Underlying Concepts in Seismic Design Codes: Application to Steel Building Structures

2. Outline. Seismic Loadings Codes- Historical Development- Intent of Seismic Performance FactorsSeismic Materials CodesDuctility vs. StrengthDuctility Design- Examples of Code Implementation (SMF, BFs)Capacity Design- Examples of Code Implementation (SMF, BFs)Summary. 3. . Historical Development of Seismic Loadings Codes.

nuru
Download Presentation

Underlying Concepts in Seismic Design Codes: Application to Steel Building Structures

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


    1. Underlying Concepts in Seismic Design Codes: Application to Steel Building Structures

    2. 2 Outline Seismic Loadings Codes - Historical Development - Intent of Seismic Performance Factors Seismic Materials Codes Ductility vs. Strength Ductility Design - Examples of Code Implementation (SMF, BFs) Capacity Design - Examples of Code Implementation (SMF, BFs) Summary

    3. 3 Historical Development of Seismic Loadings Codes

    4. 4 Basic Load Combinations (ASCE 7) E: Probably the Most Mysterious “Load”

    5. 5 Seismic Loadings: Historical Perspective

    6. 6 Design Base Shear: Historical Perspective

    7. 7 Seismic Design Philosophy

    8. 8 Earthquake Observation

    9. 9 Building Standard Law (BSL) of Japan

    10. 10 Building Standard Law (BSL) of Japan Level 2 Earthquake (PGA = 0.34?0.4 g) for Safety Consideration Level 1 Earthquake (PGA = 0.07?0.1 g) for Serviceability Consideration

    11. 11 BSL Level 1? Serviceability Design

    12. 12 BSL Level 2?Safety Design

    13. 13 US Approach?up to 1985 UBC

    14. 14 1988 UBC

    15. 15 Comparison of BSL and UBC Drift Limits

    16. 16 Implication of UBC Drift Limit

    17. 17 1997 UBC

    18. 18 ASCE 7-05

    19. 19 Performance-Based Design Two-Level Seismic Design Including Seismic Serviceability Check Is Back Again!

    20. 20 Tall Buildings PBD Guidelines Still Use Capacity Design Principles Require Nonlinear Time-History Analysis Check at Least Two Seismic Hazard Levels

    21. 21 Los Angeles Tall Buildings Structural Design Council

    22. 22 Pacific Earthquake Engineering Research Center Definition of Tal Buildings Not Height Dependent Period > 1 Second Significant Higher Mode Effects Significant Story Drift Component due to Chord (Column, Shear Wall) Deformation

    23. 23 Pacific Earthquake Engineering Research Center

    24. 24 Seismic Serviceability Design

    25. 25 Design Basis Earthquake (ASCE 7)

    26. 26 “1g” Building

    27. 27

    28. 28 Ductility Factor

    29. 29 Newmark-Hall Ductility Reduction Rule

    30. 30 Multistory Frames

    31. 31 BSL Level 2?Safety Design

    32. 32 US Approach

    33. 33 Simplicity Nonlinear Analysis not Required Ultimate Structural Strength not Known Empirical Seismic Performance Factors (R, Cd, and ?o) Design Focuses on Life Safety at One Design Earthquake (475-year) Level The Design Procedure Serves Well in General

    34. 34 Seismic Design Concept 1?Ductility Design A Reduced Design Seismic Force Can Be Used IF Sufficient Ductility Is Built into the Structure But Only Certain Elements Are Strategically Designated to Serve as Structural Fuse, i.e., Deformation-Controlled Elements (DCE)

    35. 35 Example (SCBF)

    36. 36 Example (EBF)

    37. 37 Example (SMF)

    38. 38 Seismic Design Concept 2?Capacity Design Remaining Part of the Structure Is Designed to Remain Elastic, i.e., Design These Elements as Force-Controlled Elements (FCE).

    39. 39 Two Key Concepts in AISC Seismic Provisions Ductility Design Requirements + Capacity Design Requirements

    40. 40 2005 AISC Seismic Provisions Moment Frames (Sections 9, 10, 11) Special Truss Moment Frames (Section 12) Concentrically Braced Frames (Sections 13,14) Eccentrically Braced Frames (Section 15) Buckling-Restrained Braced Frames (Section 16) Special Plate-Shear Walls (Section 17)

    41. 41 2010 AISC Seismic Provisions Section A: General Requirements Section B: General Design Requirements Section C: Analysis Section D: General Member and Connection Design Requirements Section E: Moment-Frame Systems Section F: Braced-Frame and Shear-Wall Systems Sections G, H: Composite Systems etc.

