1 / 20

Energy Code Update

Energy Code Update. Key Points Adoption of the new Energy Code will be impacting projects and specifications in Montana. Newly adopted energy codes have slightly different requirements, so be aware!

isaura
Download Presentation

Energy Code Update

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Energy Code Update Key Points • Adoption of the new Energy Code will be impacting projects and specifications in Montana. • Newly adopted energy codes have slightly different requirements, so be aware! • Northern Rockies Agency does it’s utmost to help keep our partners on top of code requirements and developments for their projects.

  2. Commercial Energy Codes Status As of July 2004 WA ME ND* MT MN VTt 2003 IECC NH OR NH WI NY ID MA SD CT CT MI RI WY NJ PA IA NEt OH NVt MD IN ILt DE UT WV* COt* VA DC KS MOt KY CA NC TN* OK AZt* SC SC AR NM GA MS AL LA TX FL AK Mandatory statewide code including state-owned buildings 2003 IECC / ASHRAE 90.1-2001 (9) (16) ASHRAE 90.1-1999 or equivalent state code adoption or in adoption process. HI* (15) ASHRAE 90.1-1989 (1) State developed code does not meet 90.1-1989 (10) Weaker/None Building Codes Assistance Project Commercial Map 7/7/04 * Code implementation depends upon voluntary adoption by local jurisdictions. t 90.1 Mandatory for state owned buildings NOTE: This map should be used in conjunction with BCAP’s Status of the State newsletter. Go to bcap-energy.org to viewcurrent newsletter.

  3. In December of 2004, Montana will begin the enforcement of the 2003 International Energy Conservation Code (2003 IECC). What is this going to mean to you?

  4. Missoula will be enforcing the 2003 IECC as of Dec.3, 2004

  5. 2003 I.E.C.C. Lighting SystemsScope • Applies to the design of: • First installed lighting systems in conditioned or unconditioned spaces • Altered systems as part of alteration • Altered system that increases the lighting load if change of occupancy • Exterior lighting systems

  6. IECC 2003 Ltg. Control Content IECC 2003 805.2 Lighting controls 805.2.1. Interior Ltg Controls 805.2.2. Additional Controls Light Reduction Controls Automatic Shutoff Guestrooms 805.2.3. Exterior Ltg Controls

  7. Interior Interior Lighting Requirements: • Mandates: • - Controls • - Switching • - Wiring Interior Lighting Power Requirements Entire Building Partial Building

  8. Interior IECC 2003Interior lighting controls • At least 1 manual control for each area enclosed by walls, or ceiling height partitions • Must be located in the space • Remote location OK if • the switch identifies the lights being controlled and • indicates status Exceptions • Areas that must be continuously lit • Spaces part of means of egress (stairway, corridor, etc.)

  9. Interior IECC 2003Additional Controls • Additional controls for each area required to have a manual control • Additional controls include: • Light Reduction Controls, and • Automatic shut-off, and • Guestroom controls (when suits application) Exceptions • Areas with 1 luminaire • Areas controlled by occupancy sensors • Corridors, storerooms, restrooms, public lobbies

  10. Interior IECC 2003Light Reduction Controls • 50% load reduction via the following: • Controlling all lamps or luminaires (Dimming – Daylighting) • Dual switching of alternate rows, luminaires, or lamps • Switching independent lamps within a luminaire • Switching each luminaire or lamp Exceptions: • Areas with 1 luminaire • Areas controlled by occupancy sensors • Spaces that use < 0.6 W/ sq. ft • Corridors, storerooms, restrooms, public lobbies, guestrooms

  11. Interior Example: Alternate Luminaires S S Bi-Level Switching • Compliance Examples

  12. D S S Dimmer Switch Bi-Level Switching • Compliance Examples Example: Alternate Lamps (a/b) Example: Dimmer Control Option

  13. Automatic Shut off Exceptions

  14. 2003 IECC Exterior Lighting Requirements: • Mandatory Requirements: • - Controls • Exterior Lighting Requirements: • - Energy Efficient Sources • - Use Load Shedding Devices

  15. Exterior 2003 IECC • Automatically Turn Lights off During Daylight Hours • Photo Cell • Automatic Time Switches • Seven Day/Seasonal Daylight Program • 4 hour Minimum Backup • Exception • Lights Intended for 24-hour Operation

  16. Demonstrating ComplianceSection 104 • Include the following information on the electrical plans • Switching / Dimming schemes • Make/model of exterior lighting controls • Make/model of interior programmable controls • Notes for tandem wiring • Make/model of the occupancy sensors • Sensor placement scheme

More Related