1 / 96

GE Mesurement PanaFlow XMT1000 Ultrasonic Liquid Flow Transmitter | Instronline

The PanaFlow XMT1000 ultrasonic flow transmitter for liquids combines state-of-the-art flow measurement capability with a low-cost transmitter package that can be installed right at the process measurement point. The XMT1000 features both local and remote mount options and carries appropriate certification for installation in hazardous (classified) locations commonly found in petrochemical and chemical processing environments. With configurable inputs and outputs, the electronics package simplifies communication with the DCS or PLC and provides more flexibility to add complimentary measurements, such as inputs from a temperature or pressure transmitter. The XMT1000 supports one, two, or three ultrasonic transducer paths for improved accuracy and added redundancy depending on the application requirements.

Instronline
Download Presentation

GE Mesurement PanaFlow XMT1000 Ultrasonic Liquid Flow Transmitter | Instronline

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. GE Oil & Gas Flow PanaFlow™ XMT1000 User’s Manual 910-313 Rev. A June 2017

  2. GE Oil & Gas PanaFlow™ XMT1000 Panametrics Liquid Flow Ultrasonic Transmitter User’s Manual 910-313 Rev. A June 2017 www.gemeasurement.com ©2017 General Electric Company. All rights reserved. Technical content subject to change without notice.

  3. [no content intended for this page] ii

  4. Contents Product Registration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii Services . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii Terms and Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii Typographical Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii Safety Issues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .vii Auxiliary Equipment. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii Environmental Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ix Chapter 1. Installation 1.1 1.2 1.3 1.4 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 CE Marking Compliance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 Unpacking the XMT1000. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Site and Clearance Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.4.1 Access to the Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 1.4.2 Vibration Exposure Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.4.3 Sunlight Exposure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 1.4.4 Local Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1.4.5 Remote Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 1.4.6 Cable Lengths. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 1.4.7 Transducer Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 Making the Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 1.5.1 Wiring the Analog Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 1.5.2 Wiring the Digital Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10 1.5.3 Wiring the Modbus/Service Port. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11 1.5.4 Wiring the Line Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12 1.5 Chapter 2. Programming 2.1 2.2 2.3 2.4 2.5 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Using the Magnetic Keypad. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13 Passcodes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14 Glossary of Terms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15 Menu Maps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16 Chapter 3. Error Codes and Troubleshooting 3.1 Error Display in the User Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 3.1.1 Error Header . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 3.1.2 Communication Error String . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 3.1.3 Flow Error String . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 3.2.1 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 3.2.2 Flowcell Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27 3.2.3 Transducer/Buffer Problems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29 3.2 PanaFlow™ XMT1000 User’s Manual iii

  5. Contents Appendix A. Specifications A.1 A.2 Operation and Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31 Electronics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .32 Appendix B. Modbus Communication B.1 B.2 Modbus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35 Modbus Register Map . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35 Appendix C. HART Communication C.1 C.2 C.3 Wiring the XMT1000 to the HART Communicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53 HART Write Mode Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53 HART Menu Maps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54 C.3.1 HART Output Menu Map. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54 C.3.2 HART Review Menu Map. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55 Appendix D. Foundation Fieldbus Communication D.1 D.2 Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 D.2.1 Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 D.2.2 Polarity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57 D.2.3 Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58 D.2.4 FISCO (Fieldbus Intrinsically Safe Concept). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .58 D.2.5 DD File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 D.2.6 Default Node Address. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .60 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 D.3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 D.3.2 Physical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 D.3.3 Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61 D.3.4 User Layer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62 D.3.5 Function Blocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62 Resource Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63 D.4.1 FF Revision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63 D.4.2 Password. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .64 D.4.3 NAMUR NE107. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .65 XMIT Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .67 D.5.1 Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68 Composite Transducer Block. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69 D.6.1 Clearing the Totalizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .72 Channel Transducer Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73 Analog Input Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75 PID Block . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75 D.3 D.4 D.5 D.6 D.7 D.8 D.9 iv PanaFlow™ XMT1000 User’s Manual

  6. Contents D.10 Error Handling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76 D.11 Simulation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78 D.12 Fieldbus Troubleshooting Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79 D.13 DPI620 FF Modular Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .81 PanaFlow™ XMT1000 User’s Manual v

  7. Contents [no content intended for this page] vi PanaFlow™ XMT1000 User’s Manual

  8. Preface Product Registration Thank you for purchasing a model PanaFlow™ XMT1000 from GE. Please register your product at www.gemeasurement.com/productregistration for product support such as the latest software/firmware upgrades, product information and special promotions. Services GE provides customers with an experienced staff of customer support personnel ready to respond to technical inquiries, as well as other remote and on-site support needs. To complement our broad portfolio of industry-leading solutions, we offer several types of flexible and scalable support services including: Training, Product Repairs, Service Agreements and more. Please visit www.gemeasurement.com/services for more details. Terms and Conditions GE’s sales Terms and Conditions for your recent purchase of a GE product, including the applicable product Warranty, can be found on our website at the following link: www.gemeasurement.com/sales-terms-and-conditions Typographical Conventions Note: These paragraphs provide information that provides a deeper understanding of the situation, but is not essential to the proper completion of the instructions. IMPORTANT: These paragraphs provide information that emphasizes instructions that are essential to proper setup of the equipment. Failure to follow these instructions carefully may cause unreliable performance. CAUTION! This symbol indicates a risk of potential minor personal injury and/or severe damage to the equipment, unless these instructions are followed carefully. WARNING! This symbol indicates a risk of potential serious personal injury, unless these instructions are followed carefully. Safety Issues WARNING! It is the responsibility of the user to make sure all local, county, state and national codes, regulations, rules and laws related to safety and safe operating conditions are met for each installation. Attention European Customers! the EU, all electrical cables must be installed as described in this manual. To meet CE Marking requirements for all units intended for use in PanaFlow™ XMT1000 User’s Manual vii

  9. Preface Auxiliary Equipment Local Safety Standards The user must make sure that he operates all auxiliary equipment in accordance with local codes, standards, regulations, or laws applicable to safety. Working Area WARNING! Auxiliary equipment may have both manual and automatic modes of operation. As equipment can move suddenly and without warning, do not enter the work cell of this equipment during automatic operation, and do not enter the work envelope of this equipment during manual operation. If you do, serious injury can result. WARNING! Make sure that power to the auxiliary equipment is turned OFF and locked out before you perform maintenance procedures on this equipment. Qualification of Personnel Make sure that all personnel have manufacturer-approved training applicable to the auxiliary equipment. Personal Safety Equipment Make sure that operators and maintenance personnel have all safety equipment applicable to the auxiliary equipment. Examples include safety glasses, protective headgear, safety shoes, etc. Unauthorized Operation Make sure that unauthorized personnel cannot gain access to the operation of the equipment. viii PanaFlow™ XMT1000 User’s Manual

  10. Preface Environmental Compliance RoHS The PanaFlow™ XMT1000 fully complies with RoHS regulations (Directive 2011/65/EU). Waste Electrical and Electronic Equipment (WEEE) Directive GE is an active participant in Europe’s Waste Electrical and Electronic Equipment (WEEE) take-back initiative (Directive 2012/19/EU). The equipment that you bought has required the extraction and use of natural resources for its production. It may contain hazardous substances that could impact health and the environment. In order to avoid the dissemination of those substances in our environment and to diminish the pressure on the natural resources, we encourage you to use the appropriate take-back systems. Those systems will reuse or recycle most of the materials of your end life equipment in a sound way. The crossed-out wheeled bin symbol invites you to use those systems. If you need more information on the collection, reuse and recycling systems, please contact your local or regional waste administration. Please visit http://www.gemeasurement.com/environmental-health-safety-ehs for take-back instructions and more information about this initiative. PanaFlow™ XMT1000 User’s Manual ix

