An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Today’s Topics 1- The per unit system 2-Transformer Voltage Regulation 3- Transformer Efficiency 4- Transformer Taps 5- Transformer Rating and Related Problems

  2. Per Unit Value = Actual value Base value The Per Unit System In power systems there are so many different elements such as Motors, Generators and Transformers with very different sizes and nominal values. To be able to compare the performances of a big and a small element, per unit system is used. In per unit system, each electric quantity is measured as a decimal fraction of some base level e.g. in a synchronous generator with 13.8 Kv as its nominal voltage, Instead of saying the voltage is 12.42 Kv, we say the voltage is 0.9 p.u.

  3. How Are the Base Values Defined For an electric element, we have : Power, Voltage, Current and Impedance Usually, the nominal apparent power (S) and nominal voltage (V) are taken as the base values for power and voltage The base values for the current and impedance can be calculated

  4. Example 1: A load takes 20 A at a power factor 0.9 lead when connected to a 600 Voltage. If the base voltage and apparent power are 600 and 6000 VA, determine the variables and impedance in per unit system

  5. Ideal Transformers in Per Unit Values

  6. Ignore the transformer

  7. Example: Given the transformer in the previous example rated at 20 kVA, 8000/240, calculate the equivalent circuit, with per unit values

  8. The equivalent circuit in per unit values Referred to the primary or secondary

  9. Transformer Voltage Regulation Fact: As the load current is increased, the voltage (usually) drops. Transformer voltage regulation is defined as:

  10. Other useful formulas Prefer small VR For an ideal transformer : VR=0 Note: If there were only resistive loads, the VR would not be much large in real transformers, but because loads normally have different power factors, VR may be considerably large in real transformers.

  11. VR in real transformers

  12. At unity power factor Resistive load At lagging power factor Inductive load At leading power factor Capacitive load

  13. Transformer Efficiency

  14. Transformer Taps The voltage in a distribution line is not constant. It may be 1.05 p.u. at generator terminal and 0.95 at the load side. Depending on the place the transformer is used, we may need to adjust the transformer ratio to get similar load voltage. That’s why we need Tap In Tap Changing Under Load (TCUL) transformer, the tap changes automatically to keep the output voltage constant

  15. Transformer Rating and Related Problems Transformers have three major ratings: Voltage, Apparent power (current) and frequency The parameters of equivalent circuit are given in p.u. As long as a transformer is working under rated conditions, there should be (is) no problem What should we consider if we want to use a transformer under de-rating conditions?

  16. Voltage rating The insulation has been designed to stand up to a particular voltage 10% increase in voltage in the linear part of B-H curve would result in 10% increase in magnetization current, but in the saturation part, the magnetization current may be unacceptable

  17. Frequency rating Exactly the same problem. If a 60 Hz transformer is going to be used in a 50 Hz system, the applied voltage should be reduced by a factor 5/6. Apparent power (current) rating Each coil has limit for current magnitude and also the higher current results in higher power loss (which is converted to heat) and may damage the insulation. This has a dramatic effect on transformer life. If the voltage rating has been reduced, the apparent power should be reduced by the same factor.

  18. Current Inrush If a transformer is switched to a system, there may be some current with large magnitude (Current Inrush), in the first few milliseconds after the switch is closed. The reason behind the current inrush is transient

  19. Transients Transient in electrical systems is the severe changes in current and voltage after a switch is closed or opened