1 / 19

Effects of Changes in Shaft Load

Effects of Changes in Shaft Load. Shaft load is doubled – I a cos θ i and E f sin δ must double. Effects of Changes in Shaft Load.

Download Presentation

Effects of Changes in Shaft Load

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Effects of Changes in Shaft Load Shaft load is doubled – Iacosθi and Efsinδ must double

  2. Effects of Changes in Shaft Load Since Field Excitation is constant, Ef traces a circular arc, δ increases θi decreases, increasing the power factor – continues until δ=90 -- pullout

  3. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance Apply step changes to Ef

  4. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance Efsinδ must be constant Apply step changes to Ef

  5. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance • Increasing the strength of the magnets should cause a closer pole alignment and a smaller power angle. • Assuming a constant shaft load, • apply a step increase to Ef • Efsinδ increases, the rotor accelerates • angle δ decreases until Efsinδ has the same value as before (synchronous speed)

  6. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance Iacosθ constant Efsinδ constant Apply step changes to Ef

  7. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance • For constant shaft load, • P is proportional to Efsinδ • Ef1sinθ1 = Ef2sinθ2 = Ef3sinθ3 = Efsinθ • Locus of the tip of the Ef phasor is parallel to the VT phasor • P is proportional to Iacosθ • Ia1cosθ1 = Ia2cosθ2 = Ia3cosθ3 = Iacosθ • Locus of tip of the Ia phasor is perpendicular to the VT phasor

  8. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance Iacosθ constant Efsinδ constant Apply step changes to Ef

  9. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance • IMPORTANT!!!! • Increasing the excitation from Ef1 to Ef3 caused the angle in the current phasor (and hence the power factor) to go from lagging to leading! • Normal excitation when power factor = 1 • Excitation greater than normal is known as overexcitation • Excitation less than normal is known as underexcitation

  10. Effects of Changes in Field Excitation Voltage on Synchronous-Motor Performance Iacosθ constant Power factor changes from lagging to leading Efsinδ constant Apply step changes to Ef

  11. V Curves • Plot armature current as a function of field current or armature current as a function of excitation voltage.

  12. V-Curves

  13. Stability Limit is where angle δ = -90° -- the rotor is still synchronized

  14. V-Curves continued • Constant-Load V-Curves can be plotted from laboratory data, phasor diagrams, or from the following expression

  15. Example 8.2 • Referring to the V-curve for 100% load, determine • a) the minimum value of excitation that will maintain synchronism 98V 100% rated load

  16. Example 8.2 continued • b) using Eq. (8 – 16)

  17. Example 8.2 continued • Repeat (a) using Eq. (8-21) Make the quantity under the radical = 0 for minimum excitation

  18. Example 8.2 continued

  19. Example 8.2 continued • d) the power angle if the field excitation voltage is increased to 175% of the stability limit determined in (c).

More Related