Ultima xl xt gas monitors providing hart and 4 20ma output
Download
1 / 13

0mA output - PowerPoint PPT Presentation


  • 301 Views
  • Uploaded on

Ultima ® XL/XT Gas Monitors Providing HART and 4-20mA output. Ultima XL / XT Gas Monitors. HART: General Information Network Topology Ultima XL/XT Features Calibration Options Approvals Sales Support . HART – General Information. HART (Highway Addressable Remote Transducer)

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about '0mA output' - Melvin


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
Ultima xl xt gas monitors providing hart and 4 20ma output l.jpg

Ultima® XL/XT Gas MonitorsProviding HART and 4-20mA output


Ultima xl xt gas monitors l.jpg
Ultima XL / XT Gas Monitors

  • HART:

    • General Information

    • Network Topology

  • Ultima XL/XT Features

  • Calibration Options

  • Approvals

  • Sales Support


Hart general information l.jpg
HART – General Information

  • HART (Highway Addressable Remote Transducer)

  • MSA device is a slave in a polled network

  • HART is a software protocol running over 4-20mA Hardware

  • Point to point

  • 1200 baud FSK


Hart general information con t l.jpg
HART – General Information con’t

  • HART Communication is a bi-directional industrial field communication protocol used to communicate between intelligent field instruments and host systems.

  • HART provides two simultaneous communication channels: the 4-20mA analog signal and a digital signal. The 4-20mA signal communicates the primary measured value (in the case of a field instrument) using the 4-20mA current loop - the fastest and most reliable industry standard. Additional device information is communicated using a digital signal that is superimposed on the analog signal. The digital signal contains information from the device including device status, diagnostics, additional measured or calculated values, etc. Together, the two communication channels provide a complete field communication solution that is easy to use and configure, is low-cost and is very robust.

    Visit www.hartcomm2.org for more information



Ultima xl xt features l.jpg
Ultima XL/XT Features

  • Non-display versions of XE & XA

  • Single sensor gas monitor

  • Enclosure options

    • Stainless steel - XL

    • Polycarbonate G.P. - XT

  • Condulet has openings for:

    • Sensor entry

    • Intrinsically Safe HART Port (optional)

    • Signal and Power Wiring

  • Internal Push-button & LEDs for Calibration

  • Available in Remote Condulet Versions


Ultima xl xt features7 l.jpg
Ultima XL/XT Features

Main board configuration

  • Similar to the UltimaX main board

  • Single removable design with standoffs

  • No tools required for insertion into the condulet


Ultima xl xt calibration options l.jpg
Ultima XL/XT Calibration Options

  • Calibration utilizing:

    • Internal push-button and LEDs (intrusive)

    • Portable handheld communicator, host DCS or laptop

    • Disconnect under power (in-shop calibration)

    • Sensor X-change program


Ultima xl xt local calibration l.jpg
Ultima XL/XT Local Calibration

  • Utilizes internal push-button & LEDs to perform local calibration without the need of the HART communicator.


Fm approvals globally l.jpg
FM Approvals Globally

  • US/Canada

    • Class I Div 1&2 Groups A,B,C,D

    • Class I Zone 1&2 Groups IIC, IIB, IIA, T6

    • Type 4X, IP 66

  • Europe

    • ATEX II 2G 3G EEx d nA [ib] IIC T6

    • IP 66

  • International

    • IEC Ex d nA [ib] IIC T6

    • IP 66


Sales support l.jpg
Sales Support

  • Customer requirements

    • HART handheld controller

      • Must be compatible with the Emerson 375

      • Emerson 275 will NOT work

      • HART Rev 6 or Rev 7

    • Latest DD’s downloaded to handheld controller

      • A Device Description (DD) is an electronic data file prepared in accordance with Device Description Language specifications that describes specific features and functions of a device including details of menus and graphic display features to be used by host applications (including handheld devices) to access all parameters and data in the corresponding device.

      • Download from Emerson website (or other handheld controller that subscribes to the HART foundation updates)

      • Through HART membership www.hartcomm2.org

      • Available from MSA


Sales support12 l.jpg
Sales Support

  • Before customer visit

    • Ensure customer has latest downloads to their handheld

    • Ask customer to bring handheld and connector cable to meeting

    • Bring power supply from XE demo kit

      Demo Ultima XL/XT during sales call!


Hart handheld menu tree l.jpg

Detailed device information

4-20 output calibration

Alarm set points

Calibration

HART handheld menu tree


ad