  11. Preface [no content intended for this page] x PanaFlow™ XMT1000 User’s Manual

  12. Chapter 1. Installation Chapter 1. Installation 1.1 Introduction To ensure safe and reliable operation of the XMT1000, it must be installed in accordance with the established guidelines. Those guidelines, explained in detail in this chapter, include the following topics: • Unpacking the XMT1000 • Selecting the location for the XMT1000 (local or remote) • Installing the XMT1000 at the selected location • Wiring the XMT1000 WARNING! The XMT1000 flow transmitter can measure the flow rate of many fluids, some of which are potentially hazardous. The importance of proper safety practices cannot be overemphasized. Be sure to follow all applicable local safety codes and regulations for installing electrical equipment and working with hazardous fluids or flow conditions. Consult company safety personnel or local safety authorities to verify the safety of any procedure or practice. Attention European Customers! described in “CE Marking Compliance” on page 1. To meet CE Marking requirements, all cables must be installed as 1.2 CE Marking Compliance For CE Marking compliance or installation in high noise areas, the XMT1000 flow transmitter must be wired in accordance with the instructions in this section. IMPORTANT: CE Marking compliance is required for all units intended for use in EU countries. The XMT1000 must be wired with the recommended cable, and all connections must be properly shielded and grounded. Grounding of the chassis must be within 10 ft (3 m) of the transmitter. Refer to Table 1 below for the specific requirements. Table 1: Wiring Requirements Cable Type Connection Transducer Input/Output Ground Termination Grounded using a cable gland. Grounded using a cable gland. Armored RG-62 a/U or equivalent Armored 22 AWG shielded with armored material added to outside of jacket Armored 14 AWG 2 conductor Power Grounded using a cable gland. Note: If the XMT1000 is wired as described above, the unit will comply with the EMC and LVD Directives. PanaFlow™ XMT1000 User’s Manual 1

  13. Chapter 1. Installation 1.3 Unpacking the XMT1000 Before removing the XMT1000 from its box, please inspect both the box and the instrument carefully. Each instrument manufactured by GE is warranted to be free from defects in material and workmanship. Before discarding any of the packing materials, account for all components and documentation listed on the packing slip. The discarding of an important item along with the packing materials is all too common. If anything is missing or damaged, contact GE Customer Care immediately for assistance. The XMT1000 is supplied with both a serial number label and a certification label for identification of the instrument (see Figure 1 below and Figure 2 on page 3). The system can be mounted either on an existing meter body (local mounting) or at another location via a connecting cable (remote mounting). Model & Serial Number (Boston) Model & Serial Number (Shannon) Certification (US/CAN, IECEx/ATEX) [FISCO] Certification (US/CAN, IECEx/ATEX) [Standard] Figure 1: Typical XMT1000 Labels (Aluminum Enclosure) 2 PanaFlow™ XMT1000 User’s Manual

  14. Chapter 1. Installation 1.3 Unpacking the XMT1000 (cont.) Model & Serial Number (Boston) Model & Serial Number (Shannon) Certification (US/CAN, IECEx/ATEX) [FISCO] Certification (US/CAN, IECEx/ATEX) [Standard] Figure 2: Typical XMT1000 Labels (Stainless Steel Enclosure) 1.4 Site and Clearance Considerations 1.4.1 Access to the Meter Because the relative location of the flowcell and the XMT1000 transmitter is important, use the guidelines in this section to plan the XMT1000 installation. For flowcell clearance recommendations, consult the manual for your specific flow meter system or contact GE for assistance. Access to the XMT1000 flow transmitter should be uninhibited, as defined by the minimum clearance distances around the enclosure specified in Figure 3 on page 4. PanaFlow™ XMT1000 User’s Manual 3

  15. Chapter 1. Installation 1.4.1 Access to the Meter (cont.) 12 in. (300 mm) CLEARANCE MINIMUM RECOMMENDED FOR SERVICE ACCESS 12 in. (300 mm) CLEARANCE MINIMUM RECOMMENDED FOR CABLE ENTRY 12 in. (300 mm) CLEARANCE MINIMUM RECOMMENDED FOR CABLE ENTRY 1000 SERIES ELECTRONICS 12 in. (300 mm) CLEARANCE MINIMUM RECOMMENDED FOR SERVICE ACCESS CUSTOMER SUPPLIED 2” PIPE 1000 SERIES REMOTE MOUNT KIT 12 in. (300 mm) CLEARANCE MINIMUM RECOMMENDED FOR CABLE ENTRY Figure 3: XMT1000 Enclosure Clearances (ref. dwg. 712-2164) 1.4.2 Vibration Exposure Considerations Whenever possible, install the XMT1000 flow transmitter in a location isolated from vibrations. Avoid installing it near equipment that generates low-frequency, high-energy random vibrations. 1.4.3 Sunlight Exposure The installer should consider and limit exposure of the XMT1000 flow transmitter to direct sunlight. Sunshades should be utilized in extreme environments. 4 PanaFlow™ XMT1000 User’s Manual

  16. Chapter 1. Installation 1.4.4 Local Mounting The XMT1000 accuracy is affected by the flowcell location in the process piping and on the orientation of the transducers. Thus, in addition to accessibility for maintenance, adhere to the following installation guidelines: • Locate the flowcell so that there are at least 10 pipe diameters of straight, undisturbed flow upstream and 5 pipe diameters of straight, undisturbed flow downstream from the measurement point (see Figure 4 below). Undisturbed flow means avoiding sources of turbulence in the fluid (e.g., valves, flanges, expansions, elbows, etc.), avoiding swirl, and avoiding cavitation. Flow Direction 10D 5D Figure 4: Minimum Straight Run Pipe Requirements • Locate the transducers on a common axial plane along the pipe. Also, locate them on the side of the pipe instead of on the top or the bottom, because the top of the pipe tends to accumulate gas and the bottom tends to accumulate sediment. Either condition will cause unwanted attenuation of the ultrasonic signals. There is no similar restriction with vertical pipes, as long as the fluid flow is upward to prevent free falling of the fluid or a less than full pipe (see Figure 5 below). Horizontal Flowcell Vertical Flowcell GOOD Flow Direction Flow Direction Flow Direction BAD GOOD BAD Figure 5: Good and Bad Flowcell/Transducer Orientations CAUTION! Do not place thermal insulation on or around the transducers, the junction boxes, or the meter electronics. The transducer and junction box act as a heat sink that protects the transducer from high and low temperatures. PanaFlow™ XMT1000 User’s Manual 5

  17. Chapter 1. Installation 1.4.5 Remote Mounting The standard XMT1000 enclosure is a powder-coated, aluminum, IP67 explosion-proof enclosure. Typically, the enclosure is mounted as close as possible to the transducers. When choosing a site for a remote-mount installation, which is recommended for process temperatures exceeding 150°C, make sure the location permits easy access to the enclosure for programming, maintenance and service. Attention European Customers! this unit requires an external power disconnect device such as a switch or circuit breaker. The disconnect device must be marked as such, clearly visible, directly accessible, and located within 1.8 m (6 ft) of the unit. For compliance with the European Union’s Low Voltage Directive, 1.4.6 Cable Lengths Locate the XMT1000 as close as possible to the transducers. The maximum distance from the transducers for remote mounting of the XMT1000 is 1000 ft (300 m) using RG-62 coaxial cable or equivalent. If longer distances are required, consult the factory for assistance. 1.4.7 Transducer Cables When installing the transducer cables, always observe established standard practices for the installation of electrical cables. Do not route transducer cables alongside high amperage AC power lines or any other cables that could cause electrical interference. Also, protect the transducer cables and connections from the weather and corrosive atmospheres, and be sure to follow the manufacturer's installation guidelines if cable glands are provided. 6 PanaFlow™ XMT1000 User’s Manual

