An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. TEAM II Cooling Tower Analysis By: Cortez Rankin & D. Caruthers

  2. Objectives • Components of Cooling Tower • Air Outlet Velocities and Flow Rates • Air Inlet Velocities and Flow Rates • Water Inlet and Outlet Data • Comparison of Data @ Different Water Inlet Flow Rates

  3. Water Cooling Tower

  4. Balances Assuming Steady State Operation [IN = OUT] Overall Mass Balance MAO + M WO = MAI + MWI Overall Energy Balance hAO MAO + h WO M WO = h AI M AI+ hWIMWI AO=Air OutletAI=Air Inlet WO=Water Outlet WI=Water Inlet

  5. Portable Cooling Tower

  6. Air Inlet

  7. Air Outlet and Water Inlet

  8. Psychrometric Chart

  9. Air Inlet Data for Water Inlet Flow Rate = 5.1 (l/min) • Velocity = 12.2 m/s • Wet Bulb Temp. = 18 °C • Dry Bulb Temp. = 25.5 °C • Area = 0.038 m2 • Relative Humidity = 48% • Volumetric Flow Rate= 0.464 m3/s

  10. Air Inlet Data for Water Inlet Flow Rate = 10.1 (l/min) • Velocity = 12.0 m/s • Wet Bulb Temp. = 17 °C • Dry Bulb Temp. = 25 °C • Area = 0.038 m2 • Relative Humidity = 45% • Volumetric Flow Rate= 0.456 m3/s

  11. Air Inlet Data for Water Inlet Flow Rate = 40.3 (l/min) • Velocity = 8.0 m/s • Wet Bulb Temp. = 19 °C • Dry Bulb Temp. = 27.5 °C • Area = 0.038 m2 • Relative Humidity = 45% • Volumetric Flow Rate= 0.304 m3/s

  12. Outlet Velocity as a Function of Radiusfor Water Inlet Flow Rate = 5.1 (l/min)

  13. Outlet Velocity as a Function of Radiusfor Water Inlet Flow Rate = 10.1 (l/min)

  14. Outlet Velocity as a Function of Radiusfor Water Inlet Flow Rate = 40.3 (l/min)

  15. Calculate Outlet Air Velocity

  16. Formulas • Volumetric Flow Rate = (Area)(Velocity) • Mass Flow Rate = (Density)(Volumetric Flow Rate)

  17. Outlet Air for Water Inlet Flow Rate = 5.1 (l/min) • Area = 0.312 m2 • Volumetric Flow Rate= 1.7 m3/s • Temp. Dry Bulb= 21 °C= Wet Bulb Temp. • Enthalpy = 79 kJ/kg Dry Air

  18. Outlet Air for Water Inlet Flow Rate = 10.1 (l/min) • Area = 0.312 m2 • Volumetric Flow Rate= 1.6 m3/s • Temp. Dry Bulb= 23 °C= Wet Bulb Temp. • Enthalpy = 86 kJ/kg Dry Air

  19. Outlet Air for Water Inlet Flow Rate = 40.3 (l/min) • Area = 0.312 m2 • Volumetric Flow Rate= 1.0 m3/s • Temp. Dry Bulb= 31°C= Wet Bulb Temp. • Enthalpy = 123 kJ/kg Dry Air

  20. Water Data for Water Inlet Flow Rate = 5.1 (l/min) • Inlet Temp.= 52.5 oC • Outlet Temp.= 27.7 oC • Temp. Change= 24.8 oC • Mass Flow Rate= 0.085 kg/s • Tons of Cooling= 2.5

  21. Water Data for Water Inlet Flow Rate = 10.1 (l/min) • Inlet Temp.= 56.3 oC • Outlet Temp.= 31 oC • Temp. Change= 25.3 oC • Mass Flow Rate= 0.168 kg/s • Tons of Cooling= 5.1

  22. Water Data for Water Inlet Flow Rate = 40.3 (l/min) • Inlet Temp.= 52 oC • Outlet Temp.= 30.4 oC • Temp. Change= 21.6 oC • Mass Flow Rate= 0.671 kg/s • Tons of Cooling= 17

  23. Admin Tower Schematic

  24. Admin Cooling Tower Front (West) Inlet • Dry Bulb Temp = 18 oC • Wet Bulb Temp = 12 oC • Area = 4.6 m2 • Air Speed = 1.4 m/s • Volumetric Flow rate = 6.1 m3/s • Density of Area = 1.2 kg/m3 • Mass flow rate = 7.3 kg/s

  25. Admin Cooling Tower Front (West) Inlet Team 3 • Dry Bulb Temp = 33 oC • Wet Bulb Temp = 24.5 oC • Area = 4.6 m2 • Air Speed = 1.6 m/s • Volumetric flow rate = 7.6 m3/s • Density of Area = 1.1 kg/m3 • Mass flow rate = 8.3 kg/s