An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Fire brigade Sprinkler Protection of Wooden Stairwells Henrik Bygbjerg, M.Sc., hby@dbi-net.dk Head of Research and Development at DBI 7th International Fire Sprinkler Conference 24-25 June 2008 in Copenhagen

  2. Sprinkler Protection of Wooden Stairwells • When renovation of old buildings 3 methods exists • Replacement of wooden stairwell with stairwell class R 30 A2-s1,d0 [BS-building element 30] i.e. steel or concrete stairwell • Protection of wooden stairwell with covering class K2 30 A2-s1,d0 [30 minutes Fire protection system] i.e. 15 mm fire gypsum board • Sprinkler protection of stair case

  3. Danish sprinkler regulation - historic • Sprinkler protection of wooden stairwell was allowed in buildings with up to 4 stories • Water amount calculated for release of all the sprinklers in the staircase • Alarm to the fire brigade by usage of Pressostat • Valves at building supply is to be installed

  4. Test programe • Laboratory test conducted in DBI laboratory • Staircase with 2.5 stories • Full scale test conducted in an existing building with 5 stories located in Copenhagen • Both test series was carried out for 4 different tests consisting of 2 fires in 2 boundary conditions: • Arson fire (fire in a child carrier) • Standard fire (wood crib) • Doors and windows to the staircase closed • Front door and top window to the staircase open

  5. Existing building for test in Copenhagen • 5 stories height • 6 sprinklers • 15 thermo couples • 2 pressure gates

  6. Standard fire (wood crib) – door and window open • Video

  7. Arson fire (child carrier) – door and window open • See the Video at: http://dbi-net.dk/Default.asp?Id=2768

  8. Results • The sprinkler system controlled all of the 4 fires • The sprinkler system extinguished 3 of the fires • Not all sprinklers in the staircase released • DBI retningslinie 251 chapter 1100 revised

  9. Results - temperatures

  10. Results - temperatures

  11. Future • Sprinkling of wooden staircase allowed in building with top floor level < 22.0 m over ground level • Release of 4 sprinkler should be used for water supply • Flow switch for transmitting alarm to the fire brigade • Valves at building supply shall not be installed

  12. Further information • Report (in danish) and video on DBI’s web page: www.en.dbi-net.dk • The test were conducted in coordination with www.social.dk www.nova5.dk www.dominia.dk www.kuben.dk www.bns.dk