1 / 22

Lecture 1

Lecture 1. Balanced Three-phase Systems From Network to Single-phase Equivalent Circuit. Power plant. Transformer. Switching station. Line. Load. Three-phase system. Single-line diagram. Equivalent single-phase circuit. Balanced Three-phase Systems.

truong
Download Presentation

Lecture 1

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Lecture 1

  2. Balanced Three-phase SystemsFrom Network to Single-phase Equivalent Circuit Power plant Transformer Switching station Line Load Three-phase system Single-line diagram Equivalent single-phase circuit

  3. Balanced Three-phase Systems • A three-phase system can be analyzed by means of a single-phase equivalent when: • The source voltages are balanced or symmetrical • The electrical parameters of the system are symmetrical • The loads are balanced • Three-phase quantities can be determined from single phase voltages and currents when symmetry is assumed between phases.

  4. Balanced and Unbalanced faults • Balanced Cases • three-phase fault • (symmetrical) load flow • Unbalanced Cases • Single line to ground fault • Line to line fault • Double line to ground fault • (unsymmetrical load flow)

  5. Analyzing unbalanced system using Fortescue’s Theorem • Unbalanced faults in power systems require a phase by phase solution method or other techniques. • One of the most useful techniques to deal with unbalanced networks is the “symmetrical component” method, developed in 1918 by C.L. Fortescue.

  6. Symmetrical Components • Reasons for use of symmetrical components: • Unbalanced systems are difficult to handle • -> several independent balanced systems are easier to handle than one unbalanced system. • Transformation of one unbalanced 3-phase system into 3 balanced 3-phase systems. • -> for each system only one phase has to be considered

  7. Analyzing unbalanced system using Fortescue’s Theorem • Any three unbalanced set of voltages or currents can be resolved into three balanced systems of voltages or currents, referred to as the system symmetrical components, defined as follows: • Positive Sequence components: three phasors of equal magnitude displaced 120 degrees from each other following the positive sequence • Negative Sequence components: three phasors of equal magnitude displaced 120 degrees of each other following the negative sequence • ZeroSequencecomponents: three parallel phasors having equal magnitude and angle For a 3-ph system: 3 unbalanced phasors can be resolved into 3 balanced systems of 3 phasors each

  8. Let Va, Vb, Vc be the Phase voltages • According to Fortescue, these can be transformed into • Positive-seq. voltages: Va1, Vb1, Vc1 • Negative-seq. voltages: Va2, Vb2, Vc2 • zero-sequence voltages: Va0, Vb0, Vc0 Thus, Va = Va1 + Va2 + Va0 Vb = Vb1 + Vb2 + Vb0 Vc = Vc1 + Vc2 + Vc0

  9. Vc1 Va1 Va2 Va0 Va1 Vb1 Vc Va Vb Vb2 Va2 Vc2 Va0 Vb0 Vc0

  10. The ‘a’ operator a = 1<1200 = -0.5 + j 0.866 a I rotates I by 1200 a2 = 1<2400 = -0.5 – j 0.866 a3 = 1<3600 = 1<00 = 1 + j 0 1 + a + a2 = 0 a -a2 1 -1 -a a2

  11. From figure previous figures Vb1 = a2Va1 Vc1 = a Va1 Vb2 = a Va2 Vc2 = a2 Va2 Vb0 = Va0 Vc0 = Va0 sub. In Eq. (Slide 8) we get: Thus, Va = Va0 + Va1 + Va2 Vb = Va0 + a2Va1 + a Va2 Vc = Va0 + a Va1 + a2Va2

  12. Matrix Relations Let And Inverse of A is

  13. Matrix Relations Similarly currents can be obtained using their symmetrical components

  14. Matrix Relations • Vp= A Vs; Vs = A-1Vp • Va0 = 1/3 (Va + Vb + Vc) • Va1 = 1/3 (Va + aVb + a2Vc) • Va2 = 1/3 (Va + a2Vb + aVc)

  15. Matrix Relations

  16. Numerical Example • The line currents in a 3-ph 4 –wire system are Ia = 100<300 ; Ib = 50<3000 ; Ic = 30<1800. Find the symmetrical components and the neutral current. • Solution : • Ia0 = 1/3(Ia + Ib + Ic) = 27.29 < 4.70 A • Ia1 = 1/3(Ia + a Ib + a2Ic) = 57.98 < 43.30 A • Ia2 = 1/3(Ia + a2 Ib + a Ic) = 18.96 < 24.90 A • In = Ia + Ib + Ic = 3 Ia0 = 81.87 <4.70 A

  17. Numerical Example 2. The sequence component voltages of phase voltages of a 3-ph system are: Va0 = 100 <00 V; Va1 = 223.6 < -26.60 V ; Va2 = 100 <1800 V. Determine the phase voltages. Solution: Va = Va0 + Va1 + Va2 = 223.6 <-26.60 V Vb = Va0 + a2Va1 + a Va2 = 213 < -99.90 V Vc = Va0 + a Va1 + a2 Va2 = 338.6 < 66.20 V

  18. Numerical Example 3. The two seq. components and the corresponding phase voltage of a 3-ph system are Va0 =1<-600 V; Va1=2<00 V ; & Va = 3 <00 V. Determine the other phase voltages. Solution: Va = Va0 + Va1 + Va2  Va2 = Va – Va0 – Va1 = 1 <600 V Vb = Va0 + a2Va1 + a Va2 = 3 < -1200 V Vc = Va0 + a Va1 + a2 Va2 = 0 V

  19. Numerical Example 4. Determine the sequence components if Ia =10<600 A; Ib = 10<-600 A ; & Ic = 10 <1800 A. Solution: Ia0 = 1/3 (Ia + Ib + Ic) = 0 A Ia1 = 1/3 (Ia + a Ib + a2Ic) = 10<600 A Ia2 = 1/3 (Ia + a2 Ib + a Ic) = 0 A Thus, If the phasors are balanced, Two Sequence components will be zero.

  20. Ia Ia Ib

  21. Numerical Example 5. Determine the sequence components if Va = 100 <300 V; Vb = 100 <1500 V ; and Vc = 100 <-900 V. Solution: Va0 = 1/3(Va + Vb + Vc) = 0 V Va1 = 1/3(Va + a Vb + a2Vc) = 0 V Va2 = 1/3(Va + a2 Vb + a Vc) = 100<300 V Observation: If the phasors are balanced, Two sequence components will be zero.

  22. Three phase power in symmetrical components • S = VpTIp* = [A Vs]T[A Is]* = VsT AT A* Is* = 3 VsTIs* = 3Va0 Ia0* + 3Va1 Ia1* + 3Va2 Ia2* note that AT = A