The three-phase alternator, as the name suggests, has three single-phase windings spaced so that the voltage induced in one of the phases is offset by 120 u00b0 with respect to the other two. A schematic diagram of a three phase stator showing all the coils gets complex and it is difficult to see what is really going on.

Tabish
Download Presentation

A few words about the three

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. A few words about the three-phase alternator Introduction The three-phase alternator, as the name suggests, has three single-phase windings spaced so that the voltage induced in one of the phases is offset by 120 ° with respect to the other two. A schematic diagram of a three phase stator showing all the coils gets complex and it is difficult to see what is really going on. The rotor is omitted for simplicity. The voltage waveforms generated across each phase are plotted on a graph, phase shifted 120 ° from each other. The three-phase alternator shown in this diagram is made up of three single-phase alternators whose generated voltages are 120º out of phase. The three phases are independent of each other. Rather than having six conductors out of the alternator, the same conductors of each phase can be connected together to form a star connection (y), as shown in figure 1, see b. It's called a star connection because, without the neutral, the windings appear under the letter y, in this case sideways or top to bottom. The neutral connection is highlighted at a terminal when a single phase load is to be supplied. Single-phase voltage is available from neutral to a, neutral to b and neutral to c. In a three-phase alternator connected in y, the total voltage, or line voltage, between two of the three line conductors is the vector sum of the voltages individual phase. Each line voltage is 1.73 times one of the phase voltages. Because the windings form only one path for the current between the phases, the line and phase currents are the same (equal). A three-phase stator can also be connected so that the phases are connected end to end; it is now connected in delta (fig. 1, view c). (Delta because it looks like the Greek letter delta,) In the delta connection, the line voltages are equal to the phase voltages, but each line current is equal to 1.73 times the phase current. Star and delta connections are used in alternators.

  2. The majority of alternators currently in use are three-phase machines. They are much more efficient than two-phase or single-phase alternators. Three-phase connections The stator coils of three-phase alternators can be interconnected by star or delta connections, as shown in figure 2. With these connections, only three wires come out of the alternator. This allows convenient connection to three-phase motors or power distribution transformers. It is necessary to use three-phase transformers or their electrical equivalent with this type of system. A three-phase transformer can consist of three single-phase transformers connected in delta, wye, or a combination of the two. If the primary and secondary are star connected, the transformer is called a wye-wye. If the two windings are connected in delta, the transformer is called delta-delta. Figure 3 shows single-phase transformers connected delta-delta for operation in a three-phase system. You will notice that the transformer windings are not angled to illustrate typical operation. Delta (∆) as was done with the alternator windings. Physically, each transformer in the diagram is autonomous. There is no angular relationship between the windings of the individual transformers. However, if you follow the connections, you should see that they form an electrical delta. Primary windings, for example, are connected to each other to form a closed loop. Each of these junctions is supplied with phase voltage by a three-phase alternator. The alternator can be connected in delta or star depending on the load and voltage requirements and the system design. Three wye-wye connected single-phase transformers. Again, note that the transformer windings are not angled. Electrically, a y is formed by the connections. The bottom connections of each winding are shorted together. These form the common point of the wye.

  3. The opposite end of each winding is insulated. These ends form the arms of the eye. Alternating current on most ships is distributed through a three phase, three wire, and 450 volt system. Single-phase transformers lower the voltage to 117 volts. These transformers are delta-delta connected as in figure 3. With a delta-delta configuration, the load can be a three-phase device connected to all phases; or, it can be a single phase device connected to a single phase. At this point, it is important to remember that such a distribution system includes everything between the alternator and the load. Due to the many choices offered by three phase systems, care should be taken that any change in connection does not provide the load with an incorrect voltage or phase. Output frequency The output frequency of the alternator voltage depends on the rotational speed of the rotor and the number of poles. The faster the speed, the higher the frequency. The lower the speed, the lower the frequency. The more poles there are on the rotor, the higher the frequency is for a given speed. When a rotor has rotated by an angle such that two adjacent rotor poles (a north pole and a south pole) have passed through a winding, the voltage induced in that winding will have varied by one full cycle. For a given frequency, the more pairs of poles there are, the lower the speed of rotation. This principle is illustrated in figure 5; a bipolar generator must spin four times faster than an eight pole generator to produce the same frequency of generated voltage. The frequency of any alternating current generator in hertz (hz), which is the number of cycles per second, is related to the number of poles and the speed of rotation, expressed by the equation: F = np / 120

  4. Where p is the number of poles, n is the rotational speed in revolutions per minute (rpm) and 120 is a constant allowing the conversion of minutes to seconds and of poles to pole pairs. Examples For example, a 2-pole 3600 rpm alternator has a frequency of 60 Hz; determined as follows: (2 x 3600) / 120 = 60 Hz A 4-pole 1800 rpm generator also has a frequency of 60 hz. A 6-pole, 500 rpm generator has a frequency of: (6 x 500) / 120 = 25 Hz A 12-pole generator, 4000 revolutions / minute has a frequency of: (12 x 4000) / 120 = 400 Hz