The Scheme of Slow Control System in BESIII

The Scheme of Slow Control System in BESIII. Xie Xiaoxi Gao Cuishan 2002.9.17. Ⅰ . The general prospect of the slow control and Environmental Monitoring in BES. Both slow control system and environmental monitoring are very important and indispensable in the new BES system.

irish
Download Presentation

The Scheme of Slow Control System in BESIII

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. The Scheme of Slow Control System in BESIII Xie Xiaoxi Gao Cuishan 2002.9.17

  2. Ⅰ. The general prospect of the slow control and Environmental Monitoring in BES Both slow control system and environmental monitoring are very important and indispensable in the new BES system. The slow control system must meet the high-level demands of the overall design, overall environment and management in the new BES.

  3. The slow control system , which is numerous and complicated, is mainly applied in experiment area and sub-detectors in BESⅢ. It will play an important role during the operational period of DAQ in the future. This system is composed of 3 main systems • temperature and humidity monitoring • gas system monitoring • controlling high-voltage system.

  4. There are more than 14 kinds of physical parameters and 3000 channels of signals need to be collected and measured. Important parameters related both to the physics analysis and operation of BESⅢ will be stored in the operational database. Parts of these parameters will be sent to online computer system via network communication to be stored in permanent media.

  5. Ⅱ. The main objects and Functions of the BESⅢ monitors and controls for slow control system

  6. The main objects include temperature humidity monitor and control of the mass flow meter for gas providing system control and monitor for HV DC AC magnet and magnetic field dangerous gas radiation monitor T-H control and monitor of hall and control room safety interlock and so on.

  7. Ⅲ.The place of slow control system in online system Event Display Run Control Histogram Display Slow Control 100M Switch 1 Online Farm Supervisor 1000M Switch

  8. Sub Detector Control Sub Detector Monitor IV.Overview of the task architecture of the slow control system for BESⅢ Gas System HV Control Files Tem Hum Control Displays Error Logger Database Editor DAQ Data Stream Slow Control Database Radiation Monitor running running running running running running running Slow Control Devices and Sensors (about 3000 channels)

  9. Ⅴ.Two kinds of bus scheme of data acquisition The primitive bus scheme of data acquisition is USB/one wire bus • Lab window/PXI

  10. The USB/one wire bus scheme can be applied in all the special facilities that can convert the physical parameters to voltage or electric current.

  11. Those facilities which appended with one of these bus interface: such as GPIB、VME、 VXI、 RS232、 CAMAC and so on can adopt the Labwindow/CVI software and NI multichannel card which is plugged in PC.

  12. Sensor Detector VI.The block diagram of slow control system architecture SC1 hardware SCXI H V CAEN SY1527 PXI Gas Patrol meter H V CAEN SY1527 HUB HUB H V CAEN SY1527 SC2 DAQ USB USB USB PC PC P C SC3 Software 100M SWITCH SC4 on line On Line

  13. VII.Client-Server diagram

  14. VIII.Some results have been obtained The research of “one wire bus” About 70% of the 3000 channels of signal could be resolved by “one wire bus” scheme in BESⅢ slow control system. we have implemented temperature/humidity monitoring system with 84 nodes for temperature and 4 nodes for humidity in BESⅡ.

  15. Design for hardware and software of USB interface device. we have finished the design for hardware of USB/CAMAC crate controller, programmed drivers based on USB1.1 of CCU-USB and application program of USB-PC, using C51/VC++6.0/VB6.0. CCU-USB have been successfully used in the check system of shower counter of BESⅡ and scintillation counter hodoscope for testing BESⅢ muon detecter.

  16. The scheme of monitoring of gas system in BESⅢ slow control system

  17. Primary scheme of high-voltage monitoring and control system • All high-voltage modules will adopt SY1527 of CAEN • The modules can be connected with PCI interface card in PC via cables • Software of slow control system will adopt the program language of C++ • Use one independent PC

  18. The block diagram of high-voltage monitor system in slow control system

  19. Thanks!