Damian Oatway (MEI - Chartered Energy Manager) Assistant Mechanical & Energy Engineer

The University of Manchester: Energy Savings & Funding. Damian Oatway (MEI - Chartered Energy Manager) Assistant Mechanical & Energy Engineer. The University of Manchester. UK’s largest university Almost 40,000 students Over 10,500 staff Located in 347 buildings on 711 acres of land

Download Presentation

Damian Oatway (MEI - Chartered Energy Manager) Assistant Mechanical & Energy Engineer

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. The University of Manchester: Energy Savings & Funding Damian Oatway (MEI - Chartered Energy Manager) Assistant Mechanical & Energy Engineer

  2. The University of Manchester • UK’s largest university • Almost 40,000 students • Over 10,500 staff • Located in 347 buildings on 711 acres of land • Income of £807m (12/13) • Ambitious plan to be one of the top 25 universities worldwide by 2015 • £1bn estates development between 2013-2020

  3. Energy Consumption • Electricity - £9.6m – 107GWh – 55,825tCO2(e) • Gas - £3.5m – 161GWh – 29,581tCO2(e) • Water - £2m – 856,000m3 • Oil - £60,000 – 805,605kWh - 239tCO2(e) • Carbon Footprint (Scope 1, 2 & 3) – 86,000tCO2(e) • Lighting Power Consumption (conservative guess 25%) • £2.4m • 26.75GWh • 14,000tCO2(e)

  4. Energy Projections • Projected energy price rises – Top out at £20m (2020) • HEFCE emissions target set as 43% of 2005 consumption by 2020 (85% by 2050) • Presently at 5% above 2005 levels • University increasing in size: • Income: +57% (2005 - £514m) (2013 - £807m) • Student Numbers: +15% (2005 – 35,018) (2013 – 39,953) • Area: +137% (2005 – 1.21km2) (2013 – 2.87km2) • 24hr operation of buildings • 3 semester academic years

  5. Opportunities • Funding – HEFCE/Salix/DECC • Legislation – CRC/ESOS/Electricity Demand Reduction • Part L – Consequential Improvements • Combined Heat and Power/Biomass • Lighting - can be minimal disruption • Greater flexibility in design • Easy to calculate and justify savings • £1.6m spent on LED Projects since 2009 • Student pressure – will seek value due to tuition fees • Carbon Reduction Technicians (CRT’s)

  6. John Ryland’s University Library – LED Lighting • Initial Problems • Over 2,000 T12 tubes of various length installed in 1960’s • Energy in-efficient • Short lifespan – constant replacement program (manpower) • Getting more difficult to source • Colour variation as tubes reach end of life • Disposal costs • Cast concrete ceiling • Library open 6,568hrs/year

  7. John Ryland’s University Library – LED Lighting Purchase and installation of T5 fittings would cost around £3m Proposal to Install LED Tubes (Total Cost - £138,000) 1222 x 6ft Tubes (85W to 30W) 417 x 5ft Tubes (65W to 20W) 320 x 4ft Tubes (40W to 18W) Estimated Initial Energy Consumption – 880,000kWh Estimated New Consumption – 320,000kWh Saving – 560,000kWh / £61,600 / 302t Carbon Payback Period – 2.2years

  8. John Ryland’s University Library – LED Lighting

  9. John Ryland’s University Library – LED Lighting

  10. John Ryland’s University Library – LED Lighting • Annual Savings around £140,000 - 642tCO2(e) • Estimated readings have been exceeded due to: • Non inclusion of ballast/transformer loss • Lamps being left on 24/7 even when closed

  11. 2012/13 Salix top 5 project types A summary of Recycling Fund & SEELS 5 projects Data as of year end 2012/13

  12. Salix Funded Lighting Projects to Date

  13. Salix Funded Internal Lighting Upgrades Lighting upgrade type 2009/10 2010/11 2011/12 2012/13 LED Lighting 10% 33% 38% 52% T5 and other lighting 90% 67% 62% 48% Data as of Aug 2013

  14. Lighting projects funded to date Data as of Aug 2013

  15. Salix 100% interest free capital finance funding programmes Salix Energy Efficiency Loans (SEELS) • Funding currently available for this year • Funding from £5,000 upwards • Interested in funding large programmes over several years Salix Current Products Recycling Fund • Matched capital funding investment • Typical £250,000 100% interest free funding given but can be up to £500,000 • Projects payback within 5 years • 100% interest free capital finance tailored for schools • Flexible paybacks to ensure schools can do best possible energy efficiency projects • Project payback within 8 years Salix Schools Loans Scheme

  16. The University of Manchester • Any Questions?