1 / 17

NSLS-II Shielding Workshop

NSLS-II Shielding Workshop. S. Buda Personnel Protective Systems March 27, 2007. Design Goals Personnel Protection System . Protects personnel from high radiation areas by preventing access and controlling radiation producing devices Linac (LPPS) Booster Ring (BPPS) Storage Ring (APPS)

lamya
Download Presentation

NSLS-II Shielding Workshop

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NSLS-II Shielding Workshop S. Buda Personnel Protective Systems March 27, 2007

  2. Design Goals Personnel Protection System Protects personnel from high radiation areas by preventing access and controlling radiation producing devices • Linac (LPPS) • Booster Ring (BPPS) • Storage Ring (APPS) • Experimental Beam Lines (PSS) • RF test cell area

  3. NSLSII Facility Hazards Linac Hazards • Accelerated electrons • Dark Current Main Ring /Booster Hazards • Radiation produced from secondary emissions in RF cavities (Both main ring and booster RF cavities) • Accelerated electrons • Synchrotron and Bremsstrahlung radiation • Oxygen Deficiency Alarm (ODH) (RF Cavity and cryo plant) Experimental Beam Lines hazards • Synchrotron and Bremsstrahlung radiation

  4. Linac Area

  5. NSLSII Storage Ring

  6. Design Goals Personnel Protection System • Modular • Simple as possible to carry out task • Designed with testing as a key feature • Meet DOE and BNL requirements for Interlocks • Quality assurance system • Flexibility for expansion and modification • Diverse Component Selection • Ability to be upgraded with technology • Diagnostic capability

  7. Technical Description Personnel Protection Systems • Dual chain PLC architecture (one safety rated) • Modular • Designed with testing as key consideration • Reliability and availability emphasized • Reduce wiring where possible • Use fiber optic busses for interference and security • Compatible I/O for all systems • Separate safety and command functions in beam line systems

  8. Technical Highlights of Personnel Protection Systems • Integration of Radiation monitors with the main ring system (APPS) 40+ locations • Main ring divided into 6 separate sections for modular concept. • Main ring uses a distributed I/O system • Interface to APICS for archiving of system data • Use of safety rated PLC’s to increase reliability and diagnostic capability

  9. Other Design Features • Interlock system must allow: • Linac operable with personnel in booster • Booster operable with personnel in storage ring • All interlock logic trees will have redundant and independent chains • The system will be fail safe for foreseeable failure modes (e.g., loss of power/pressure, open circuit, short to ground, and single component failure • Redundant circuits will not share cables and should be separated physically on circuit boards and terminal strips. Redundant systems should be configured differently.

  10. Other Design Features (Cont.) • A rigorous configuration management program will be established to control unauthorized modifications to interlock system components • All interlock lines and components will be labeled and readily identifiable. • Testing & certification of interlock systems will be performed by independent personnel • Design for enclosure search systems will include sequenced and timed inspection stations, warning lights, audible alarms, and emergency off- switches.

  11. NSLS X-RAY INTERLOCK LOGIC

  12. NSLS VUV INTERLOCK LOGIC

  13. NSLS INJECTOR INTERLOCK LOGIC

  14. NSLS STANDARD SHUTTER LOGIC

  15. SYSTEM CONFIGURATION CONTROL PHYSICAL ACCESS CONTROL CABLE IDENTIFICATION

  16. STANDARD LASER INTERLOCK

  17. INJECTOR INTERLOCK PLC

More Related