1 / 176

Tanks Essentials Organic Liquid Above-Ground Storage Tank Basics

Tanks Essentials Organic Liquid Above-Ground Storage Tank Basics. Jim Miller, P.E. Senior Environmental Engineer Delek US, Big Spring Refinery Jim.Miller@delekus.com. Bart Leininger, P.E. Principal Ashworth Leininger Group Camarillo, CA.

hisa
Download Presentation

Tanks Essentials Organic Liquid Above-Ground Storage Tank Basics

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Tanks EssentialsOrganic Liquid Above-Ground Storage Tank Basics Jim Miller, P.E. Senior Environmental Engineer Delek US, Big Spring Refinery Jim.Miller@delekus.com Bart Leininger, P.E. Principal Ashworth Leininger Group Camarillo, CA Special Note: Credit for the tank design diagrams and information used in this presentation is given to Rob Ferry, TGB Partnership and associated content used under the permission of the 4C Conference.

  2. Objectives • Exposure to Tank Design Parameters • Understand Source Emissions Driving Forces and Calculation Basics • Evaluate Standard Practices for Emission Rate Determination • Introduction to Federal Regulatory Requirements

  3. Tank Categories API 650 • 0 to 2.5 psig, “atmospheric tanks” API 620 • Up to 15 psig, “low-pressure tanks” ASME Boiler and Pressure Vessel Code, Section 8 • Above 15 psig, “pressure vessels”

  4. Tank Design • Types of Above-Ground Organic Liquid Storage Tanks • Fixed-roof, IFR, EFR, Domed EFR • Types of Floating Roofs • IFR/EFR, bolted/welded, contact/noncontact • Floating Roof Design Details • Deck Seams, Rim Seals, Fittings

  5. Types of Above-Ground Storage Tanks • Fixed-roof • Fixed roof at the top of the shell; no floating roof • Internal floating roof (IFR) • Fixed roof and a light-duty floating roof • External floating roof (EFR) • Open top (no fixed roof), with a floating roof • Covered (Domed) external floating roof • Fixed roof and an external-type floating roof

  6. Fixed-Roof Tanks • No floating roof • Liquid surface is free to evaporate into the headspace • Typically low-profile cone roof supported with columns • Requires interior supports, frangible joint • Vented to the atmosphere • Open vents (gooseneck) or P/V breather vents

  7. Fixed-Roof Tanks

  8. Fixed-Roof Tank Driving Forces for Emissions: Working Losses

  9. Fixed-Roof Tank Driving Forces for Emissions: Standing Losses

  10. Fixed-Roof Tank Failures

  11. Fixed-Roof Tank Failures

  12. Fixed-Roof Tank Failures

  13. Fixed-Roof Tank Failures

  14. Internal Floating-Roof Tanks (IFRTs) • Floating roof covers the liquid surface • Greatly reducing free evaporation into the headspace • Fixed roof is freely vented • For maintaining vapors << LEL (unless gas blanketed) • Floating roof deck is lightweight, per API 650, App. H • Protection by the fixed roof allows lightweight design • Some vapors escape past the floating roof • At rim seals, deck fittings, & deck seams (if bolted)

  15. Internal Floating-Roof Tanks

  16. IFRT Summary • Deck construction can be lightweight • Short sleeves (housings) for deck support legs • Deck seams may be bolted (typ. for aluminum) • Fixed roof may require support columns • Which penetrate the deck, creating paths for emissions • Wind is not a factor in emissions • Vapors escape past the floating roof independent of ambient wind speed, and daily breathing results in enough air movement to carry vapors out of the tank

  17. External Floating-Roof Tanks (EFRTs) • Floating roof covers the liquid surface • Greatly reducing free evaporation • Fixed roof is subject to wind action • Tank shell provides a partial shield, but losses still wind driven • Floating roof deck is heavyweight, per API 650, App. C • Designed for external forces (e.g., snow, torrential rain) • Some vapors escape past the floating roof • At rim seals, deck fittings (but deck seams are welded)

