1 / 16

ERICSON UNIVERSITY LIVE TRAINING SESSION: 4-1 & 4-2 April 2010 GFCI

ERICSON UNIVERSITY LIVE TRAINING SESSION: 4-1 & 4-2 April 2010 GFCI. GFCI. G round F ault C ircuit I nterrupter. Preventing Electrical Equipment Hazards. I. Insulation. Non-conductive material around conductors – wire insulation (THHN, SOW)

farhani
Download Presentation

ERICSON UNIVERSITY LIVE TRAINING SESSION: 4-1 & 4-2 April 2010 GFCI

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ERICSON UNIVERSITY LIVE TRAINING SESSION: 4-1 & 4-2 April 2010 GFCI

  2. GFCI Ground Fault Circuit Interrupter

  3. Preventing Electrical Equipment Hazards I. Insulation • Non-conductive material around conductors – wire insulation (THHN, SOW) • Insulation materials in tools and motors (single and double) • Air gap is normally the second insulation in double insulated tools • Breakdown of insulation results in contact with live conductors • Insulation materials in tools become saturated with carbon brush dust – arc trail “…Insulation may be damaged by hard usage on the job or simply by aging. If this damage causes the conductors to become exposed, the hazards of shocks, burns, and fire will exist. Double insulation may be used as additional protection on the live parts of a tool, but double insulation does not provide protection against defective cords and plugs or against heavy moisture conditions.” - OSHA

  4. Preventing Electrical Equipment Hazards II. Grounding “…Consider, for example, the metal housing or enclosure around a motor or the metal box in which electrical switches, circuit breakers, and controls are placed. Such enclosures protect the equipment from dirt and moisture and prevent accidental contact with exposed wiring. However, there is a hazard associated with housings and enclosures. A malfunction within the equipment—such as deteriorated insulation—may create an electrical shock hazard. Many metal enclosures are connected to a ground to eliminate the hazard. If a "hot" wire contacts a grounded enclosure, a ground fault results which normally will trip a circuit breaker or blow a fuse. Metal enclosures and containers are usually grounded by connecting them with a wire going to ground. This wire is called an equipment grounding conductor. Most portable electric tools and appliances are grounded by this means. There is one disadvantage to grounding: a break in the grounding system may occur without the user's knowledge.” - OSHA • Grounding conductors can be cut, panel ground bad, ground pins pulled out, etc • Plugs replaced on portable tools can be wired incorrectly • Metal gang (job) boxes used as portable power are extremely dangerous!

  5. Anatomy of an Electric Shock Double insulated tool issues: • Carbon dust trails • Moisture trails • Cracked housings • Miswired plugs • Drill chucks are connected to the armature – metal • Cord fraying • Strain relief damage GFCI shuts off power in 25 msec to prevent injury Faster than the human can sense an electric shock!

  6. Metal Gang Box Death Trap Line of Protection Protected NOT Protected • Code Violation • Metal gang boxes are for PERMANENT INSTALLATIONS ( non-moving) • Use rubberized boxes that are UL tested for Portable Power Tap use • Use GFCI inline near the plug or at source Problem # 4 Ground at panel Neutral bond bad GFCI Problem # 3 Cord damage Problem # 1 Loss of Ground (ungrounded box) Problem # 2 Hot wire touching box

  7. Anatomy of a GFCI Line Load Relay Sense ring .5 amp H N .5 amp .4 amp • Rules of GFCI: • 6 mA max • 25 mSec release • break both sides of the line   Electronics Gnd Target = > 6 mA

  8. OSHA REQUIREMENTS General. The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors. • OSHA ( 29 CFR) 1926.404(b)(1)(i) Ground-fault circuit interrupters. All 120-volt, single-phase 15- and 20-ampere receptacle outlets on construction sites, which are not a part of the permanent wiring of the building or structure and which are in use by employees, shall have approved ground-fault circuit interrupters for personnel protection. Receptacles on a two-wire, single-phase portable or vehicle-mounted generator rated not more than 5kW, where the circuit conductors of the generator are insulated from the generator frame and all other grounded surfaces, need not be protected with ground-fault circuit interrupters. Assured Equipment Grounding Continuity Program – cover next month E.U. Session

  9. Interpretation Letter from OSHA (dated May 2002) states the following Q & A: Question (1): Does the requirement in 29 CFR 1926.404(b)(1)(i) to have either a ground-fault circuit interrupter protection (GFCI) or an assured equipment grounding conductor program (AEGCP) apply only to 120 V circuits, or does it also apply to a 240 V circuit?Answer: Yes. §1926.404(b)(1)(i) provides:(b) Branch circuits -- (1) Ground-fault protection - (i) General. The employer shall use either ground fault circuit interrupters as specified in paragraph (b)(1)(ii) of this section or an assured equipment grounding conductor program as specified in paragraph (b)(1)(iii) of this section to protect employees on construction sites. These requirements are in addition to any other requirements for equipment grounding conductors. Under this provision, employers must provide protection against ground-fault by using either a GFCI or AEGCP. The provision, by its terms, is not limited to 120 V circuits. Employers are required to protect employees under this provision with respect to 240 V circuits as well. Question (2): What are the requirements when a temporary service panel has both a 120 V and a 240 V circuit? Would protecting the 120 V circuit with a GFCI comply with the standard, or does the 240 V circuit also have to be protected by a GFCI or an assured equipment grounding conductor program? Answer: The 240 V circuit must be protected as well. Installing a GFCI designed for a 120 V circuit in a panel that also has a 240 V circuit will not provide ground-fault protection to the 240 V circuit. While technically the option of using GFCI under (b)(1)(ii) is available only for 120 V circuits, that limitation was put in the standard only because GFCIs for 240 V were generally unavailable when the standard was promulgated. Employers may choose to use GFCIs designed for 240 V to protect 240 V circuits; the technical violation of (b)(1)(ii) would be considered de minimis. De minimis violations are those which have no direct or immediate relationship to safety or health. Citations are not issued for de minimis violations.

  10. GFCIs and NEC 2008 • Article 590.6 calls for basically all receptacles that are in use to be GFCI protected. Again OSHA considers this violation minor and citations are not being given at this time.

  11. GFCIs and Lighting • OSHA does not call for lighting circuits to be GFCI protected. • NEC 525.23(c) specifically states that egress lighting shall not be GFCI protected.

  12. Auto vs Manual • Auto = Auto powerup start • Manual = Manual powerup start • RESET button serves as initial “start” button • ALL GFCIs must be physically RESET after a fault trip • Automatically Reseting GFCIs do not exist

  13. Industrial Grade Commercial Grade GFCI Offerings 90 Degree Plug Inline Style Panel Mount Custom Industrial Grade • Add-a-cord • Some corded models

  14. Protector Series Launch

  15. Distribute / Split Phases / GFCI Protection Distribute Point to Point Only Cordsets Oscars Gen Cords Big-E Jr Big-E Distribute Multiple Taps Distribute / High Power ( 480 or 600 V ) 480V Big-E “Y” “W” Power Stringers 6000 7000 8000 Series Transform / Distribute / GFCI Protect Distribute with GFCI Protection e-Cart Jr. e-Cart GFCI 1060/1070

  16. END OF SESSION

More Related