Disturbances due to high frequency signals (above 2 kHz). Martin Lundmark EMC on Site martin.lundmark@ltu.se. OUTLINE. BACKGROUND CONDUCTIVE AND RADIATED EMISSION IN A THREE-PHASE GRID ORIGIN OF CONDUCTIVE HIGH-FREQUENCY LEAKAGE CURRENT MEASUREMENTS CONCLUSION. BACKGROUND

wallis
Download Presentation

Disturbances due to high frequency signals (above 2 kHz)

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Disturbances due to high frequency signals (above 2 kHz) Martin Lundmark EMC on Site martin.lundmark@ltu.se

  2. OUTLINE • BACKGROUND • CONDUCTIVE AND RADIATED EMISSION IN A THREE-PHASE GRID • ORIGIN OF CONDUCTIVE HIGH-FREQUENCY LEAKAGE CURRENT • MEASUREMENTS • CONCLUSION

  3. BACKGROUND • Sign of HF-harmonics • PWM motor drives - motor bearing currents • TV and audio studios - disturbances • Power Line Communication - signal interference • Distribution transformers - damage • Power supply units - damage • Cable and cable termination - damage • Electronic office equipment - malfunction • Fluorescent lights - league currents

  4. BACKGROUND • CHANGING CIRCUMSTANCES IN POWER LOADS… • The use of power electronics • Faster changesin loads than in the power grid • …AND IN COMMUNICATION • The changes from analogue to digital communications technique • The radiated emission of electronic equipment is limited with respect to analog radio communications services

  5. BACKGROUND The changes from analogue to digital communications technique

  6. CONDUCTIVE AND RADIATED EMISSION IN A THREE-PHASE GRID

  7. CONDUCTIVE EMISSION IN A THREE-PHASE GRID

  8. ORIGIN OF CONDUCTIVE HF LEAKAGE CURRENT Symmetrical load current in a three phase system

  9. ORIGIN OF CONDUCTIVE HF LEAKAGE CURRENT Symmetrical load current, including harmonics, in a three phase system

  10. ORIGIN OF CONDUCTIVE HF LEAKAGE CURRENT Symmetrical load current, including HF- harmonics, in a three phase system

  11. ORIGIN OF CONDUCTIVE HF LEAKAGE CURRENT Symmetrical load current, including HF- harmonics, in a three phase system 1 1 A 2 kHz high-pass filter used on the simulated neutral current from HF fluorescent lamps in three-phase connection A detail of the left graph shows the damped peak having about a 156 microsecond period time, a frequency close to 6.4 kHz. 1

  12. Symmetrical load current, including HF- harmonics, in a three phase system <2 kHz >2 kHz Neutral current (RMS) when increasing the numbers of three-phase connected HF-fluorescent lamps, unfiltered upper left, 2 kHz high-pass filter down left. To the right- the neutral current shown on the left is divided by the number of three-phase connected groups of HF-fluorescent lamps.

  13. Symmetrical load current, including HF- harmonics, in a three phase system 1 Highest peak value in neutral current above 2 kHz when increasing the numbers of three-phase connected HF fluorescent lamps, to the left. To the right, the peak value is divided by the number of three-phase connected groups of HF fluorescent lamps.

  14. Symmetrical load current, including HF- harmonics, in a three phase system Z 100 m Z = R + jX The impedance for 2.5 mm 2 Cu wire with a length of 100 m upper line, 30 m middle line and 1 m lower line. 1 m 30 m

  15. ORIGIN OF CONDUCTIVE HF LEAKAGE CURRENT Symmetrical load current, including HF- harmonics, in a three phase system Calculations on the neutral peak voltage with increasing numbers of HF-fluorescent lamps with (upper line) and with only the wire resistance (lower line). Z = R + jX, for 2.5 mm2 Cu wire with a length of 30 m

  16. ORIGIN OF CONDUCTIVE HF LEAKAGE CURRENT

  17. MEASUREMENTS

  18. Communications failures on a specific communication line in a server room powered by a 50 kVA uninterruptible power supply P-N N-PE P-PE

  19. MEASUREMENTS A- building, in the office part of the LTU Skellefteå Campus.

  20. MEASUREMENTS D-building, first floor, adjacent to room 3045.

  21. MEASUREMENTS A- building D-building, first floor

  22. CONCLUSION • It is possible to find HF- harmonics, almost everywhere in power grids. • The origin to the HF- harmonics is finding in power electronics in domestic, commercial and industrial equipment. • The number of emitting devices is growing significantly. • Literature describes interference on electronic office equipment, in TV and audio studios and in power grid using power line communication due to HF- harmonics, to give some examples. • Literature also describes damage in distribution transformers, cable and cable termination and in motor bearings due to HF- harmonics. • While the symmetrical fundamental frequency current is cancelled and the zero-sequence harmonics is summarized in the neutral wire the HF- harmonic current increased when the number of loads symmetrically increased in the three phases, and there was almost no cancellation. • Adding the effect of increasing impedance in wires resulting from increasing frequency, one origin of conductive high-frequency leakage current in the grid is shown.