  18. External Floating-Roof Tank

  19. EFRT Summary • Deck construction is heavyweight • Tall sleeves (housings) for deck support legs • Welded deck seams • No fixed roof; no support columns • Typically fewer deck penetrations than for an IFRT • Wind is a factor in emissions • The rate at which vapors escape past the floating roof is very sensitive to ambient wind speed • Wind action offsets lower loss factors, fewer fittings

  20. Covered (Domed) External Floating-Roof Tanks • Differs from IFRT in the type of floating roof • EFR-type deck, w/ welded deck seams, tall leg sleeves • Fixed roof is freely vented (as for IFRT) • Typically an aluminum dome over an EFRT • Particularly for retrofit applications, where a dome can be installed in-service • Could be a steel cone roof, but this would typically involve installing out-of-service, roof support columns

  21. Covered (Domed) External Floating-Roof Tank

  22. Domed External Floating-Roof Tank Summary • Deck construction is heavyweight • Tall sleeves (housings) for deck support legs • Welded deck seams • Typically with dome roof; no columns • Means typically fewer deck penetrations than for an IFRT • Wind is not a factor in emissions • Lower loss factors, fewer fittings, and not subject to wind action – lowest emitting type of construction.

  23. Floating Roof Tank Driving Forces for Emissions: Working Losses

  24. Floating Roof Tank Driving Forces for Emissions: Standing Losses

  25. Floating Roof Features • Emissions sources • Withdrawals • Deck Seams (bolted decks only) • Rim Seals • Deck Fittings • Controls • Rim Seals • Deck Fittings

  26. Types of Floating Roof Decks

  27. Floating Roof Cutaway

  28. Pan Deck

  29. Bulkheaded Deck

  30. Pontoon Deck

  31. Pontoon Deck

  32. Double-Deck

  33. Double Deck

  34. On-Floats Deck- aka skin & pontoon, or noncontact

  35. On-Floats Deck- aka skin & pontoon, or noncontact

  36. Sandwich Panel Deck

  37. Sandwich Panel Deck

  38. Floating Roof Considerations • Design: • External floating roofs per API 650, Appendix C • Internal floating roofs per API 650, Appendix H • Costs • Environmental • Fire Safety

  39. External Floating Roofs • Potentially more economical to initially construct versus IFR • But future costs may be unacceptable: • Problems associated with water intrusion • Drain lines pose maintenance problems • Snow load poses maintenance problems • Higher liquid surface temp = higher emissions • This is not presently accounted for in the emission factors, but an API study is seeking to quantify this

  40. Floating Roof Considerations • Design: • External floating roofs per API 650, Appendix C • Internal floating roofs per API 650, Appendix H • Costs • Environmental • Fire Safety

  41. Rainwater Problems with an EFRT

  42. EFR Drain Line Problems

  43. Snow Problems with an EFRT

  44. Emissions Increased with an EFRT

  45. Fixed Roofs for Floating Roof Tanks • Steel cone roof • Typically column supported • Requires painting for maintenance • Retrofit installation requires out-of-service • Aluminum dome roof • Self-supporting (no interior columns) • No painting necessary • Retrofit installation may be done in-service

  46. Problems with Support Columns • Increased air emissions • Due to penetrations through the floating roof • May involve significant foundation costs • Soft soils may require piles under each column. • High corrosion potential/unable to inspect • Bottom corrosion & leaks are accelerated at columns • Interfere with secondary bottom installation

  47. Support Columns

  48. IFR Comparison

  49. Limitations for Pan-Type • Does not meet NFPA 30 criteria • Nor does the bulkheaded, as noted in the prior table - they do not have enclosed flotation compartments • Does not provide redundant buoyancy • A single leak can flood the entire deck, whereas other designs still float with two flooded compartments. • Is readily sunk by upsets or turbulence • Unsymmetrical loading may buckle the rim of the deck, allowing it to fold up like a taco. • Foam system must be for full surface area.

  50. Floating Roof “Taco” Failure