Zone Selective Interlocking (ZSI)

Zone Selective Interlocking (ZSI). Functionality and Structure of ZSI For short circuit and ground fault as well Application Guide. t sd = 300 ms. ZSI. ZSI. t sd = 300 ms. ZSI OUT. ZSI OUT. t sd = 200 ms. ZSI. ZSI IN. ZSI IN. ZSI. t ZSI = 50 ms. ZSI OUT. ZSI OUT.

eben
Download Presentation

Zone Selective Interlocking (ZSI)

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Zone Selective Interlocking (ZSI) Functionality and Structure of ZSIFor short circuit and ground fault as well Application Guide

  2. tsd = 300 ms ZSI ZSI tsd = 300 ms ZSI OUT ZSI OUT tsd = 200 ms ZSI ZSI IN ZSI IN ZSI tZSI = 50 ms ZSI OUT ZSI OUT tZSI = 50 ms ZSI ZSI IN ZSI OUT Example: ZSI function in the event of a short-circuit A) B) ZSI ZSI ZSI ZSI ZSI ZSI ZSI ZSI

  3. tg = 500 ms ZSI ZSI tg = 500 ms ZSI OUT ZSI OUT tg = 400 ms ZSI ZSI IN ZSI IN ZSI tZSI = 100 ms ZSI OUT ZSI OUT tZSI = 100 ms ZSI ZSI IN ZSI OUT Example: ZSI function in the event of a ground fault A) B) ZSI ZSI ZSI ZSI ZSI ZSI ZSI ZSI

  4. ZSI ZSI Example: ZSI function in the event of a short-circuit ZSI OUT 1 ZSI tsd = 300 ms ZSI IN With ZSI and without ZSI function in grading level 3 ZSI OUT ZSI ZSI tZSI = 50 ms tsd = 200 ms Trip 2 tsd = 0 ms  tsd = 100 ms tsd = 100 ms ZSI Trip 3

  5. Thank you for your attention! Zone Selective Interlocking (ZSI) Rainer Huentemeier Productmanager I BT LV GC MCCB V2.0 2010