  18. Chapter 1. Installation 1.5 Making the Electrical Connections This section contains instructions for making all the necessary electrical connections for the XMT1000 flow transmitter. Refer to Figure 6 on page 8 for a complete wiring diagram. Note: Both flying lead and MCX transducer connectors are shown in the figure for completeness. Only the type of connector appropriate for each meter ordered will be installed on the PCB. WARNING! Always disconnect the line power from the XMT1000 before removing either the front cover or the rear cover. This is especially important in a hazardous environment. Attention European Customers! described in “CE Marking Compliance” on page 1. To meet CE Marking requirements, all cables must be installed as Prepare the XMT1000 for wiring by completing the following steps: • To access the wiring terminals, complete the following steps: 1. Disconnect any previously wired power line from the unit. 2. Loosen the set screw on the wiring cover. 3. Place a rod or long screwdriver across the cover in the slots provided, and rotate the cover counterclockwise until it comes free from the enclosure. 4. Install any required cable glands in the appropriate conduit holes on the opposite side of the enclosure. 5. Note the labels inside the rear cover to assist in wiring the power and option connections. • Wiring any option set requires completion of the following general steps: 1. Disconnect the main power from the unit and remove the wiring cover. 2. Install a cable gland in the chosen conduit hole on the side of the electronics enclosure and feed a standard 26-12 AWG twisted-pair cable through this conduit hole. 3. Locate the Standard I/O or Analog I/O options terminal block and wire the option as indicated on the label inside the wiring cover. Secure the cable gland. 4. If wiring of the unit has been completed, reinstall the wiring cover on the enclosure and tighten the set screw. WARNING! Proper grounding of the XMT1000 enclosure via the external grounding screw on the enclosure (see Figure 6 on page 8) is required to prevent the possibility of electric shock. All ground screws should be hand tightened only, to a maximum allowable torque of 2.5 N-m (22 in-lb). For specific instructions on wiring a particular output configuration, proceed to the appropriate sub-section. PanaFlow™ XMT1000 User’s Manual 7

  19. Chapter 1. Installation 1.5 Making the Electrical Connections (cont.) CH2 FLYING LEAD TERMINAL BLOCK (TB6) ANALOG I/O TERMINAL BLOCK (TB2) ACCEPTS 26-12 AWG WIRE ACCEPTS 26-12 AWG WIRE DIGITAL COMMUNICATION ADDITIONAL CUSTOMER GROUND, 3X ????????????????????? ????????????????????? FIELDBUS NET (+) TERMINAL BLOCK (TB1) FIELDBUS NET (-) CH 2 DOWNSTREAM RTN (-) CH 2 DOWNSTREAM SIG (+) ACCEPTS 26-12 AWG WIRE DESCRIPTION DESCRIPTION CH 2 UPSTREAM RTN (-) CH 2 UPSTREAM SIG (+) HART (+) ACCEPTS 26-12 AWG WIRE HART (-) ? FOR FUTURE USE ? NONE, [OR] PCB GROUND DESCRIPTION [OR] PIN PIN 1 2 1 2 PIN 1 2 3 4 CONNECT GROUND TO CHASSIS CONNECT GROUND TO CHASSIS LINE POWER TERMINAL BLOCK (TB4) [TB2] [TB1] [TB6] ACCEPTS 20-10 AWG WIRE [TB4] (L2/N) NEUTRAL DESCRIPTION DESCRIPTION [TB3] [TB5] (L1) LINE + - [OR] ???? PIN PIN ???? 1 2 1 2 * * CH1 FLYING LEAD TERMINAL BLOCK (TB5) ACCEPTS 50 ? RIGHT ANGLE MCX PLUG CASTED GROUND SYMBOL CH 1 DOWNSTREAM RTN (-) CH 1 DOWNSTREAM SIG (+) MCX TERMINAL CONNECTORS EXTERIOR GROUND SCREW *ENCLOSURE MAIN CUSTOMER GROUND CH 1 UPSTREAM RTN (-) CH 1 UPSTREAM SIG (+) STANDARD I/O TERMINAL BLOCK (TB3) FREQUENCY/TOTALIZER/CAL (+) FREQUENCY/TOTALIZER/CAL (-) DN1 CH 1 DOWNSTREAM DN2 CH 2 DOWNSTREAM DN3 CH 3 DOWNSTREAM ACCEPTS 26-12 AWG WIRE UP1 CH 1 UPSTREAM UP2 CH 2 UPSTREAM UP3 CH 3 UPSTREAM DESCRIPTION DESCRIPTION ANALOG 4-20MA OUT (+) ANALOG 4-20MA RTN (-) ACCEPTS 26-12 AWG WIRE RS485 MODBUS (+) RS485 MODBUS (-) RS485 COMMON DESCRIPTION PIN PIN 1 2 3 4 PIN 1 2 3 4 5 6 7 Figure 6: XMT1000 Terminal Board Wiring Diagram (ref. dwg. 702-2040) 8 PanaFlow™ XMT1000 User’s Manual

  20. Chapter 1. Installation 1.5.1 Wiring the Analog Outputs The standard configuration of the XMT1000 flow transmitter includes one isolated 4-20 mA analog output. Connections to this output may be made with standard twisted-pair wiring, but the current loop impedance for this circuit must not exceed 600 ohms. Two additional analog outputs are available as an option. To wire the analog outputs, complete the following steps: 1. Disconnect the main power to the unit and remove the wiring cover. 2. Install the required cable gland in the chosen conduit hole on the side of the electronics enclosure. 3. Refer to Figure 6 on page 8 for the location of the terminal block and wire the analog output as shown. Secure the cable gland. Attention European Customers! described in “CE Marking Compliance” on page 1. To meet CE Marking requirements, all cables must be installed as IMPORTANT: Analog output A is an active signal. Do not supply power to this circuit, as the circuit is powered by the flow meter. 4. If wiring of the unit has been completed, reinstall the wiring cover on the enclosure and tighten the set screw. WARNING! Make sure all covers, with their o-ring seals, are installed and the set screws tightened before applying power in a hazardous environment. Note: Prior to use, the analog output must be set up and calibrated. Proceed to the next section to continue the initial wiring of the unit. Note: See Appendix A, Specifications, for the load and voltage requirements. PanaFlow™ XMT1000 User’s Manual 9

  21. Chapter 1. Installation 1.5.2 Wiring the Digital Output The standard XMT1000 flow transmitter configuration includes one isolated digital output, which can be used as a totalizer (pulse) output, a frequency output, or a calibration port. Wiring this output requires completion of the following general steps: 1. Disconnect the main power to the unit and remove the wiring cover. 2. Install the required cable gland in the chosen conduit hole on the side of the electronics enclosure. 3. Refer to Figure 6 on page 8 for the location of the terminal block and wire the digital output as shown. Secure the cable gland. Attention European Customers! described in “CE Marking Compliance” on page 1 To meet CE Marking requirements, all cables must be installed as 4. If wiring of the unit has been completed, reinstall the wiring cover on the enclosure and tighten the set screw. 1.5.2a Wiring as a Totalizer (Pulse) Output Wire this option in accordance with the connections shown on the label in the rear cover (see Figure 6 on page 8). Refer to Appendix A, Specifications for the load and voltage requirements. 1.5.2b Wiring as a Frequency Output Wire this option in accordance with the connections shown on the label in the rear cover (see Figure 6 on page 8). Refer to Appendix A, Specifications for the load and voltage requirements. 1.5.2c Wiring as a Calibration Port The XMT1000 flow transmitter is equipped with a calibration port specifically designed for calibrating the XMT1000. It is wired for a frequency output. To wire to this port, refer to Figure 6 on page 8 and complete the following steps: Note: Performing a calibration of the meter requires entering an Admin-level password. 1. Disconnect the main power to the unit and remove the rear cover. 2. Install the required cable gland in the chosen conduit hole on the side of the electronics enclosure. 3. Feed one end of the cable through the conduit hole, wire it to the terminal block. 4. If wiring of the unit has been completed, reinstall the wiring cover on the enclosure and tighten the set screw. WARNING! Make sure all covers, with their o-ring seals, are installed and the set screws tightened before applying power in a hazardous environment. 10 PanaFlow™ XMT1000 User’s Manual