    42. 42 Sample Section (§13 on SCBF)

    43. 43 Ductility vs. Capacity Design

    44. 44 Ductility Design Concept

    45. 45 Target Yield Mechanism

    46. 46 2010 AISC Seismic Provisions Definition of Highly Ductile Members and Moderately Ductile Members Seismic Compactness Requirement Lateral Bracing Requirement

    47. 47 Ductility Requirements Code Implementation Example 1: Special Moment Frame (SMF) Design

    48. 48 RBS Moment Connection

    49. 49 RBS Moment Connection

    50. 50 BFP Moment Connection

    51. 51 Dynamic Testing of Pre-Northridge Moment Connection

    52. 52 Local Buckling Control

    53. 53 Local Buckling Control (2005 SP)

    54. 54 Local Buckling Control (2010 SP)

    55. 55 Lateral-Torsional Buckling

    56. 56 Lateral-Torsional Buckling

    57. 57 Lateral-Torsional Buckling

    58. 58 Panel Zone

    59. 59 Protected Zone (AISC SP §9.3)

    60. 60 Ductility Requirements Code Implementation Example 2: Special Concentrically Braced Frame (SCBF) Design

    61. 61 Target Yield Mechanism

    62. 62 Bracing Ductility Requirements Bracing Buckling (SP §13.2a)

    63. 63 Bracing Ductility Requirements Local Buckling (SP §8.2b): Seismically Compact

    64. 64 Gusset “2t” Requirement

    65. 65 Gusset “2t” Requirement

    66. 66 Ductility Requirements Code Implementation Example 3: Eccentrically Braced Frame (EBF) Design

    67. 67 EBF Configuration

    68. 68 Link Ductility Requirement

    69. 69 Link Ductility Requirements Link Deformation Capacity Depends on ? (Seismic) Compactness ? Length ? Link Stiffeners

    70. 70 Link Length Effect

    71. 71 Link Web Stiffeners (AISC SP §15.2c)

    72. 72 Capacity Design Concept

    73. 73 Ductility vs. Capacity Design

    74. 74 ASCE 7 Seismic Performance Factors 3 System Factors: R, Cd, and ?o

    75. 75 Capacity Design Seismic Forces

    76. 76 Seismic Load Combinations (IBC) §16.5.2.1 Basic Seismic Load Combination: 1.2D + f1L + f2S + 1.0E §1605.4 Special Seismic Load Combination: 1.2D + f1L + 1.0Em

    77. 77 Internal Force Distribution At Seismic Force Level II (Basic Seismic Load Combination)?Use Elastic Structural Analysis to Determine Internal Force Distribution At Seismic Force Level III (Special Seismic Load Combination)?Internal Force Re-distribution Occurs due to Nonlinear Response

    78. 78 Example

    79. 79 Capacity Design Think beyond Elastic Response Mentality Use Expected Material Strength to Estimate Maximum Force Developed in Structural Fuse (Note: Structural Fuse Material Strength too High Is not Desirable for Seismic Design) Two Methods to Calculate Seismic Force Level III for Capacity Design ?Local Approach ?Global Approach

    80. 80 Expected Material Strength AISC SP §6.2 Expected Yield Stress,

    81. 81 Method 1?”Local” Approach When the Structural Fuse Is Next to Force-Controlled Element Apply Statics at “Local” Level Seismic Force Level II not Needed An Upper-Bound Estimate of Seismic Force Level III

    82. 82 Example 1: SCBF Bracing Connection Bracing is Structural Fuse AISC SP §13.3 Bracing Connection Design

    83. 83 Example 1: SCBF Beam Design AISC SP §13.4a Beam Design for V-Type Bracing

    84. 84 Example 1: SCBF Beam Design

    85. 85 Example 2: EBF Column Design Links Are Structural Fuse AISC SP §15.8 for Column Design

    86. 86 Example 2: EBF Brace Design Links Are Structural Fuse AISC SP §15.6 for Beam/Bracing Design

    87. 87 Example 3: SMF AISC 358-05

    88. 88 Example 3: SMF Strong Column-Weak Beam Condition (AISC SP §9.6):

    89. 89 Method 2?”Global” Approach An Approximate (or “Lazy”) Method: ?o ? (Seismic Force Level II) Use It When Method 1 Cannot Be Applied Easily Usually Applied at the “Global” (or System) Level Can Be Dangerous If Not Properly Applied

    90. 90 Example 1?SCBF

    91. 91 SCBF: 2010 AISC SP Case 1 All Tensile Braces: T = Ry Fy Ag All Compressive Braces: P = min{Ry Fy Ag, 1.14FcreAg} Case 2 All Tensile Braces: T = Ry Fy Ag All Compressive Braces: 30% of P in Case 1

    92. 92 Example 1?SCBF Column Design

    93. 93 Example 2?SCBF Column Design

    94. 94 Example 2?SCBF Column Design

    95. 95 Summary Seismic Provisions Trade Strength with Ductility AISC Seismic Provisions Centered on Two Concepts. A Target Yield Mechanism Is Aimed for Each Lateral Force-Resisting System Deformation-Controlled Elements (Structural Fuse): ?Design for Reduced Seismic Forces ?Ductility Design Is Relatively Straightforward Force-Controlled Element: ?Design for Amplified Seismic Forces ?Use Either “Local” or “Global” Approach ?Capacity Design Requires Good Judgment and Experience