1 / 36

BRANDISOLERING

BRANDISOLERING. AV. BÄRANDE. STÅLKONSTRUKTIONER. MED. NOVATHERM 4FR. PASSIVT BRANDSKYDD. NOVATHERM. BRANDISOLERING. SPRUTISOLERING - Cement eller silikatbindemedel. Fördelar:. Täcker lätt komplexa detaljer. Ingen förbehandling av stålet. Begränsningar:.

tamra
Download Presentation

BRANDISOLERING

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. BRANDISOLERING AV BÄRANDE STÅLKONSTRUKTIONER

  2. MED NOVATHERM 4FR

  3. PASSIVT BRANDSKYDD NOVATHERM

  4. BRANDISOLERING SPRUTISOLERING - Cement eller silikatbindemedel Fördelar: Täcker lätt komplexa detaljer. Ingen förbehandling av stålet Begränsningar: Grov finish och för ytskikt krävs inklädnad. Bör utföras i ett tidigt skede av byggandet. Appliceringen kräver specialutbildad personal. Endast för applicering inomhus.

  5. BRANDISOLERING STENULLSSKIVOR Fördelar: Torrt material som orsakar ringa störning. Ingen förbehandling av stålet Montage kräver ej specialutbildad personal. Begränsningar: Synligt ytskikt kräver inklädnad. Mindre lämpligt för komplexa konstruktioner. Låga profilfaktorer kräver relativt tjocka skivor. Endast för montage inomhus.

  6. BRANDISOLERING INKLÄDNAD - fibersilikatskivor eller gipselement Fördelar: Torrt material som orsakar ringa störning. Ingen förbehandling av stålet är nödvändigt. Ger ett ytskikt som kan målas eller tapetseras. Begränsningar: Mindre lämpligt för komplexa konstruktioner. Måttlig tålighet mot slag eller påkörning. Montage kräver oftast specialutbildad personal. Endast för montage inomhus.

  7. BRANDISOLERING SVÄLLANDE BRANDSKYDDSFÄRG Fördelar: Estetiska ytskikt som exponeras med en täckfärg. Ökar inte konstruktionens dimensioner. Snabb applicering och täcker lätt komplexa detaljer. Kan appliceras före montage av stålkonstruktionen och är lätt att komplettera eller bättra. Begränsningar: Friliggande konstruktion med hög profilfaktor och lastutnyttjandegrad kan ha vissa begränsningar för att klara R60 och R90. Förbehandling av stålet krävs.

  8. KOSTNAD SEK 800 600 400 200 Brandskydds- färg Sprut- isolering Stenulls- skivor Inklädnads- element

  9. BERÄKNINGSPARAMETRAR BRANDTEKNISK KLASSR30, R60 eller R90 KONSTRUKTIONSTYPbalk eller pelare PROFILTYPex. HEA 200 EXPONERING3- el. 4-sid. eller ingjuten PROFILFAKTOR F/A m-1 LASTUTNYTTJANDEGRAD pelare , balk eller 0

  10. PROFILFAKTOR F/A =Sektionsfaktorm -1 d F=Exponerad yta per meter 4b - 2d + 2 h m h A =Exponerad tvärsnittsyta 2 bt + d (h-2t) m ² t b

  11. PROFILFAKTOR FÖR ÖPPET TVÄRSNITT F = Tresidigt exponerad mantelyta 3b - 2d + 2h m t A = Tvärsnittsyta i exponerad del 2bt + d( h - 2t) m 2 d h b

  12. PROFILFAKTOR FÖR ÖPPET TVÄRSNITT F = Tresidigt exponerad mantelyta 3b - 2d + 2h m t d A = Tvärsnittsyta i exponerad del 2bt + d( h - 2t) m 2 h b F = Fyrsidigt exponerad mantelyta 4b - 2d + 2h m t d h A = Tvärsnittsyta i exponerad del 2bt + d( h - 2t ) m 2 b

  13. PROFILFAKTOR FÖR ÖPPET TVÄRSNITT F = Tresidigt exponerad mantelyta 3b - 2d + 2h m t d h A = Tvärsnittsyta i exponerad del 2bt + d( h - 2t) m 2 b t F = Fyrsidigt exponerad mantelyta 4b - 2d + 2h m d h A = Tvärsnittsyta i exponerad del 2bt + d( h - 2t ) m 2 b F = Exponerad mantelyta b + 2t m t A = Tvärsnittsyta i exponerad del bt m 2 b