  22. Chapter 1. Installation 1.5.3 Wiring the Modbus/Service Port The XMT1000 flow transmitter is equipped with a Modbus communication port for either a connection to Vitality (PC software) or to a separate control system. The port is an RS485 interface. IMPORTANT: The maximum cable length for an RS485 connection is 4000 ft (1200 m). To wire to this RS485 serial port, refer to Figure 6 on page 8 and complete the following steps: 1. Disconnect the main power to the unit and remove the rear cover. 2. Install the required cable gland in the chosen conduit hole on the side of the electronics enclosure. 3. Feed one end of the cable through the conduit hole, and wire it to the terminal block. 4. If wiring of the unit has been completed, reinstall the wiring cover on the enclosure and tighten the set screw. Note: Prior to use, the serial port must be programmed. WARNING! Make sure all covers, with their o-ring seals, are installed and the set screws tightened before applying power in a hazardous environment. PanaFlow™ XMT1000 User’s Manual 11

  23. Chapter 1. Installation 1.5.4 Wiring the Line Power The XMT1000 may be ordered for operation with power inputs of either 100-240 VAC or 12-28 VDC. The label on the side of the enclosure lists the meter’s required line voltage and power rating. Be sure to connect the meter to the specified line voltage only. Attention European Customers! this unit requires an external power disconnect device such as a switch or circuit breaker. The disconnect device must be marked as such, clearly visible, directly accessible, and located within 1.8 m (6 ft) of the unit. For compliance with the European Union’s Low Voltage Directive, WARNING! Improper connection of the line power leads or connecting the meter to the incorrect line voltage may damage the unit. It may also result in hazardous voltages at the flowcell and associated piping as well as within the electronics enclosure. Refer to Figure 6 on page 8 to locate the terminal blocks and connect the line power as follows: 1. Prepare the line power leads by trimming the line and neutral AC power leads (or the positive and negative DC power leads) to a length 0.5 in. (1 cm) shorter than the ground lead. This ensures that the ground lead is the last to detach if the power cable is forcibly disconnected from the meter. 2. Install a suitable cable gland in the conduit hole. If possible, avoid using the other conduit holes for this purpose, to minimize any interference in the circuitry from the AC power line. Attention European Customers! described in “CE Marking Compliance” on page 1. To meet CE Marking requirements, all cables must be installed as 3. Route the cable through the conduit hole and connect the line power leads to the power terminal, using the pin number assignments shown in Figure 6 on page 8. IMPORTANT: The ground wire must be connected to the system chassis. 4. Leaving a bit of slack, secure the power line with the cable clamp. 5. If wiring of the unit has been completed, reinstall the wiring cover on the enclosure and tighten the set screw. WARNING! Make sure all covers, with their o-ring seals, are installed and the set screws tightened before applying power in a hazardous environment. CAUTION! The transducers must be properly wired before applying power to the meter. 12 PanaFlow™ XMT1000 User’s Manual

  24. Chapter 2. Programming Chapter 2. Programming 2.1 Introduction This chapter provides instructions for programming the various features of the XMT1000 flow transmitter. Before the XMT1000 can begin taking measurements, settings for the User Preferences and Inputs/Outputs must be entered and tested. To program your XMT1000, see the next section for programming instructions and refer to “Menu Maps” on page 16 to configure the desired features. Note: For help with the programming of any system parameters which may be unclear, refer to “Glossary of Terms” on page 15 for a brief description of the standard flow meter terminology used in this manual. 2.2 Using the Magnetic Keypad The display window on the XMT1000 includes the components shown in Figure 7 below. Figure 7: The Display and Keypad IMPORTANT: The XMT1000 magnetic keypad enables programming of the instrument through the glass faceplate without removing the cover. Thus, all programming procedures may be performed while the unit is installed in a hazardous area. PanaFlow™ XMT1000 User’s Manual 13

  25. Chapter 2. Programming 2.2 Using the Magnetic Keypad (cont.) Above the display, the blue light is for power indication and the red light is for system health indication. Once system power is applied, the blue light stays on until power is lost. The red light blinks when the system is in error. When the red light is off - the system is operating without error. The six keys on the magnetic keypad are used to program the XMT1000: • [√] - confirms the choice of a specific option and data entry within that option • [] - enables users to exit from a specific option without entering unconfirmed data • [] and [] - enable users to highlight a specific window in the display option or to scroll through a list of options (parameters, letters, and numbers, 0-9 as well as the negative sign and decimal point) in a menu • [] and [] - enable users to scroll to a specific option, among choices in an option, or to a character in a text entry. When the XMT1000 is powered up, the initial screen display appears, followed by meter boot up, then by a display of measurement parameters. Velocity INITIALIZE . . . XMT 1000 9.3 m/s As a guide to help follow the programming instructions in this chapter, the XMT1000 menu maps have been reproduced in Figure 8 on page 17 through Figure 15 on page 24. IMPORTANT: If the keypad has not been pressed for 10 minutes, the XMT1000 exits the Keypad Program and returns to displaying measurements. Because changes can only be retained after the user confirms them, the meter discards any unconfirmed configuration changes. 2.3 Passcodes The default passcodes for the XMT1000 flow transmitter are: • Default Operator Password = 111111 • Default Admin Password = 111111 IMPORTANT: The default Admin password must be changed before the meter is placed into service, and the new Admin password must be properly secured. Unauthorized access to the Admin menus may result in programming changes that have a negative impact on the performance and operation of the meter. 14 PanaFlow™ XMT1000 User’s Manual

