2009 International Fuel Gas Code With Wisconsin Amendments. Training As Developed by Randy Dahmen, WI PE John Spalding, WI Architect WI Dept. of Commerce, Safety & Buildings Division, Madison, WI & LaCrosse, WI Web Site: COMMERCE.WI.GOV/SB.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about '2009 International Fuel Gas Code With Wisconsin Amendments' - malorie


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
2009 international fuel gas code with wisconsin amendments
2009 International Fuel Gas Code With Wisconsin Amendments

Training As Developed by

Randy Dahmen, WI PE

John Spalding, WI Architect

WI Dept. of Commerce, Safety & Buildings Division, Madison, WI & LaCrosse, WI

Web Site:

COMMERCE.WI.GOV/SB

ICC Codes w/WI Amendments

international fuel gas code ifgc table of contents
International Fuel Gas Code (IFGC) Table of Contents
  • Ch. 1 Administration
  • Ch. 2 Definitions
  • Ch. 3 General Regulations
  • Ch. 4 Gas Piping Installations (IFGC Chapter 4 “Gas Piping” is Replaced with the National Fuel Gas Code NFPA 54-2002)
  • Ch. 5 Chimneys and Vents
  • Ch. 6 Specific Appliances
  • Ch. 7 Gaseous Hydrogen Systems
  • Ch. 8 Referenced Standards

ICC Codes w/WI Amendments

elevation of ignition sources ifgc 305 3
Elevation of Ignition Sources IFGC 305.3
  • Equipment & appliances w/ ignition sources shall be elevated > 18” above the floor. Exception if appliance is listed as “flammable vapor ignition resistant” (Note: DVSC appliances do NOT necessarily meet this criteria)
  • Locations include hazardous areas, public/private garages, repair garages automotive service stations & parking garages.

ICC Codes w/WI Amendments

electrical bonding ifgc 310 1 comm 16 nec 250 104 b
Electrical Bonding IFGC 310.1/Comm 16/NEC 250.104(B)
  • Above ground portion of a gas piping system (other than CSST) is to be bonded to an effective ground-fault current path. Gas piping, other than CSST, to be considered to be bonded where it is connected to appliances that are connected to the equipment grouping conductor of the circuit supplying that appliance.

ICC Codes w/WI Amendments

electrical bonding csst ifgc 310 1 1 comm 16 nec 250 104 b
Electrical Bonding (CSST) IFGC 310.1.1/Comm 16/NEC 250.104(B)
  • The figure shown on the next slide has been tested for use on a pipe.
  • The Dept. requires that the clamp be used on a hard pipe, and NOT on the CSST itself.
  • An Licensed electrician is not required unless the bonding is occurring within the electrical box, or local rules are stricter

ICC Codes w/WI Amendments

electrical bonding csst ifgc 310 1 1 comm 16 nec 250 104 b7
Electrical Bonding (CSST) IFGC 310.1.1/Comm 16/NEC 250.104(B)
  • Corrugated Stainless Steel Tubing (CSST) gas piping systems shall be bonded to the electrical service grounding electrode system at the point where the gas service enters the building. The bonding jumper shall not be smaller than 6 AWG copper wire or equivalent

ICC Codes w/WI Amendments

ifgc ch 4 nfpa 54
IFGC Ch. 4/NFPA 54
  • All gas piping and gas piping installations shall comply with NFPA 54-2009

ICC Codes w/WI Amendments

plastic piping used for venting ifgc 503 4 1 1
Plastic Piping Used for VentingIFGC 503.4.1.1
  • Plastic pipe & fittings used to vent appliances to be installed in accordance with appliance manufacturer’s installation instructions.
  • Where a primer is required, the primer shall be of a contrasting color.

ICC Codes w/WI Amendments

chimney termination low heat gas ifgc 503 5 4
Chimney Termination -Low Heat GasIFGC 503.5.4
  • DO NOT
  • INSTALL
  • Below parapets
  • Under eaves
  • Next to walls

INSTALL

> 2 ft

> 3 ft

> 10 ft

< 10 ft

(unless the product is listed for such use)

ICC Codes w/WI Amendments

slide11

Per the Vent Product Listing?

ICC Codes w/WI Amendments

chimney termination medium heat gas ifgc 503 5 4
Chimney Termination - Medium Heat GasIFGC 503.5.4
  • DO NOT INSTALL
  • Below parapets
  • Under eaves
  • Next to walls

INSTALL

> 10 ft

> 10 ft

> 25 ft

< 25 ft

(unless the product is listed for such use)

ICC Codes w/WI Amendments

venting 2 or more gas appliances ifgc 503 10 4
Venting 2 or more Gas AppliancesIFGC 503.10.4
  • Where 2 or more vent connectors enter a common gas vent, chimney flue or single-wall metal pipe, the smaller connector shall enter at the highest level consistent with the available headroom or clearance to combustible material.

ICC Codes w/WI Amendments

venting 2 or more gas appliances ifgc 503 10 4 1
Venting 2 or more Gas AppliancesIFGC 503.10.4 .1
  • Where two or more openings are provided into one chimney flue or vent, the openings shall be at different levels, or the connectors shall be attached to the vertical portion of the chimney or vent at an angle of < 45o or less from vertical

ICC Codes w/WI Amendments

vent connector requirements ifgc 503 10 7 8 9
No dips or sags, fasten to flue collars and hood outlets with screws or other acceptable means

Must slope upward to vent or chimney at least 1/4” per 1 ft

Max horizontal length for single wall is 75% of height

Max horizontal length for “B” double wall or chimney vent, is 100% of height

Vent Connector RequirementsIFGC 503.10.7, 8 & 9

ICC Codes w/WI Amendments

slide16

Harry Homeowner installed this CPVC pipe touching the flue pipe.

  • The fix? Slip some cardboard between the warm flue pipe and meltable plastic!
  • The good news? The gas was turned off and repairs were done by a licensed plumber before re-inspection.

ICC Codes w/WI Amendments

gas cooking appliances ifgc 623
Gas Cooking Appliances IFGC 623
  • Open-top broiler units hoods to have a min. clearance of 24” to be maintained between the cooking top and combustible material above the hood, such as cabinets.
  • A minimum clearance of 30” is required above household cooking appliances. Req’t reduced to 24” where 1 of 3 listed exceptions are met.

ICC Codes w/WI Amendments