1 / 25

Software of Programmable Controllers

Slovak University of Technology Faculty of Material Science and Technology in Trnava. Software of Programmable Controllers. 2007. Programmable controller KRGN 90. 8 - loop controller HW configurable I/O signal more than 40 pre-programmed functions operator panel operator interface

cyndi
Download Presentation

Software of Programmable Controllers

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Slovak University of Technology Faculty of Material Science and Technology in Trnava Software of ProgrammableControllers 2007

  2. Programmable controller KRGN 90 • 8 - loop controller • HW configurable I/O signal • more than 40 pre-programmed functions • operator panel • operator interface • engineering functions • 4 displays to monitor a controlled processes • communication protocol...

  3. KRGN 90 - operator interface • Displays • DATA - VALUE • Set Point • PROCESS • OUTPUT • ALARMS

  4. KRGN 90 - operator interface • Keys • Set Point • MAN, AUTO, CAS • Man Reset • PP, II, DD • ACK

  5. KRGN 90 - eng. functions • Displays • Object - step - function - data - value • AI configuration • CONF / AUX - ANAL • Loop configuration • CONF / AUX - LOOP • INS - RPL - DEL

  6. Analogue input configuration • CONF - ANAL- AInn • FNC 01 - Q1, Q2, Q3, Q4... • AUX - ANAL - Ainn • DFIL, ISCL, ISCH • IALL, IALH, • ISFL, ISFH, SAFE • ANAL - Ainn • AI type assignment to the physical AInn

  7. Loop configuration • CONF - LOOP- l • FNC 10, FNC 20, FNC 55 • AUX - LOOP - l • SCAN, OLIL, OLIH, OGRL, OGRH • LSCL, LSCH, GRAD • PALL, PALH, DALL, DALH • DINL, DINH, GAPL, GAPH... • LOOP • ON / OFF

  8. Loop program structure • Controller KRGN 90 has 8 LOOPs • Loop has 20 program STEPs maximum • Program step consists one function FNCnn • Function has questions Q1,Q2, Q3,...

  9. FNC 01 - AI processing • Purpose: The unified analogue signal transformation to digital representation in e.u. and primary input variable processing. • Q1 – a type of current unified input signal • Q2 – linearisation type • Q3 – binary output for technological alarm signalisation • Q4 – safety alarm signalisation

  10. FNC 10 - step signal specification • An value assignment to the real and logical part of program step output, where the function FNC 10 is configured. • Q1 – real part of the program step value • Q2 – logical part of the program step specification

  11. FNC 20 - PID function • The ideal paralel type of a PID algorithm as a sum of the proportional, integral and derivative part of a control action. • Q1– the type of the set point processing when a loop is switched from MAN to AUTO mode. • Q2 – control action direction • Q3 – loop mode after controller restart

  12. FNC 20 - PID function FNC 20 continued: • Q4 – type of the derivative part of control action • Q5 – binary variable address for process variable alarm • Q6 – binary vaariable address for deviation alarm • Q7 – control action computation type

  13. FNC 21 – Set Point computation for cascade loop • A computation of the set point for a slave loop in cascade mode. • A set point of the cascade loop is computed according the expression ZHCAS = RATIO*INPUT+BIAS • Q1 – signal source specification

  14. FNC 22 – Auto RATIO • On line computation of the slave loop RATIO for a bumpless switching the AUTO mode to the CAS one • Q1 – signal source specification

  15. FNC 23 – Auto BIAS • On line computation of the slave loop BIAS for a bumpless switching the AUTO mode to the CAS one • Q1 – signal source specification

  16. FNC 24 - SP computation for slave loop • A set point computation for a cascade loop, when the limits of this set point are given. • Q1 – loop number

  17. FNC 30- arithmetic operations • Arithmetic operations: sum, difference, multiplication and division. • Q1 – the second operand • Q2 – type of arithmetic operation • Q3 – order of operands

  18. FNC 50 – Dynamic signal compensation • Dynamic compensation of a signal by the block LEAD/LAG of 1st order. • Q1 – lead time constant in the interval 0 to 99999 sec. • Q2 – lag time constant in the interval 0.5 to 99999 sec.

  19. FNC 51 – Dead Time Block • A delay of a main value signal at a specified time. • Q1 – time delay in the interval 0.5 to 99999 sec.

  20. FNC 55 – D/A conversion • A conversion of a control action value to the corresponding analogue unified signal. • Q1 – type of analogue current unified signal • Q2 – signal specification

  21. Auxiliary parameters for AI • DFIL – the time constant of 1st. order digital filter • ISCL – input scale lower • ISCH – input scale upper • IALL – lower limit for technological alarm • IALH – upper limit for technological alarm

  22. Auxiliary parameters for AI • ISFL – input safety lower value • ISFL – input safety lower value • SAFE - safety/ default value of input signal

  23. Auxiliary parameters for LOOP • SCAN – program loop execution scan period • OLIL – lower limit of control action • OLIH – upper limit of control action • OGRL – maximum rate of valve closing rate during one scan period • OGRH – maximum rate of valve opening rate during one scan period

  24. Auxiliary parameters for LOOP continued • GRAD – maximum rate of set point change during one scan period • LSCL – lower limit of set point • LSCH – upper limit of set point • PALL – lower limit of process variable alarm • PALH – upper limit of process variable alarm • DALL – lower limit of deviation alarm • DALH – upper limit of deviation alarm

  25. Auxiliary parameters for LOOP continued • DINL – deviation lower limit indicated on the bargraph • DINH – deviation upper limit indicated on the bargraph • GAPL – lower hysteresis band for control action execution • GAPH – upper hysteresis band for control action execution

More Related