  26. Chapter 2. Programming 2.4 Glossary of Terms • Backlight: The LCD display backlight has three user-adjustable parameters. The brightness, the contrast, and the length of inactivity which triggers automatic shutdown can be individually set within available limits. • Error Handling: The manner in which various XMT1000 outputs respond to automatically generated system errors can be set by the user by selecting the options from a drop-down list. • Frequency Output: In frequency mode, the digital output generates a pulse with a frequency that is proportional to the magnitude of the measured flow parameter (e.g., 10 Hz = 1ft3/hr). • HART: HART is a serial communication protocol used for industrial automation. Its main advantage is that it can communicate over 4-20 mA analog instrumentation current loops over the pair of wires used by the analog only host system. • K-Factor: To calibrate the XMT1000 against a reference value, the raw flow velocity readings may need to have a correction factor applied. This K-Factor can be a single constant or a table of K-Factor vs. Velocity values. • Loop Powered: Loop powered analog devices use the power provided by the meter itself rather than by an external power supply. This results in a simple 2-wire connection between the meter and the external device. • Mass Flow: Mass flow is the mass of fluid passing the measurement point in a given period of time. This value is calculated by the meter from the measured flow velocity and the programmed pipe and fluid parameters. • Modbus: Modbus is a serial communication protocol developed by Modicon® for use with its programmable logic controllers. It is a method used for transmitting information over serial lines between electronic devices. • Pulse Output: In pulse/totalizer mode, the digital output generates a pulse with a width corresponding to one unit of the measured flow parameter (e.g., 1 pulse = 1 ft3). • Reynolds Correction: When turned on, a factor based on the kinematic viscosity and the flow rate of the fluid is applied to all measurements. Reynolds correction should be On for most applications. • Serial Port Settings: When the XMT1000 serial port is connected to an external serial device, communication between the two devices only occur if the serial port settings of the two devices match. These settings include: baud rate, data bits, stop bits, and parity. • Special Transducer: If your transducer has no number engraved on the body, select SPECIAL in the Transducer Number menu. • Tw: The TW parameter is the time the transducer signal spends traveling through the transducer body and the transducer cable. This value must be subtracted from the total signal transit time to calculate the actual signal transit time only through the fluid. • Totalizer: The totalizer accumulates a running total of the amount of fluid which passes the measurement point between specified start and stop times. • Tracking Window: The tracking window is used to detect the receive signal when you are unsure of the fluid sound speed. For the XMT1000 flow transmitter, the Tracking Window is always ON. • Zero Cutoff: When the measured flow rate is below the zero cutoff value, the display is forced to 0.00. This is to avoid rapid fluctuations in the reading whenever the flow rate is close to zero. PanaFlow™ XMT1000 User’s Manual 15

  27. Chapter 2. Programming 2.5 Menu Maps Use the menu maps in this section to program the desired XMT1000 features. • "Measurement Display Menu Map (Rev. 10)" on page 17 • "Main Menu Map (Rev. 10)" on page 18 • "SYSTEM Menu Map (Rev. 10)" on page 19 • "MAIN Board I/O Menu Map (Rev. 10)" on page 20 • "OPTION Boards Menu Map (Rev. 10)" on page 21 • "SENSOR SETUP Menu Map (Rev. 10)" on page 22 • "CALIBRATION Menu Map (Rev. 10)" on page 23 • "ADVANCED Menu Map (Rev. 10)" on page 24 In addition, the following menu maps are available in Appendix C: • “HART Output Menu Map” on page 54 • “HART Review Menu Map” on page 55 IMPORTANT: Not all users will have access to all of the above menus. Some menus are restricted to only those users with the proper passcodes. 16 PanaFlow™ XMT1000 User’s Manual

  28. Chapter 2. Programming 2.5 Menu Maps (cont.) Press to Enter the Display ? Measurement Menu Inventory Reynolds Standard Batch Diagnostics Velocity Soundspeed K-Factor Volumetric Total Total Reylnolds Actual On Board Mass K-Factor Temperature Volumetric Number Reverse Forward Ch 1 Ch 2 Ch 3 Net Time Flow Values Signal Quality Signal Process System Status Figure 8: Measurement Display Menu Map (Rev. 10) PanaFlow™ XMT1000 User’s Manual 17

  29. Chapter 2. Programming 2.5 Menu Maps (cont.) Main Menu Keypad Program Diagnostics Display Format Lockout When the keypad is locked, press [ ], [ ], [ ] to open the password screen. Enter an Admin password to unlock the keypad. ? ? ? 1 Variable 2 Variables Totalizer Forward Total Factory Operator Admin Reverse Total Password XXXXXX PASSWORDS Net Total ? Operator Password (default password = 111111) ? Admin Password (default password = 111111) ? If Admin password is lost, meter must be reset. Totalizer Time Contact the factory for instructions. SYSTEM HART SENSOR SETUP CALIBRATION ADVANCED OPTION Boards MAIN Board I/O (Operator Password) Save Change? Save to Save to No Active Settings Commissioned Display Figure 9: Main Menu Map (Rev. 10) 18 PanaFlow™ XMT1000 User’s Manual

  30. Chapter 2. Programming 2.5 Menu Maps (cont.) Operator/Admin Password SYSTEM SENSOR SETUP CALIBRATION ADVANCED HART OPTION Boards MAIN Board I/O Change Measure Meter Setup Display Flow Units Settings Password Language Operator Velocity Backlight Flow Limits System Date Always On Zero Cutoff Admin m/s Not visible in Operator menu. Admin password is required. Meter Tag Averaging Timeout ft/s (see Units list) Actual SoS Low Limit Timeout Time Label Volumetric Standard Actual SoS High Limit About Volumetric Volumetric Density Mass KV Inputs System S/N Totalizer MAIN Board COM Board Sensor S/N Density Product Type Path Error FLOW Board IO Board Figure 10: SYSTEM Menu Map (Rev. 10) PanaFlow™ XMT1000 User’s Manual 19

  31. Chapter 2. Programming 2.5 Menu Maps (cont.) Operator/Admin Password SYSTEM HART SENSOR SETUP CALIBRATION ADVANCED OPTION Boards MAIN Board I/O Modbus/Service Analog Output Digital Output Port Bit/Parity Measurement Base Value Baud Rate Off Actual Velocity 2400 4800 8 no 8 odd Full Value Pulse Volumetric Standard Frequency Mass 9600 19200 8 even Calibrate Volumetric Sound Speed 4mA 20mA 38400 57600 Batch Total Address Inventory Percentage Diagnostic Stop Bit 115200 Total of Scale 1 2 Error Handling Measurement Base Value HOLD LOW Actual Velocity On Time Full Value Pulse Value Volumetric HIGH OTHER Standard Full Frequency Error Handling Mass Test Pulses Volumetric Test Frequency Sound Speed Measurement Batch Total Inventory Diagnostic Error Handling Total HOLD LOW HOLD LOW HIGH OTHER HIGH OTHER Forward Batch Reverse Batch Net Batch Figure 11: MAIN Board I/O Menu Map (Rev. 10) 20 PanaFlow™ XMT1000 User’s Manual

  32. Chapter 2. Programming 2.5 Menu Maps (cont.) Operator/Admin Password SYSTEM HART SENSOR SETUP CALIBRATION ADVANCED OPTION Boards MAIN Board I/O FF HART Hardware Revision Analog Software HART Info Output Revision (Admin access only) Hardware Analog Revision Base Value Measurement Software Actual Revision Velocity Full Value Volumetric Error Standard Mass Handling Volumetric HOLD LOW Calibrate HIGH OTHER 4mA 20mA Percentage of Scale Figure 12: OPTION Boards Menu Map (Rev. 10) PanaFlow™ XMT1000 User’s Manual 21

  33. Chapter 2. Programming 2.5 Menu Maps (cont.) Operator/Admin Password SYSTEM HART SENSOR SETUP CALIBRATION ADVANCED OPTION Boards MAIN Board I/O Channel Pipe OD Pipe ID/WT Configure mm In ID-In ID-mm WT-In WT-mm Ch 1 Ch 2 Ch 3 Wall Pipe OD Pipe ID Thickness Configure Transducer Path (No Off for Ch1) Length Off Standard Special TD Axial Frequency Midradius 0.2 0.5 4M 1M 2M Static Tw Other Chord Input Figure 13: SENSOR SETUP Menu Map (Rev. 10) 22 PanaFlow™ XMT1000 User’s Manual

  34. Chapter 2. Programming 2.5 Menu Maps (cont.) Operator/Admin Password SYSTEM HART SENSOR SETUP CALIBRATION ADVANCED OPTION Boards MAIN Board I/O Calibration Calibration Calibration Calibration Calibration Calibration Type Config Run Factor Points Table Composite Velocity Off Reynolds Gate Number Frequency Figure 14: CALIBRATION Menu Map (Rev. 10) PanaFlow™ XMT1000 User’s Manual 23