  14. PROFILFAKTOR, SLUTET TVÄRSNITT F = 2b + 2h h t A = bh - (b-2t)(h-2t) b

  15. PROFILFAKTOR, SLUTET TVÄRSNITT F = 2b + 2h h t A = bh - (b-2t)(h-2t) b F = b + 2h t A = bh - (b-2t)(h-2t) h b

  16. MEKANISKA EGENSKAPER - STÅL Hållfasthetens temperaturberoende enligt Eurocode 3 med kritisk töjning om 2% Relativ elasticitetsmodul som funktion av temperaturen

  17. LASTUTNYTTJANDEGRAD a=kxm0däraär lastutnyttjandegraden i normaltillståndet och m0i brandtillståndet. Korrektionskoefficientkpelare= 1,25 ochkbalk= 2 • Lastutnyttjandegrader och kritiska temperaturer för • pelare och balk vid normal- resp. brandtillstånd

  18. HJÄLPMEDEL FÖR BERÄKNING BERÄKNA PROFILFAKTOR F/A OCH AVLÄS FÄRGMÄNGDEN I DIAGRAM AVLÄS DIREKT FÄRGMÄNGDEN I TABELLER FÖR STANDARDPROFILER • KALKYLPROGRAM FÖR PC NOVACALC.

  19. ÖPPET TVÄRSNITT

  20. SLUTET TVÄRSNITT

  21. BETONGFYLLDA PELARE • f = min. 15 mm 120 mm o o max. 5 m o o 120 mm

  22. BRANDPÅVERKAD UNDERFLÄNS tu bu

  23. BERÄKNINGSÖVNINGAR BRANDISOLERING AV BÄRANDE STÅLKONSTRUKTIONER EFTER NT FIRE 021 MED NOVATHERM 4FR

  24. BERÄKNA ENLIGT NT FIRE 021 Exempel 1 : Pelare HEA 140 R30 • = 75 % 0 = 60% F/A = 250 Svar: 1500 g/m2

  25. BERÄKNA ENLIGT NT FIRE 021 Exempel 2 : Ingjuten balk HEB 300 R90 a = 60% 0 = 30%

  26. BERÄKNA ENLIGT NT FIRE 021 Exempel: 2 Tabell 8 Erforderlig mängd NOVATHERM 4FR för ingjutna HEB- balkar med brandexponerad underfläns som uppfyller brandteknisk klass R60 respektive R 90 Svar: 400 g/m2

  27. BERÄKNA ENLIGT NT FIRE 021 Exempel 3: öppet tvärsnitt, balk HEB 360 R60 • = 80 % 0 = 40% F/A = 86

  28. BERÄKNA ENLIGT NT FIRE 021 Exempel: 3 Svar: 1250 g/m2

  29. BERÄKNA ENLIGT NT FIRE 021 Exempel 4: öppet tvärsnitt, balk HEB 360 R90 • = 80 % 0 = 40% F/A = 86

  30. BERÄKNA ENLIGT NT FIRE 021 Exempel: 4 Svar: 2250 g/m2

  31. BERÄKNA ENLIGT NT FIRE 021 Exempel 5: öppet tvärsnitt, pelare HEB 280 R60 • = 75 % 0 = 60% 3- resp. 4-sid. exponerad F/A 3-sid = 102 4 sid = 123

  32. BERÄKNA ENLIGT NT FIRE 021 Exempel: 5 Svar: 1750 g/m2 vid tresidig exp. 2000 g/m2 vid fyrsidig exp.

  33. BERÄKNA ENLIGT NT FIRE 021 Exempel 6: Slutet tvärsnitt, balk R90 Rundjärn Ø= 60 mm 0 = 40 %

  34. BERÄKNA ENLIGT NT FIRE 021 Exempel: 6 F = d x  ; 0,06 x 3,14 = 0,1884 m A = r2 x  ; 0,03 x 0,03 x 3,14 = 0,002826 m2 F/A = 0,1884 : 0,002826 = 66,66 m-1 Svar: 2000 g/m2

  35. BERÄKNA ENLIGT NT FIRE 021 Exempel 7: slutet tvärsnitt, pelare VKR 200x200x16 R90 • = 75 % 0 = 60 % F/A = 65

  36. BERÄKNA ENLIGT NT FIRE 021 Exempel: 7 Dimensioneringstabell för tre- och fyrsidigt brandpåverkade balkar och pelare medslutettvärsnitt Svar: 3000 g/m2 vid fyrsidig exponering

More Related