Zonepro modulating thermostats
Download
1 / 23

ZonePRO™ Modulating Thermostats - PowerPoint PPT Presentation


  • 94 Views
  • Uploaded on

ZonePRO™ Modulating Thermostats. Technical Training July 10, 2006. Models and Features. Models with 1 output TB6980A1007 (Floating) TB7980A1006 (Analog 0-10V or 2-10V) Models with 3 outputs TB6980B1006 (1 st output is floating) TB7980B1005 (1 st output is analog 0-10V or 2-10V)

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about ' ZonePRO™ Modulating Thermostats ' - ginger


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
Zonepro modulating thermostats

ZonePRO™ Modulating Thermostats

Technical Training

July 10, 2006


Models and features
Models and Features

  • Models with 1 output

    • TB6980A1007 (Floating)

    • TB7980A1006 (Analog 0-10V or 2-10V)

  • Models with 3 outputs

    • TB6980B1006 (1st output is floating)

    • TB7980B1005 (1st output is analog 0-10V or 2-10V)

    • 2nd output can be configured for:

      • Analog 0-10V

      • Analog 2-10V

      • 24V

    • 3rd output is 24V only

  • Features for all models

    • Automatic changeover (duct sensor required)

    • Manual changeover (remote switch or relay required)

    • Night setback

    • Min and Max temperature setpoint stops


Applications and accessories
Applications and Accessories

  • Hydronic and pressure dependent VAV with or without reheat

  • Non-programmable

  • Up to three outputs depending on model

  • Can be used for:

    • Floating or Analog damper/valve actuator control

    • Damper/valve actuator with duct reheat and aux heat (B models)

    • Hydronic systems (room control, perimeter heating and cooling)

  • Compatible accessories

    • R841 family of electromechanical relays

    • 50014156-002 remote room sensor

    • 50014157-001 duct temperature sensor

    • 32004800-001 bare thermistor



Typical applications
Typical Applications

Relay

24 VAC not COM

TB6980B

Damper control with electric reheat and auxiliary hot-water heating


Typical applications1
Typical Applications

Relay

TB7980B

Relay

Damper control with electric reheat and auxiliary baseboard heating


Typical applications2
Typical Applications

50014157-001

Relay

TB7980B

Damper control with automatic changeover, electric reheat and central cooling


Typical applications3
Typical Applications

50014157-001

Relay

TB6980B

Temperature control of fresh air supply


Typical applications4
Typical Applications

TB7980B

TB7980B

TB7980B

Changeover and NSB inputs sharing the same 24-Vac transformer


Configuration tb7980b1005
Configuration – TB7980B1005

Default configuration


Configuration tb6980b1006
Configuration – TB6980B1006

Default configuration


Configuration menu tb6980b
Configuration menu TB6980B

Output 1 Activation

output 1 default mode



Configuration menu tb6980b2
Configuration menu TB6980B

Output 2 Activation

output 1 default mode

Output 1 jumps at 100% if there is an instant 5°F difference



Configuration menu tb6980b4
Configuration menu TB6980B

Output 3 Activation

Output 1 jumps at 100% if there is an instant 5°F difference

output 1 default mode

Output 2 jumps at 100% if there is an instant 11°F difference



Configuration menu tb6980b6
Configuration menu TB6980B

Output 3 Activation “Contact Mode”

output 1 default mode


Configuration and operation
Configuration and Operation

  • Configuration

    • Dip switches

      • Temperature display, F or C (SW1)

      • Access mode (SW2)

      • Output 2 type (SW6)

        • This sets output 2 type (analog or triac)

  • Operation

    • Backlight (on for 12 seconds)

    • Temperature setting by 1° increments (2°F in changeover)

    • Output display (Hold Override for 4 seconds)


Operation continued
Operation (continued)

  • Operation

    • Changeover

      • Manual changeover (contact)

      • Automatic changeover (9°F differential between duct and room)

      • Night setback

  • Override (2 hours)

  • Error codes

    • E1 (internal sensor defective)

    • E2 (internal sensor shorted)

    • E3 (external temperature sensor defective or not connected)

    • E4 (external temperature sensor shorted)


System components

ML6984

VC7930

ZonePRO

MN7505

ST7009

System Components


Literature and point of purchase materials
Literature and Point of Purchase Materials