An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. FULL-SCALE AIRCRAFT CABIN AND EE-BAY TEST RESULTS FROM GREENWOOD, MSPresented 29 August 2000 to:INTERNATIONAL AIRCRAFT SYSTEMS FIRE PROTECTIONWORKING GROUP Joe Wolfe Naval Aviation Systems Team (732) 323-7343

  2. 737-200 TEST AIRCRAFT Greenwood, MS test aircraft and test equipment shown Aircraft interior and instrumentation shown

  3. CABIN FIRE SUPPRESSION Backside view and side view of stow bin Aircraft constraints followed for low pressure nozzle installation.

  4. CABIN FIRE SUPPRESSION No interference with aircraft systems for low pressure installation View between the stow bins

  5. CEILING WIRE ARC THREAT Wire bundles being set in place for wire arc fire above the ceilingtest condition

  6. CEILING WIRE ARC THREAT Wire arc event after low pressure water mist application. No arcing detected after mist activation.

  7. AEROSOL GENERATORS • Large surface area for extinguishing actions • Small amount required for reliable extinguishing • Gas-like 3 dimensional distribution • Long suspension times – micron size particles • Dual Extinguishing Actions • Primary: • Chemical - Removal of chain carriers • Secondary: • Physical - Heat absorption

  8. 737-200 EE-BAY SUPPRESSION

  9. 737-200 EE-BAY SUPPRESSION Electrically arced cable bundles above fuel source. Pyrogen aerosol generator installed in the EE-bay.

  10. O2 CONCENTRATION

  11. TEMPERATURE MEASUREMENTS

  12. CONCLUSIONS • The twin fluid low pressure nozzles proved highly reliable and maintenance free. • The installation of the twin fluid low pressure nozzles can be accomplished with minimal aircraft interior configuration changes. • Low pressures allow for lightweight, flexible material • The twin fluid low pressure nozzles proved highly effective in suppressing and extinguishing fires during all threat scenarios. • The Pyrogen Aerosol Generators were highly effective in extinguishing fires in the EE-Bay.

  13. RECOMMENDATIONS • It is recommended that this test series be repeated with inclusion of airline industry, FAA and NTSB. • It is recommended that a subsequent test series be structured to reflect the operating parameters of a production system. • Pressures should start at 0 psi and ramp up to operating pressure. • Prototype systems should comply with standard aircraft system design. • In-flight airflow should be simulated to max. possible.