CÁLCULO DE MATERIALES

CÁLCULO DE MATERIALES. ABP = amperaje del breaker de alimentación principal del tablero de la enjuagadora de botellas. ABB = amperaje del breaker que alimentara la bomba de enjuague. ABM = amperaje del breaker del transportador de botellas.

mizell
Download Presentation

CÁLCULO DE MATERIALES

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CÁLCULO DE MATERIALES • ABP = amperaje del breaker de alimentación principal del tablero de la enjuagadora de botellas. • ABB = amperaje del breaker que alimentara la bomba de enjuague. • ABM = amperaje del breaker del transportador de botellas. • ACB = amperaje del contactor para la bomba de enjuague. • ACM = amperaje del contactor para el motor de transportador de botellas. • AOLB = Rele térmico para protección de la bomba de enjuague. • AOLM = Rele térmico para protección del motor para transportador de botellas. • AcP = amperaje del conductor principal del tablero de la maquina enjuagadora. • AcB = amperaje del conductor que alimentara la bomba de enjuague de envases. • AcM = amperaje del conductor que alimentara el transportador de botellas. • ANB = amperaje nominal de la bomba de enjuague de botellas, dato de la placa de la bomba de limpieza. • ANM = amperaje nominal del transportador de botellas, dato de la placa del motor del transportador. • AV = amperaje de las 4 válvulas solenoides a 220 voltios alternos el conjunto consume 1 amperio. • AS = amperaje de los 2 sensores de 0.2 amperios de consumo cada uno, por lo que entre los dos seria un consumo de 0.4 amperios. • A = unidad de amperios. • CALCULO DEL BREAKER PRINCIPAL • Breaker principal = 200 % x (amperaje mayor del circuito) + suma del resto de los amperajes del sistema. ABP = 200 % x (ANB) + ANM + AV + AS ABP = 200 % (2.8 A) + 1.9 A + 1 A + 0.4 A ABP = 8.9 A EL BREAKER PRINCIPAL SERÁ DE 3 POLOS 10 amperios (tabla 1)

  2. BOMBA DE ENJUAGUE DE BOTELLAS • TRANSPORTADOR DE BOTELLAS ABM = ANM / 80 % ABM = 1.9A / 80 % ABM = 2.375 A ABB =ANB / 80% ABB = 2.8A / 80 % ABB = 3.5 A. Tabla 1

  3. CÁLCULO DE CONTACTORES • BOMBA. • TRANSPORTADOR ACB = 115 % x ANB ACB = 115 % x 2.8 A ACB = 3.22 A ACB = 115 % x ANM ACB = 115 % x 1.9 A ACB = 2.185 A Tabla 2

  4. CÁLCULO DE RELES TÉRMICOS • BOMBA • TRANSPORTADOR AOLB = 125 % x ANB ACB = 125 % x 2.8 A ACB = 3.5 A AOLB = 125 % x ANB ACB = 125 % x 2.8 A ACB = 2.375 A Tabla 3

  5. Amperaje del conductor principal AcP = 125 % x (ANB) + ANM + AV + AS Cálculo del amperaje para el neutro.Se toma la misma capacidad del breaker principal, por lo tanto corresponde a un conductor calibre # 14. AcP = 5A + 1.9 A + 1.4 AcP = 8.3 A, conductor 14 BOMBAAcB = 125 % x ANB AcB = 125 % x 4 AAcB = 5 A, conductor 16 TRANSPORTADORAcM = 125 % x ANM AcM = 115 % x 1.9 AAcM = 2.185 A, conductor16 Ver tabla 4

  6. Tabla 4