1 / 24

Aerobiological Simulations Using Arc 1

Aerobiological Simulations Using Arc 1. Dr Cath Noakes ; Dr Andy Sleigh; Dr Carl Gilkeson; Dr Miller Camargo -Valero; Dr Amir Khan. Outline. Airborne pathogens and natural ventilation Experimental study Computational Fluid Dynamics Results Conclusions. PaCE Institute.

jabir
Download Presentation

Aerobiological Simulations Using Arc 1

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Aerobiological Simulations Using Arc 1 Dr CathNoakes; Dr Andy Sleigh; Dr Carl Gilkeson; Dr Miller Camargo-Valero; Dr Amir Khan

  2. Outline • Airborne pathogens and natural ventilation • Experimental study • Computational Fluid Dynamics • Results • Conclusions

  3. PaCE Institute • Pathogen Control Engineering Institute (PaCE) directed by Dr Cath Noakes, School of Civil Engineering. • Aerobiology and Infection Control • Experimental • Computational www.engineering.leeds.ac.uk/pace

  4. Airborne Pathogens • Great threat to human health: • Swine flu campaign… • Effective ventilation can reduce • Spanish Influenza (1918-1920) 50 - 100 million deaths • Asian flu (1957-1958) 1.5 - 2 million deaths • infection risk in indoor • environments.

  5. Natural Ventilation 1900 1910 • Nightingale wards characterised by: • High ceilings, Large windows for natural ventilation. • Many of these wards exist within the UK.

  6. St. Lukes Hospital Open ward Partitioned Anemometer

  7. Ventilation Tests – Pulse Injection 3 x latex balloons CO2 sensors

  8. Measured Ventilation Rates • Typical Results: Delayed peak Low wind speed 0.4 m/s ACH = 2/h (~30 m3/h) Decay – fresh air mixing High wind speed 5.0 m/s ACH = 30/h (~450 m3/h) Pulse

  9. Flow Visualisation: Inlet • Turbulence • Pulsating flow of varying duration • Ingestion followed by extraction

  10. Flow Visualisation: Outlet • Less turbulent • Controlled extraction • Efficient even for small wind speeds

  11. Flow Visualisation: Internal • High-velocity air entry • Rapidly decaying air velocities • Range of length and time scales

  12. Modelling Challenges • Natural ventilation unpredictable, flows are time-dependent, turbulent and reliant on ambient weather conditions. • Simulations in large 3D air volumes are computationally expensive. • Necessitates a steady-state approach – transient simulations unfeasible. • Boundary conditions (inlets/outlets/walls) require careful consideration.

  13. Computational Fluid Dynamics • CFD is a powerful tool for indoor airflow simulations. • Utilizes the speed and power of computers to solve governing fluid flow equations. Step 1 = CAD Step 2 = Mesh Step 3 = Solve...

  14. 2D Coupled Flow Velocity contours 2 m/s Pressure contours 2 m/s

  15. 3D Model 1.3 M 3.3 M 9.9 M

  16. 3D Model – Open-plan Ward

  17. 3D Model – Partitioned Ward

  18. Pathogen Transport Tests

  19. Windward Release – Experiment P3 P2 HW2 Source HW1 P1 • Open ward: Even spread, dilution. • Partitioned ward: Cross infection reduced (P1, P2), higher concentrations in central bays .

  20. Windward Release – CFD Open-ward Partitioned-ward Mixing smears the pathogen Pathogen contained

  21. Leeward Release – Experiment P1 HW1 HW2 Source P3 P2 • Open ward: Even spread, average 15% reduction. • Partitioned ward: Lower average infection risk. Concentration 76% lower for healthcare worker by source.

  22. Leeward Release – CFD Open-ward Partitioned-ward Efficient extraction, prevents spread of infection Partition channelling effect hinders progress of pathogen

  23. Conclusions • CFD simulations complement the experimental results. • Qualitative and quantitative comparison good, further model validation required. • Arc1 facilitates significantly improvement compared with previous machines (Abax, Everest, White Rose Grid). • Simulation times up to 4 x faster. • Larger and more complex problems can now be undertaken: • Time-dependent simulations. • Higher-fidelity models (more cells) • Enables computation on ever larger air indoor air spaces such as hospitals/offices.

  24. Thank you for Listening Questions?