Freeze of Nozzle/Receptacle during Hydrogen Fueling

Freeze of Nozzle/Receptacle during Hydrogen Fueling. Wataru Hiraki 1 , Hiroyuki Mitsuishi 1 1 Japan Automobile Research Institute. Hydrogen station. http://hysut.or.jp/. Compressor. Pressure vessel. Dispenser. FCV. Overpressure. 87.5. Overfill. SOC 100%. 70. Pressure [MPa]. Overheat.

ahaddad
Download Presentation

Freeze of Nozzle/Receptacle during Hydrogen Fueling

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Freeze of Nozzle/Receptacle during Hydrogen Fueling Wataru Hiraki1,Hiroyuki Mitsuishi1 1Japan Automobile Research Institute

  2. Hydrogen station http://hysut.or.jp/ Compressor Pressure vessel Dispenser FCV Overpressure 87.5 Overfill SOC 100% 70 Pressure [MPa] Overheat use Pre-cool 15 85 -40 Temperature [°C] Hydrogen station is possible about fast-fueling safely, using pre-cool

  3. Issue of nozzle/receptacle freeze lock Receptacle Nozzle Disconnection Freeze lock Ice forms during fueling which causes the nozzle and receptacle to freeze together. This phenomenon is not specific to a single nozzle/receptacle design.

  4. Object Safety evaluation of the nozzle/receptacle freeze lock Confirmation of a water amount to cause the freeze lock

  5. Test condition & Experiment setup Fueling gas: Hydrogen, 35 MPa Gas temperature: -40°C Gas Sensor Ambient temperature: 30°C Hydrogen Ambient humidity: 95 %RH Flow rate: 650 g/min T Fueling time: 3 min Test interval: 10 min Thermocouple T T Nozzle: A, B(Two types) N2 T Water added : Nozzle, Receptacle Nozzle Receptacle Nitrogen Condition for the end of the test: Freeze lock occured or pass for 5 times Incubator

  6. Experiment setup Receptacle Incubator Receptacle Nozzle connected nozzle

  7. Disconnect procedure (1) Slidable locking sleeve is released (2) Draw out the nozzle  ⇒disconnect Chuck Receptacle Receptacle Receptacle (1') Chuck goes up (※Shape of the sleeve and inner chuck are estimated) Chuck Procedure for identification of freeze lock Sleeve Sleeve Sleeve • Check immediately after the fueling • Action for the disconnection; • Revolve → Release the locking mechanism → Draw out • Identify as freeze lock if the nozzle is not disconnected in the above condition Nozzle Nozzle Nozzle Chuck

  8. Water Spraying Position Receptacle Nozzle Hydrogen Gas Line Pin Cover spray Nozzle Receptacle Sleeve Chuck Fitting part Fitting part

  9. Freeze lock

  10. Freeze lock

  11. Freeze lock

  12. Freeze lock

  13. Result Freeze lock is caused by water inside the nozzle. Hydrogen does not leak from the nozzle/receptacle even if the nozzle/receptacle were freeze lock. Freeze lock does not cause any damage of the equipment.

  14. Estimation of freezing part Chuck Receptacle Clearance of sleeve Chuck part Fitting part Sleeve Nozzle Estimated freezing part:Clearance of sleeve, Chuck part

  15. Effect of a water amount on freeze lock Water injection method Micropipette Nozzle head Water is injected to the nozzle inside before fueling. Connect to receptacle and flow -40°Cgas Freeze lock?

  16. Test condition & Experiment setup Fueling gas: Hydrogen, 35 MPa Gas Sensor Gas temperature: -40°C Hydrogen Ambient temperature: 30°C Ambient humidity: 60 %RH Flow rate: 650 g/min Thermocouple Fueling time: 3 min T T N2 Nozzle: A Nozzle Receptacle Water added : injection the Nozzle Incubator Nitrogen

  17. Result of Quantification After fueling Freeze lock

  18. Conclusions ・ The nozzle and the receptacle are safely, even if the freeze lock occurred ・ The freeze lock is caused by the water freezing in the locking mechanism of the nozzle ・ The freeze lock occurred after fueling when water of 1000 μL over 750 μL injected to the nozzle A

  19. Next step Experiment of the freeze lock Investigation of the freeze lock with other nozzles. Investigation of ambient condition when the freeze lock occurs. Investigation of a technique that protect the freeze lock. Proposition of the freeze lock testing condition and procedure

  20. ACKNOWLEDGEMENTS This study is a summary of the “Hydrogen Using Technology Research and Development Project”, and the "Hydrogen production, transportation and storage system technology development" under consignment by the New Energy and Industrial Technology Development Organization (NEDO). Thank you for your attention