Ridge - Harper 138kV Contingent Element: Spearville - Mullegren 230kV • Cause of Violation: Wind volatility                 

  6. SSHWALDOLXFR • Violation Intervals: 4/30/2012 12:20 – 4/30/2012 13:55 • Cause of Violations: Units off dispatch    

  7. TEMP15_18082 • Violation Intervals: 5/7/2012 6:45 – 5/7/2012 7:50 • Monitored Element: GRDA17 - Tonnece 345kV Contingent Element: Chambers - Clarksville 345kV • Cause of Violations: Loading was caused by a difference in ratings. The ratings were corrected and this issue went away.

  8. OKMHENOKMKEL • Violation Intervals: 5/21/2012 14:05 – 5/21/2012 15:30 • Causes of Violations: Loading was caused by generator outages south of the flowgate. One large unit tripped unexpectedly as well as other planned outages.

  9. TEMP66_18169 • Violation Intervals: 5/29/2012 14:00 – 5/29/2012 15:00 • Monitored Element: Brookline XFMR 345/161kV #2 Contingent Element: Morgan – Huben 345kV • Cause of Violations: Loading was caused by an outage in the area.

  10. TEMP13_18068 • Violation Intervals: 5/30/2012 9:15 – 5/30/2012 10:15 • Monitored Element: AES5 - TARBY1 161KV LN:9127 Contingent Element: AES5 - BONTP 161KV LN:AES5___BONTP_1 • Cause of Violations: Nearby resource changed from Self Scheduled to Available and was dispatched down by the Market, clearing the violation.