1 / 9

S4000C Intelligent Sensors..

S4000C Intelligent Sensors. … for Combustible Gas Detection. Features: Three Digit Display 4-20mA Output Dual Redundant MODBUS Communications Warning, Alarm & Fault Relays Calibration, Gas Check, Setup Modes Remaining Sensor Life Indication Sensor can be remote mounted up to

rian
Download Presentation

S4000C Intelligent Sensors..

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. S4000C Intelligent Sensors.. … for Combustible Gas Detection

  2. Features: Three Digit Display 4-20mA Output Dual Redundant MODBUS Communications Warning, Alarm & Fault Relays Calibration, Gas Check, Setup Modes Remaining Sensor Life Indication Sensor can be remote mounted up to 7,600ft. (2,316M) Benefits: Displays gas concentrations in %LEL, fault codes for troubleshooting and calibration prompts Industry standard output for remote alarm and fault indication Provides complete diagnostic status Provides local alarm capability Simplifies operation and maintenance Reduces downtime by providing heads-up on sensor life Increased installation flexibility Model S4000C

  3. S4000C Key Features / Benefits • Remaining Sensor LifeThe technician is able to determine when it is time to replace the sensor before it fails. The (%) remaining sensor life is displayed upon initiation of calibration. • Surface Mount ElectronicsAllows for higher MTBF and reduces cost of purchase. • Target Gas CalibrationAllows you to set the gas detector to the specific (target) gas you want detected, but uses only one type of calibration gas. • Easily upgrade your installed GMI Smart Sensors Backwards compatible with our Smart Sensors (Models S104/S106A) – no need to re-wire.

  4. S4000C Key Features / Benefits • Magnet A magnet is used for calibration prompts and to configure the relays and Modbus actions. This eliminates the cost of an expensive hand held device. • Remote Mounting & Remote Calibration This allows for easy and fast remote calibration. • Optional Outputs Standard 4-20 mA. 3- eight amp relays for Fault, Warn and Alarm. Dual Modbus for redundant digital communication and reduction of field wiring cost.

  5. Model S4000C Intelligent Sensors • Ease of Calibration • Single Point by One Person • Display Prompts User • No Adjustments, Tools or De-classification • Approvals • CSA Certified • FMRC Tested and Approved • Two Year Warranty • Sensor & Electronics are covered against defects in materials and workmanship • Fault Diagnostics • 6 Parameters Monitored During Operation • +3 Parameters Monitored During Calibration • Display Codes, Relays & Analog Signal are Output

  6. Model S4000C Intelligent Sensors Outputs • Digital Display Codes • 8 User Prompts • 9 Fault Codes • 3 User Selectable Relay Options • Analog Signal Output • 0mA Malfunction (optional calibration signal) • 1.5mA Calibration, Test Gas Mode • 1.5mA Relay Options Selection • 4 to 20mA 0 to 100% of full scale (proportional) • 20 to 22mA Over Range (not proportional) • SPDT Relay Outputs • Alarm, Warn & Malfunction Indications • 8A @ 250 VAC, 8A @ 30 VDC, resistive max.

  7. Display Units for S4000C • Model DC110 • 8 Channel Readout/Relay Display Module with Peak Channel Indication • Provides Common & Discrete Outputs for Malfunction, Warn and Alarm • Features: • DIP Switch Selectable Options • Relay Contacts for all Common Outputs • Open Collectors for all Discrete Outputs • Optional Voting for Common Alarm Output

  8. Display Units for S4000C • Model DC120 • Dual Channel Explosion-proof Display Module with Dual Digital Displays • Provides Common Relay contacts for Malfunction, Warn and Alarm • Model DC130 • Dual Channel Readout/Relay Display Module with Dual Digital Displays • Provides Common Relay contacts for Malfunction, Warn and Alarm • DIP Switch Selectable Options

  9. Mounting Hardware Duct Mounting Plate (10041) Wall and Panel Mounted Chassis 2 inch, 4 inch and 19 inch Chassis Splash Guard 10395-1 Dust Guard & Dust Guard Kits 1800822, 10110-1 & 10044-1 Test Gas Applicator 10460-2 & 10535-1 Aluminum Sensor Block (for sample draw) 10066 Calibration & Test Gas Equipment Portable Purge Calibrator Methane (1400150-M) Hydrogen (1400150-H) Other Gases are available 1400150-x 3 Liter Chamber for calibrating to volatile liquid vapors (1400200) Accessories