  35. Chapter 2. Programming 2.5 Menu Maps (cont.) Operator/Admin Password SYSTEM SENSOR SETUP CALIBRATION ADVANCED HART OPTION Boards MAIN Board I/O Error Log Reset Settings Signal Setup Flash Update Limits Active Tw Transmit Volt Corr Peak % Main Board On Off Update Limit Velocity Low Limit Reset to Low Hi Ch 1 Ch 2 Ch 3 Commission Velocity High Limit Reset to Factory View Log Delta T Offset Acceleration Limit Reset Log % of Peak Amp Disc Min Limit Min Peak % Amp Disc Max Limit Max Peak % Errors Allowed Figure 15: ADVANCED Menu Map (Rev. 10) 24 PanaFlow™ XMT1000 User’s Manual

  36. Chapter 3. Error Codes and Troubleshooting Chapter 3. Error Codes and Troubleshooting 3.1 Error Display in the User Interface The bottom line of the LCD displays a single, top priority error message during Measurement Mode. This line, called the Error Line, includes two parts: Error header and Error String. The Error header indicates the error pattern and error number, while the Error string gives a detailed description of the error information 3.1.1 Error Header Table 2: Error Header Error Pattern Communication error Flow error System error XMIT error OPT error Error Header Cn (n is error number) En (n is error number) Sn (n is error number) Xn (n is error number) On (n is error number) 3.1.2 Communication Error String The XMT1000 flow transmitter electronics includes two independent sub-systems. The purpose of the Communication error string is to convey to the operator an issue with communication between these two sub-systems. Table 3: Communication Error String Error Header C1 Error Message Flow PCB Comm error PanaFlow™ XMT1000 User’s Manual 25

  37. Chapter 3. Error Codes and Troubleshooting 3.1.3 Flow Error String Flow errors are errors detected by the Flow PCB in the course of making a flow measurement. These errors can be caused by disturbances in the fluid, such as excessive particles in the flow stream or extreme temperature gradients. The errors could also be caused by an empty pipe or other such issue with the fluid itself. Flow errors are typically not caused by a malfunction of the flow measurement device, but by an issue with the fluid itself. Note: For troubleshooting tips, see “Diagnostics” on page 27. Table 4: Flow Error String Description The acoustic signal from the process is very low. This could be due to bubbles, other fluid conditions, an empty pipe, broken cables, transducers, couplant or buffers. The measured soundspeed exceeds programmed limits. flow conditions or poor transducer orientation. It may also occur if signal quality is poor. The measured velocity exceeds programmed limits. flow conditions and/or excessive turbulence. The signal quality is lower than the programmed limits. reciprocity, or signal correlation value has fallen below the correlation peak limit. The cause is usually the same as E6 or E5. The signal amplitude exceeds the programmed limits. amplification due to changes in fluid properties, or transducer/buffer/couplant issues. A cycle skip is detected while processing the signal for measurement. fluids, or cavitation. The Active Tw measurement is invalid. be re-coupled. This may also be due to incorrect programming, or extreme process temperatures. One of the measurement channels is in error. measurement may be compromised because the meter might be using a sister chord substitution. Two or more measurement channels are in error. the measurement may be compromised because the meter is using a sister chord substitution. There is a software malfunction This is a software malfunction. Try power cycling the meter. If the error persists after power cycle, contact GE factory. E29: Velocity Warning The measured velocity exceeds programmed warning limits. flow conditions and/or excessive turbulence. E31: Not Calibrated The flow meter has not been calibrated. making measurements. Error Code E1: SNR Error Message The Signal to Noise ratio is low. E2: Soundspeed The error may be caused by incorrect programming, poor E3: Velocity Range This error may be caused by incorrect programming, poor E4: Signal Quality This means the signal shape, upstream to downstream E5: Amplitude This error may occur due to high signal attenuation or E6: Cycle Skip This is usually due to poor signal integrity, possibly because of bubbles in the pipeline, sound absorption by very viscous E15: Active Tw A transducer or cable is damaged, or a transducer needs to E22: Single Channel Accuracy One measurement channel is in error; accuracy of the E23: Multi Channel Accuracy Two or more measurement channels are in error; accuracy of E28: Software Fault This error may be caused by incorrect programming, poor The flow meter has not been calibrated and hence is not 26 PanaFlow™ XMT1000 User’s Manual

  38. Chapter 3. Error Codes and Troubleshooting 3.2 Diagnostics 3.2.1 Introduction This section explains how to troubleshoot the XMT1000 if problems arise with the electronics enclosure, the flowcell, or the transducers. Indications of a possible problem include: • Display of an error message on the LCD display screen, Vitality PC software, or HART. • Erratic flow readings • Readings of doubtful accuracy (i.e., readings which are not consistent with readings from another flow measuring device connected to the same process). If any of the above conditions occurs, proceed with the instructions presented in this section. 3.2.2 Flowcell Problems If preliminary troubleshooting with the Error Code Messages and/or the Diagnostic Parameters indicates a possible flowcell problem, proceed with this section. Usually, flowcell problems are either fluid problems or pipe problems. Read the following sections carefully to determine if the problem is indeed related to the flowcell. If the instructions in this section fail to resolve the problem, contact GE for assistance. 3.2.2a Fluid Problems Most fluid-related problems result from a failure to observe the flow meter system installation instructions. Refer to Chapter 1, Installation, to correct any installation problems. If the physical installation of the system meets the recommended specifications, it is possible that the fluid itself may be preventing accurate flow rate measurements. The fluid being measured must meet the following requirements: • The fluid must be homogeneous, single-phase, relatively clean and flowing steadily.Although a low level of entrained particles may have little effect on the operation of the XMT1000, excessive amounts of solid or gas particles will absorb or disperse the ultrasound signals. This interference with the ultrasound transmissions through the fluid will cause inaccurate flow rate measurements. In addition, temperature gradients in the fluid flow may result in erratic or inaccurate flow rate readings. • The fluid must not cavitate near the flowcell.Fluids with a high vapor pressure may cavitate near or in the flowcell. This causes problems resulting from gas bubbles in the fluid. Cavitation can usually be controlled through proper installation design. • The fluid must not excessively attenuate ultrasound signals.Some fluids, particularly those that are very viscous, readily absorb ultrasound energy. In such a case, an error code message will appear on the display screen to indicate that the ultrasonic signal strength is insufficient for reliable measurements. • The fluid sound speed must not vary excessively.The XMT1000 will tolerate relatively large changes in the fluid sound speed, as may be caused by variations in fluid composition and/or temperature. However, such changes must occur slowly. Rapid fluctuations in the fluid sound speed, to a value that is considerably above the limit programmed into the XMT1000, will result in erratic or inaccurate flow rate readings. Refer to Chapter 2, Programming, and make sure that the appropriate sound speed limit is programmed into the meter. PanaFlow™ XMT1000 User’s Manual 27

