html5-img
1 / 31

Application of Unit Protection Schemes for Auto-Transformers

Application of Unit Protection Schemes for Auto-Transformers. Zoran Gaji ć ABB AB Vasteras, Sweden. Authors: Z. Gaji ć, ABB Sweden S. Holst, ABB Sweden. Auto-Transformer. An auto-transformer is a power transformer in which at least two windings have a common part

merlin
Download Presentation

Application of Unit Protection Schemes for Auto-Transformers

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Application of Unit Protection Schemes for Auto-Transformers Zoran Gajić ABB AB Vasteras, Sweden • Authors: • Z. Gajić, ABB Sweden • S. Holst, ABB Sweden

  2. Auto-Transformer • An auto-transformer is a power transformer in which at least two windings have a common part • Typically auto-transformers are used to interconnect two electrical networks with similar voltage levels (e.g. system intertie transformer) • In practice auto-transformer tertiary delta winding is normally included. It serves to limit generation of third harmonic voltages caused by magnetizing currents and to lower the zero sequence impedance for five-limb core constructions or for auto-transformers built from three single phase units

  3. Example Auto-Transformer

  4. Auto-Transformer has Dual Rating • It can be shown that power is transferred in two different ways through an auto-transformer. • One part of the power is transferred by galvanic connection and the other part is transferred via magnetic circuit (i.e. transformer action) • Auto-transformer is cheaper that corresponding two/three winding power transformer design • Possible problem with short circuit current withstand

  5. One three-phase unit Typically has five-limb core Three single-phase units connected to form three-phase group Auto-transformer Construction

  6. Possible CT Locations for Auto-Transformer

  7. Based on autotransformer ampere-turn balance 87T Based on the first Kirchhoff’s law between galvanically interconnected parts 87B Possible Differential Protection Principles

  8. Restricted Earth-Fault Zero-sequence current based Dedicated delta winding unit protections Special Unit Protections

  9. 87T Differential protection using CT1 and CT2 • SBase=Throughput Power(400MVA) • Tertiary delta winding can not be loaded • Mandatory zero sequence current reduction

  10. 87T Differential protection using CT1 and CT2

  11. 87T Differential protection using CT1, CT2 and CT3 • SBase=Throughput Power(400MVA) • Tertiary delta winding can be loaded • Mandatory zero sequence current reduction

  12. 87T Differential protection using CT1, CT2 and CT3

  13. 87T Differential protection using CT1, CT2 and CT7 • SBase=Throughput Power(400MVA) • Tertiary delta winding can be loaded • CT location within delta winding requires “special attention” • Zero sequence current reduction not required if it is a five-limb or single-phase construction

  14. 87T Differential protection using CT1, CT2 and CT7 * Influenced by CT location within tertiary delta winding

  15. 87T Differential protection using CT1, CT5 and CT7 • SBase=Magnetic Power(169MVA) • Tertiary delta winding can be loaded • CT location at neutral point and within delta winding requires “special attention” • Zero sequence current reduction not required if it is a five-limb or single-phase construction • MV (i.e. 220kV) bushings not protected!

  16. 87T Differential protection using CT1, CT5 and CT7 Influenced by CT5 location in neutral point * Influenced by CT7 location within tertiary delta winding

  17. 87T Differential protection using CT1, CT2, CT7 and CT8 • SBase=Throughput Power(400MVA) • Tertiary delta winding can be loaded • Double CT location within delta winding requires “special attention” • Relay with four restraint inputs required • Mandatory zero sequence current reduction

  18. 87T Differential protection using CT1, CT2, CT7 and CT8 * Influenced by double CT location within tertiary delta winding

  19. 87T Differential protection using CT1, CT5, CT7 and CT8 • SBase=Magnetic Power(169MVA) • Tertiary delta winding can be loaded • CT location at neutral point and within delta winding requires “special attention” • Relay with four restraint inputs required • Zero sequence current reduction not required if it is a five-limb or single-phase construction • MV (i.e. 220kV) bushings not protected!

  20. 87T Differential protection using CT1, CT5, CT7 and CT8 Influenced by CT5 location in neutral point * Influenced by CT7, CT8 location within tertiary delta winding

  21. 87B Differential protection using CT1, CT2 and CT6 • SBase=Throughput Power(400MVA) • Zero sequence current reduction not required • Tertiary delta winding can be loaded • Not sensitive for winding turn to turn faults

  22. 87B Differential protection using CT1, CT2 and CT6

  23. REF protection using CT1, CT2 and CT4 • Base quantity is current (either CT2 or W2 rating) • Tertiary delta winding can be loaded but it is not protected • Operates only for phase to ground faults

  24. REF protection using CT1, CT2 and CT4

  25. Dedicated unit scheme for tertiary winding • Use simple I> relay to provide only earth-fault protection for tertiary delta winding

  26. Field Recording CT1 CT5 CT2 CT4 & CT7 • External L2-Gnd fault which before clearing evolved into a L2-L3-Gnd fault • CT1, CT2, CT4 and CT7 currents recorded • CT5 current calculated • Delta winding not loaded, thus CT7 currents are identical in all three phases

  27. Calculated Diff Currents from Field Recording

  28. Calculated REF Diff Current from Field Recording

  29. Conclusion • The following data are crucial for proper application of the selected differential protection scheme for Auto-transformer: • Which base quantities (i.e. power, no load voltage and current) shall be used • Which vector group shall be entered • Whether or not zero sequence current elimination shall be enabled

  30. Conclusion • Selection of unit protection schemes for particular auto-transformer application depends on: • Available CTs • User preference • Previous experience

  31. СПАСИБО ЗАВНИМАНИЕ! THANK YOU!

More Related