1 / 17

Resource Control Performance Measure

Resource Control Performance Measure. A Continuous Measure of Delivery of Primary Frequency Response. By: Sydney Niemeyer NRG Energy. Resource Control Performance. One minute Average Data of Grid Frequency and the Resource’s Control Error (RCE).

katy
Download Presentation

Resource Control Performance Measure

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Resource Control Performance Measure A Continuous Measure of Delivery of Primary Frequency Response. By: Sydney Niemeyer NRG Energy

  2. Resource Control Performance • One minute Average Data of Grid Frequency and the Resource’s Control Error (RCE). • Control Error = Actual Generation minus Expected Generation. • Expected Generation = Updated Base Point + Regulation Deployment + Expected Primary Frequency Response (EPFR). • EPFR based on Resource droop and dead-band setting.

  3. RCPS1 Formula [ 2 – (RCE x Delta Hz)/(-10 x BiasResource) ] x 100 (Epsilon1)2 Delta Hz = Grid Frequency – Scheduled Frequency RCE = Resource Control Error BiasResource= Resource Seasonal Capacity/(60 x Droop x (-)10) Where Droop = 5% = 0.05 Epsilon1 = Current Grid Annual RMS1 of Frequency.

  4. Grid Frequency Epsilon 1 = 0.0300 Hz BiasResource = -20 MW/0.1 Hz

  5. Grid Frequency Epsilon 1 = 0.0300 Hz BiasResource = -20 MW/0.1 Hz 188.89 155.56 100.00 22.22 -77.78

  6. Grid Frequency Epsilon 1 = 0.0300 Hz BiasResource = -20 MW/0.1 Hz

  7. Grid Frequency Epsilon 1 = 0.0175 Hz BiasResource = -20 MW/0.1 Hz

  8. Grid Frequency Epsilon 1 = 0.0175 Hz BiasResource = -20 MW/0.1 Hz 167.35 69.39 -93.88 -322.45 -616.33

  9. Grid Frequency Epsilon 1 = 0.0175 Hz BiasResource = -20 MW/0.1 Hz

  10. Example Generator Responding to Grid Frequency One minute average frequency and MW data.

  11. Example Generator Responding to Grid Frequency – Hour Resource CPS 1

  12. Determining Resource CPS 1 of a Single Non-Responsive Resource – Zero Delivery of Frequency Response

  13. Actual RCPS1 for the Hour of any Non-Responsive Resource – MW Output Exactly on Target But No Frequency Response -19.678 RCPS1 value sets the Zero Delivery point for all Resources for This Hour.

  14. Calculating Resource Frequency Response Delivery During This Hour From our Example: (258.4 – (-)19.678) X 100 = (200 – (-)19.678) 278.078 X 100 =126.58 % 219.678 -3.25 MW/0.1 Hz X 126.58 % = -4.114 MW/0.1 Hz Average Frequency Response Delivery during this hour.

  15. Summary • Average delivery of Primary Frequency Response can be measured on a continuous bases. • Once known, the MW movement due to providing Primary Frequency Response can also be calculated (mileage). • The CPS calculation weights the evaluation when frequency is off schedule the furthest, when response is most important.