Risk communication approach Case public exposure Case worker´s exposure Martti Hyvönen MD, Environmental Director at

RT 2c: EMF – Revision of magnetic field limits. Risk communication approach Case public exposure Case worker´s exposure Martti Hyvönen MD, Environmental Director at Helsinki Energy Chairman of Eurelectric WG Environment and Society Chairman of EMF Forum in Finland

tanginika
Download Presentation

Risk communication approach Case public exposure Case worker´s exposure Martti Hyvönen MD, Environmental Director at

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. RT 2c: EMF – Revision of magnetic field limits • Risk communication approach • Case public exposure • Case worker´s exposure Martti Hyvönen MD, Environmental Director at Helsinki Energy Chairman of Eurelectric WG Environment and Society Chairman of EMF Forum in Finland martti.hyvonen@helen.fi Phone: +358 50 364 8840 HYVONEN-FI-RT.2c

  2. Communication - the implicit messages? • MF limit increased to 200 µT instead of 100 µT… • Power lines are visible - substations near people • EF limit decreased to avoid spark discharges … • DSO´s EMF actions are based on … • Health controls … HYVONEN-FI-RT.2c

  3. Children´s playground under power line HYVONEN-FI-RT.2c

  4. Children´s playground near power line City bridge(110 kV cable) 110 kV OH line; load 2 x 500 A 0,16 µT at playground fence HYVONEN-FI-RT.2c

  5. Public exposure to distribution substation MF HYVONEN-FI-RT.2c

  6. Public exposure to distribution substation MF • TransCat project – Categorization of indoor MV/LV transformer substations according to magnetic field exposure • 250 + 53 substations in Finland; by the structure of LV connection • MF ≥100 µT possible when bus bars or cables near ceiling • Measurement guide provided Kettunen K &al.: Magnetic field categorization in indoor MV/LV substations by the structure of the low voltage connection. Cired Conference Vienna 2007 • TransExpo project?? In the appartment above, MF ≥0,4 µT/24 h Hareuveny R, Kandel S, Yitzhak NM, Kheifets L, Mezei G: Exposure to 50 Hz magnetic fields in apartment buildings with indoor transformer stations in Israel. J Expo Sci Environ Epidemiol. 2010 HYVONEN-FI-RT.2c

  7. Inspection round at a CCGT power plant 85 µT HYVONEN-FI-RT.2c

  8. Inspection round at a CCGT power plant Steam T generator GT bus bar ≤ 1 µT 43 % of time max 401 µT(1732 µT) HYVONEN-FI-RT.2c

  9. Work at distribution substations HYVONEN-FI-RT.2c

  10. Work at distribution substations • MF-Safety project – Magnetic field safety in power distribution switchgears and substations • Evaluation of routine tasks with a simple flow chart • Basic restriction 10 mA/m2 is not exceeded when MF <500 µT. But, higher induced currents possible in non-homogenous fields. • The relation between MF and induced currents was similar to Dimbylov´s (2005) results. • Substation tasks and layouts can be modified in a simple way to reduce exposure. There was no need to restrain routine work. Keikko T &al: Magnetic field risk eavaluation of workers in indoor distribution substations. Cired Conference Prague 2009 HYVONEN-FI-RT.2c

  11. Exposure to electric fields • High voltage lines are not a significant source of EF public exposure. However, EF guideline values (5 or 10 kV/m) can be exceeded mid-span in the Finnish countryside. • At 400 kV substation maintenance work EF up to 25 kV/m, but, induced current densities were below the limit value 10 mA/m2 • By grounding themselves skilled workers avoid spark discharges Korpinen L, Elovaara J, Kuisti H: Occupational exposure to electric fields and induced currents associated with 400 kV substation tasks from different service platforms. Bioelectromagnetics 32,1;79–83, Jan 2011 HYVONEN-FI-RT.2c

  12. Communication - the implicit messages? • MF limit increased to 200 µT instead of 100 µT… • Power lines are visible - substations near people • EF limit decreased to avoid spark discharges … • DSO´s EMF actions are based on …0,4 µT «yearly average» – precaution? • Health controls: doctor´s magic touch? HYVONEN-FI-RT.2c