  39. Chapter 3. Error Codes and Troubleshooting 3.2.2b Pipe Problems Pipe-related problems may result either from a failure to observe the installation instructions, as described in Chapter 1, Installation, or from improper programming of the meter (see Chapter 2, Programming, for details). By far, the most common pipe problems are the following: • The collection of material at the transducer location(s). Accumulated debris at the transducer location(s) will interfere with transmission of the ultrasound signals. As a result, accurate flow rate measurements are not possible. Realignment of the flowcell or transducers often cures such problems, and in some cases, transducers that protrude into the flow stream may be used. Refer to Chapter 1, Installation, for more details on proper installation practices. • Inaccurate pipe measurements. The accuracy of the flow rate measurements is no better than the accuracy of the programmed pipe dimensions. For a flowcell supplied by GE, the correct data will be included in the documentation. For other flowcells, measure the pipe wall thickness and diameter with the same accuracy desired in the flow rate readings. Also, check the pipe for dents, eccentricity, weld deformity, straightness and other factors that may cause inaccurate readings. Refer to Chapter 2, Programming, for instructions on programming the pipe data. In addition to the actual pipe dimensions, the path length (P) and the axial dimension (L), based on the actual transducer mounting locations, must be accurately programmed into the flow meter. For a GE flowcell, this data will be included with the documentation for the system. If the transducers are mounted onto an existing pipe, these dimensions must be precisely measured. • The inside of the pipe or flowcell must be relatively clean.Excessive build up of scale, rust or debris will interfere with flow measurement. Generally, a thin coating or a solid well-adhered build up on the pipe wall will not cause problems. Loose scale and thick coatings (such as tar or oil) will interfere with ultrasound transmission and may result in incorrect or unreliable measurements. 28 PanaFlow™ XMT1000 User’s Manual

  40. Chapter 3. Error Codes and Troubleshooting 3.2.3 Transducer/Buffer Problems Ultrasonic transducers are rugged, reliable devices. However, they are subject to physical damage from mishandling and chemical attack. The following list of potential problems is grouped according to transducer type. Contact GE if you cannot solve a transducer-related problem. • Leaks: Leaks may occur around the transducer buffers and/or the flowcell fittings. Repair such leaks immediately. If the leaking fluid is corrosive, carefully check the transducer and cables for damage, after the leak has been repaired. • Corrosion Damage: If the transducer buffer material was not properly chosen for the intended application, they may suffer corrosion damage. The damage usually occurs either at the electrical connector or on the face. If corrosion is suspected, remove the transducer from the flowcell and carefully inspect the buffer electrical connector and the transducer face for roughness and/or pitting. Any transducer damaged in this manner must be replaced. Contact GE for information on transducers in materials suitable for the application. • Internal Damage: An ultrasonic transducer consists of a ceramic crystal bonded to the transducer case. The bond between the crystal and the case or the crystal itself may be damaged by extreme mechanical shock and/or temperature extremes. Also, the internal wiring can be corroded or shorted if contaminants enter the transducer housing. • Physical Damage: Transducers may be physically damaged by dropping them onto a hard surface or striking them against another object. The transducer connector is the most fragile part and is most subject to damage. Minor damage may be repaired by carefully bending the connector back into shape. If the connector can not be repaired, the transducer must be replaced. IMPORTANT:Transducers must be replaced in pairs. Refer to Chapter 2, Programming, to enter the new transducer data into the meter. If the instructions in this section fail to resolve the problem, contact GE for assistance. PanaFlow™ XMT1000 User’s Manual 29

  41. Chapter 3. Error Codes and Troubleshooting [no content intended for this page] 30 PanaFlow™ XMT1000 User’s Manual

  42. Appendix A. Specifications Appendix A. Specifications A.1 Operation and Performance Fluid Types Acoustically conductive fluids, including most clean liquids, and many liquids with entrained solids or gas bubbles. Maximum void fraction depends on transducer, interrogation carrier frequency, path length and pipe configuration. Transducer Types All liquid wetted transducers Pipe Sizes Standard: 1 in. to 76 in. (25 mm to 1930 mm) Optional: >76 in. (1930 mm) consult factory Data Logging Storage standard on meter, up to 10,000 flow data points with up to 26 parameters per data point (requires Vitality™ software) Measurement Parameters Volumetric Flow, Mass Flow, Flow Velocity and Totalized Flow Flow Accuracy (Velocity) Up to ±0.3% of reading (achievable when supplied with a complete flow meter system and process calibration). Accuracy depends on pipe size, installation and number of measurement paths. Note: The accuracy statement assumes measurement of a single phase homogeneous liquid with a fully developed symmetrical flow profile passing through the meter. Applications with piping arrangements that create an asymmetrical flow profile may require extended piping straight runs and/or flow conditioning for the meter to perform to this specification. Repeatability ±0.1% to 0.3% of reading Range (Bidirectional) –40 to 40 ft/s (–12.2 to 12.2 m/s) Meter Turndown 400:1 Optional PC Software Vitality™ PC software for added functionality PanaFlow™ XMT1000 User’s Manual 31

  43. Appendix A. Specifications A.2 Electronics Enclosure Standard: Epoxy-coated aluminum weatherproof 4X/IP66 Class I, Div 1, Groups B, C & D, Flameproof II 2 G Ex d IIC T5/T6 Optional: Stainless steel Dimensions (Standard) Weight: 10 lb (4.5 kg) Size (h x d): 8.2 in. x 6.6 in. (208 mm x 168 mm) Paths 1, 2 or 3 paths Display 128 x 64 mono-color LCD display, configurable for single or dual measurement parameters Display Languages English Keypad Built-in magnetic, six-button keypad, for full functionality operation Inputs/Outputs Standard: one analog output**, one digital output*, service/Modbus (RS485) Optional: one analog output** with HART *Digital outputs are programmable as either pulse or frequency outputs **Analog outputs are NAMUR NE43 compliant Power Supplies Standard: 100-240 VAC (50/60 Hz) Optional: 12 to 28 VDC Power Consumption 15 Watts maximum Wiring Connection Conduit entries include 6 x 3/4” NPT and 1 x 1/2” NPT on bottom, consult GE for available adapters 32 PanaFlow™ XMT1000 User’s Manual

  44. Appendix A. Specifications A.2 Electronics (cont.) Electronics Classifications (Pending) USA/Canada- Explosion-proof Class I, Division 1, Groups B, C, & D ATEX - Flameproof II 2 G Ex d IIC T6 Gb IECEx - Flameproof Ex d IIC T6 Gb RoHS compliance (Directive 2011/65/EU) CE Marking (EMC directive 2014/30/EU, LVD 2014/35/EU) WEEE compliance (Directive 2012/19/EU) Electronics Mounting Standard: Local Mounting (on meter body) Optional: Remote Mounting (recommended for process temperatures exceeding 150°C). The maximum distance is 1000 ft (300 m) using RG-62 coaxial cable or equivalent. If longer distances are required, consult the factory for assistance. Terminal Blocks Table 5: Standard Terminal Block (Output A) Connection Active Output I/O Type Specifications Analog Output Output current: 0-22 mA Max load: 600 Ω Output voltage: 5 VDC Max. voltage with light load: 7 VDC Standard RS485 Communications Pulse, Frequency Active Output RS485 Modbus RS485 Communications Operating Temperature –40° to 140°F (–40° to +60°C) Note: The LCD display is only visible down to -13°F (-25°C). Storage Temperature –40° to 158°F (–40° to 70°C) Humidity (Operating and Storage) 10-90% RH PanaFlow™ XMT1000 User’s Manual 33

