Flammable and Combustible Liquids

Flammable and Combustible Liquids. Flammable liquids. Class I - liquids have flashpoints below 100 degrees F, with vapor pressures not exceeding 40 psia Class IA - liquids having flashpoints below 73 degrees F and boiling points below 100 degrees F. 1a. Flammable liquids.

sebille
Download Presentation

Flammable and Combustible Liquids

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Flammable and Combustible Liquids

  2. Flammable liquids • Class I - liquids have flashpoints below 100 degrees F, with vapor pressures not exceeding 40 psia • Class IA - liquids having flashpoints below 73 degrees F and boiling points below 100 degrees F 1a

  3. Flammable liquids • Class IB - liquids having flashpoints below 73 degrees F and boiling points at or above 100 degrees F • Class IC - liquids having flashpoints at or above 73 degrees F and below 100 degrees F 1b

  4. Flammable liquids • Flammable liquids give off ignitable vapors 1c

  5. Combustible liquids • Class II liquids have flashpoints at or above 100 degrees F and below 140 degrees F 1d

  6. Combustible liquids • Class III liquids have flashpoints at or above 140 degrees F • Class IIIA liquids have flashpoints at or above 140 degrees F and below 200 degrees F • Class IIIB liquids have flashpoints at or above 200 degrees F 1e

  7. Handling and storage procedures • Two forms of storage: • Reserve storage in drums • Operational storage in small quantities at work stations • Connect drums to a grounding system 2a

  8. Handling and storage procedures • Liquids can be dispensed by two methods: • Gravity flow • Pump methods 2b

  9. Handling and storage procedures • Areas where flammable liquids are transferred from one container to another must: • be protected from ignition sources • have drainage or other methods to control spills • have natural or mechanical ventilation 2c

  10. Handling and storage procedures • Store flammable liquids in approved safety cans 2d

  11. Handling and storage procedures • Flammable liquids used at workstations must not exceed the sum of: • 25 gallons of Class IA liquids in containers • 120 gallons of Classes IB, IC, II, or III liquids in containers • 660 gallons of Class IB, IC, Class II, or Class IIIA liquids in a single portable tank 2e

  12. Handling and storage procedures • Use specially designed waste cans for the disposal of waste • Remember that it is the vapors, not the liquid that burns • Use specially developed absorbent materials for spill cleanup 2f

  13. Handling and storage procedures • Compressed Gas Cylinders 2f

  14. Flood emergencies If flammable liquids are stored in tanks, review and understand the location and contents of flood emergency instructions • Emergency action plans 3a

  15. Flood emergencies and storage tanks • Keep debris and vegetation away from the tank area • Situate tanks in areas where high-level water will not occur • Anchor horizontal tanks if more than 70 percent of the tank’s capacity will be submerged 3d