Adaptation of refrigeration compressors for Joule-Thomson cryocoolers fed with gas mixturesAgnieszka Piotrowska, Maciej Chorowski, Pawel DoroszWroclaw University of Technology, PolandCEC-ICMC 2015, June 29th, 2015
Outlines • Joule-Thomson coolers – open system • Joule-Thomson coolers supplied with gas mixture – closed system • Refrigeration compressors • The possibility of the compressor cooling • Conclusions
Joule-Thomson coolers – open system • Simple construction • No moving parts working at low temperatures • Short start-up time High workingpressure, min. 80 bar for N2, up to inversionpressure Lowthermodynamicefficiency Limited workingtime (need of pressure tank replacement)
Joule-Thomson coolers J-T coolers Micro capacity below 1 W Low capacity up to 10 W Medium capacity up to 50 W Cooling power: Wroclaw University of Technology, Poland CLOSED SYSTEM REQUIRED (reduction of working pressure) University of Twente, Netherlands
Joule-Thomson cooler – closed system NITROGEN HEAT EXCHANGER AZOT AFTERCOOLER JT VALVE HEAT EXCH. COMPRESSOR MIXTURE MIESZANINA
J-T cooler with hermetic piston compressor COMPRESSOR ELEMENTS ELECTRIC MOTOR
Compression process Poisson equation Nitrogenk = 1.40 Methanek = 1.31 Ethanek = 1.19 Propanek = 1.13 I-butanek = 1.10 Mixturek = (1.10 - 1.40)
Compressor test stand aftercooler throttling valve compressor
Test results Nitrogen Methane Ethane Propane I-butane 5-components mixture
Solutions of the compressor cooling Compressor located in the stream of theafter-cooler air - refrigeration technology v
Hermetic compressors Calculation results of the required compressor surface Compressors: Danfoss VTZ serie nitrogen mixture
Solutions of the compressor cooling Process modification To decrease inlet temperature of the working mixture:
DTexpected = 22K Process modification Test results: DTmeasured = 6 K
Solutions of the compressor cooling Modification of the construction Additionalcooling of the oil Outlet temperatureof gas – no additionalcooling Outlet temperatureof gas – additionalcooling Temperatureof the compressorshell – no additionalcooling Temperatureof the compressorshell – additionalcooling
J-T coolers designed, manufactured and tested at WUT CRYOGENIC SUB-SYSTEM REFRIGERATION SUB-SYSTEM CRYOGENIC SUB-SYSTEM REFRIGERATION SUB-SYSTEM
Test results – min. temp. 84 K Nitrogen 20%, Methane 30%, Ethane 10%, Propane 20%, I-butane 20% Temperature, K Pressure, bar Time, min
Summary • Laboratory tests confirm the possibility of using refrigeration compressors for Joule-Thomson coolers supplied with gas mixtures. • Temperature of oil (directly depending on the final temperature of compressionprocess) is main limit factor. • Depending on the volumetric efficiency, the hermetic refrigeration compressors can be used without any modifications (for low efficiencies), for high efficiencies the modifications are the must.