  45. [no content intended for this page] 34 PanaFlow™ XMT1000 User’s Manual

  46. Appendix B. Modbus Communication Appendix B. Modbus Communication B.1 Modbus Protocol In general, the PanaFlow XMT1000 flow meter follows the standard Modbus communications protocol defined by the reference MODBUS APPLICATION PROTOCOL SPECIFICATION V1.1b. This specification is available at www.modbus.org on the Internet. With this reference as a guide, an operator could use any Modbus master to communicate with the flow meter. Listed below are two limits of this implementation: • The PanaFlow XMT1000 supports only four of the standard function codes. These are Read Holding Registers (0x03), Read Input Registers (0x04), Write Multiple Registers (0x10), and Read File Record (0x14). and • The flow meter needs a 15 msec gap between Modbus requests. The prime objective of the flow meter is to measure flow, so the Modbus server has a low priority. B.2 Modbus Register Map Table 6: XMT1000 Modbus Register Map - Revision 4.19 Reg # in Hex Access Level Size in Bytes Register ID Description Units RO/RW Format Health Check + Identification (Input Registers) 210 210 NONE System Real RW 400 System Int RW 500 500 Operator Product Type unitless RO 4 INT32 eUnit_ActVol Global Unit group 1 for Actual Volumetric eUnit_Day Global Unit group 2 for Day eUnit_Db Global Unit group 3 for dB eUnit_Dens Global Unit group 4 for Density eUnit_Diam Global Unit group 5 for Dimension eUnit_Hz Global Unit group 6 for Hz eUnit_Kv Global Unit group 7 for Viscosity eUnit_mA Global Unit group 8 for mA eUnit_Mass Global Unit group 9 for Mass eUnit_MS Global Unit group 10 for Milli Second unitless RW 4 INT32 502 Operator unitless RW 4 INT32 504 Operator unitless RW 4 INT32 506 Operator unitless RW 4 INT32 508 Operator unitless RW 4 INT32 50A Operator unitless RW 4 INT32 50C Operator unitless RW 4 INT32 50E Operator unitless RW 4 INT32 510 Operator unitless RW 4 INT32 512 Operator unitless RW 4 INT32 PanaFlow™ XMT1000 User’s Manual 35

  47. Appendix B. Modbus Communication Table 6: XMT1000 Modbus Register Map - Revision 4.19 (cont.) Access Level Register ID Description Reg # in Hex Size in Bytes Units RO/RW Format 514 Operator eUnit_NS Global Unit group 11 for Nano Second unitless RW 4 INT32 516 Operator eUnit_Percent Global Unit group 12 for Percent eUnit_Second Global Unit group 13 for Second eUnit_StdVol Global Unit group 14 for Standard Volumetric eUnit_Therm Global Unit group 15 for Therm eUnit_TotTime Global Unit group 16 for Totalizer time Operator eUnit_TotalizerGlobal Unit group 17 for unitless RW 4 INT32 518 Operator unitless RW 4 INT32 51A Operator unitless RW 4 INT32 51C Operator unitless RW 4 INT32 51E Viewer unitless RW 4 INT32 520 unitless RW 4 INT32 Totalizer 522 Operator eUnit_Unitless Global Unit group 18 for unitless RW 4 INT32 Unitless Global Unit group 19 for Micro Second Global Unit group 20 for Velocity Global Unit group 21 for Reynolds 524 Operator eUnit_US unitless RW 4 INT32 526 Operator eUnit_Vel unitless RW 4 INT32 528 Operator eUnit_Rey unitless RW 4 INT32 52A Gen User eUnit_Temp Global Unit group 22 for Temperature Gen User eUnit_Pressure Global Unit group 23 for unitless RW 4 INT32 52C unitless RW 4 INT32 Pressure 540 540 542 Viewer Viewer eSysReq_Levelsystem request level eSysReq_ Password eSysReq_ Command eInventory_ Command command ePCModbus_ Baudrate ePCModbus_ Parity ePCModbus_ Stop ePCModbus_ Address ePCModbus_ Bits character ePCModbus_ Termination unitless unitless RW RW 4 4 INT32 INT32 system request password 544 Viewer system request command unitless RW 4 INT32 546 Factory inventory request unitless RW 4 INT32 580 580 Operator PC MODBUS baud rate unitless RW 4 INT32 582 Operator PC MODBUS parity unitless RW 4 INT32 584 Operator PC MODBUS stop bits unitless RW 4 INT32 586 Operator PC MODBUS meter addr unitless RW 4 INT32 588 Operator PC MODBUS bits per unitless RW 4 INT32 58A Operator PC MODBUS termination unitless RW 4 INT32 36 PanaFlow™ XMT1000 User’s Manual

  48. Appendix B. Modbus Communication Table 6: XMT1000 Modbus Register Map - Revision 4.19 (cont.) Access Level Register ID Description Reg # in Hex Size in Bytes Units RO/RW Format 5C0 5C0 Operator eSystem_ TagShort eSystem_ TagLong eSystem_ OptType eSystem_MCU _Serial _Number eSystem_MCU _Hardware_ Version eSystem_COM _Hardware_ Version eSystem_OPT_ Hardware_ Version eSystem_ ComType eCh_1_Path Configuration _E eCh_2_Path Configuration _E eCh_3_Path Configuration _E Meter Tag unitless RW 16 CHAR * 16 5C8 Operator Long Tag unitless RW 32 CHAR * 32 5D8 Factory IO Option Board Type unitless RW 4 INT32 5DA Factory MCU serial number unitless RW 4 INT32 5DC Factory MCU Hardware version unitless RW 4 INT32 5DE Factory COM Board Hardware version unitless RW 4 INT32 5E0 Factory IO Option Hardware version unitless RW 4 INT32 5E2 Factory COM Option Board Type unitless RW 4 INT32 5E4 Factory Ch 1 Path Configuration unitless RW 4 INT32 5E6 Factory Ch 2 Path Configuration unitless RW 4 INT32 5E8 Factory Ch 3 Path Configuration unitless RW 4 INT32 System Real RO 600 600 N/A eInventory_ FwdTotal eInventory_ RevTotal eInventory_ NetTotal eInventory_ TotalTime inventory fwd totals 17 RO 4 (IEEE 32 bit) 602 N/A inventory rev totals 17 RO 4 (IEEE 32 bit) 604 N/A inventory net totals 17 RO 4 (IEEE 32 bit) 606 N/A inventory totals time 2 RO 4 (IEEE 32 bit) System Int RO 700 700 N/A eSystem_ IdMax eSystem_ IdMin eSystem_User Password NetworkID_Max unitless RO 4 INT32 702 N/A NetworkID_Min unitless RO 4 INT32 704 N/A General user password unitless RO 4 INT32 PanaFlow™ XMT1000 User’s Manual 37

  49. Appendix B. Modbus Communication Table 6: XMT1000 Modbus Register Map - Revision 4.19 (cont.) Access Level Register ID Description Reg # in Hex Size in Bytes Units RO/RW Format 706 N/A eSystem_ Admin Password eSystem_MCU _Bootloader_ version eSystem_MCU _Software_ Version eSystem_COM _Software _Version eSystem_OPT_ Software_ Version Reserved eSystem_MCU _Flash_CRC eSystem_ ErrMaster eSystem_ MCU_Err eSystem_OPT_ Err eSystem_MCU _Startup_Err eSystem_OPT_ Startup_Err eSystem_ Comm_Err eSystem_ Comm_ TryNum eSystem_ Comm_ FailNum eSystem_ Comm_ WrongNum eSystem_Cmd_ State Admin user password unitless RO 4 INT32 708 N/A MCU bootloader version unitless RO 4 INT32 70A N/A MCU Software version unitless RO 4 INT32 70C N/A COM Option Software version unitless RO 4 INT32 70E N/A IO Option Software version unitless RO 4 INT32 710 712 N/A N/A Reserved MCU flash CRC unitless unitless RO RO 4 4 INT32 INT32 740 740 N/A master error unitless RO 4 INT32 742 N/A MCU error unitless RO 4 INT32 744 N/A Option Board error unitless RO 4 INT32 746 N/A MCU startup error unitless RO 4 INT32 748 N/A Option startup error unitless RO 4 INT32 74A N/A comm error unitless RO 4 INT32 74C N/A comm try times unitless RO 4 INT32 74E N/A comm fail times unitless RO 4 INT32 750 N/A comm data wrong times unitless RO 4 INT32 752 N/A System command state unitless RO 4 INT32 System Real RO Display Real RW 800 38 PanaFlow™ XMT1000 User’s Manual

More Related