1 / 22

Selection of HCRW Treatment Technologies for Gauteng

Selection of HCRW Treatment Technologies for Gauteng. David A Baldwin, PhD, Pr.Sci.Nat. Environmental and Chemical Consultants cc and Torben Kristiansen Chief Technical Advisor. Gauteng Department of Agriculture, Conservation, Environment and Land Affairs Ramb ø ll, Hanneman and Hojland

lunette
Download Presentation

Selection of HCRW Treatment Technologies for Gauteng

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Selection of HCRW Treatment Technologies for Gauteng David A Baldwin, PhD, Pr.Sci.Nat. Environmental and Chemical Consultants cc and Torben Kristiansen Chief Technical Advisor. Gauteng Department of Agriculture, Conservation, Environment and Land Affairs Rambøll, Hanneman and Hojland August 2003

  2. Introduction Status Quo Study into HCRW in Gauteng – 2000: • Confirmed parlous state of HCRW management in Gauteng • Treatment facilities included 70 incinerators at 58 different locations • Only 58 were “operational” but only 25 had a permit • Many incinerators were poorly operated and maintained • Only one fitted with emission control equipment, which was not operational • Capital and operating costs were estimated at only R1.00 per kilogram of waste treated

  3. Introduction to Technologies -1 • Thermal treatment/combustion technologies: • Incineration which includes: • excess air, • controlled air, • rotary kiln and • fluidised bed • Plasma Arc and • Pyrolysis

  4. Introduction to Technologies -2 • Sterilisation/Disinfection Technologies, • Steam sterilisation, e.g. Autoclaving • Chemical sterilisation, e.g. with chlorine, glutaraldehyde • Gas sterilisation, e.g. with ethylene oxide, formaldehyde • Dry heat sterilisation, e.g. oil heated screw feed technology • Electro-thermal deactivation (ETD), • Microwave sterilisation, • Irradiation sterilisation • Cobalt-60 gamma rays • Ultra violet • Electron beam sterilisation

  5. Waste Pathway for Incineration Infectious waste & Sharps Ash Landfill Leachate Flue gas cleaning residues PathologicalWaste Incineration Chemical Waste Emissions to Air

  6. Waste Pathway for Non-Burn Technologies Leachate + Gas Emissions Non-infectious waste Infectious waste & Sharps Non-Burn Treatment Landfill Incineration Cremation or Burial Ash or Body Parts PathologicalWaste Cemetery Treatment as Hazardous Waste Waste Treatment Residues to Landfill Chemical Waste

  7. Flow Diagram of Modern Incineration Plant

  8. Advantages of Incineration • Safe elimination of all infectious organisms in the waste at temperatures above ~700oC • Flexible, as it can accept pathological waste and depending on the technology chemical waste. • Residues are not recognisable • Reduction of the waste by up to 95% by volume or 83 to 95% by mass: typically 5-17% ash is obtained. • Very well proven technology • No pre-shredding required • No special requirements for packaging of waste • Full disinfection is assumed to have occurred provided the high temperatures are maintained and the ash quantity is adequate. No monitoring of sterilisation efficiency is required.

  9. Disadvantages of Incineration • Normally higher investment costs required for incinerator and flue gas cleaning compared to non-burn technologies • Point source immediate emissions to the air (as opposed to attenuated emission of CH4 and CO2 from landfill body over a period of decades) • High cost of monitoring gas emissions and demonstrating compliance to emission standards. • Solid and liquid by-products must be handled as potentially hazardous waste (may not apply to bottom ash if waste is well sorted and FGC residues handled separately) • Incineration is perceived negatively by many sections of the community. • PVC and heavy metals in the waste provide a significant pollutant load on the gas cleaning system and for heavy metals on the quality of bottom ash • Existing health care risk waste incinerators in South Africa cannot accept significant amounts of chemical waste because of refractory damage.

  10. Flow Diagram a Typical Microwave Plant

  11. Advantages Non-Burn Technologies -1 Autoclaving, Microwaving ETD and DHS (Cross cutting) • High sterilisation efficiency under appropriate conditions • Low temperature of operation 90oC to 160oC • Volume reduction depending on type of shredding/compaction equipment that has been installed • Low risk of air pollution • Moderate operation costs • Easier to locate as generally more acceptable to communities and neighbours than incineration • Recovery technologies can be used on sterilised waste

  12. Advantages Non-Burn Technologies -2 • Autoclaving • Proven system that is familiar to health-care providers • Relatively High Sterilisation Temperature • Microwaving • Low capacity units are available for small waste producers e.g. clinics and GPs • Moderate investment costs • Low Sterilisation Temperature may lower energy costs • Electro-thermal Deactivation • Low Sterilisation Temperature may lower energy costs

  13. Disadvantages Non-Burn Technologies -1 Autoclaving, Microwaving ETD and DHS (Cross cutting) • Not suitable for pathological waste and chemical waste • Good waste segregation required • No or limited mass reduction • Shredders are subject to breakdowns and blocking and repairs are difficult when the waste is infectious. • It is not possible to visually determine that waste has been sterilised • Waste is not rendered unrecognisable or unusable, if not shredded • “High” monitoring costs to demonstrate compliance with sterilisation standards • Treated waste must be disposed to landfill • Air filtration is needed – some odour problems • Operation requires highly qualified technicians. • HEPA filters must be maintained and replaced regularly

  14. Disadvantages Non-Burn Technologies -2 • Autoclaving • Significant amounts of volatile organic carbon compounds produced • Contaminated water must be discharged to sewer • Waste and containers must have good steam permeability, especially if there is no prior shredding • No waste reduction • Microwaving • Unsuitable for very high quantities of infected metal (e.g. needles from inoculation campaigns) • Low sterilisation temperature increases time required for treatment. • Electro-thermal Deactivation • Relatively high investment and operating costs • Low sterilisation temperature increases time required for treatment.

  15. Cost Comparison of Selected HCRW Treatment Technologies - 1 Assumptions: • Salary costs include all normal contributions • The cost for the establishment of a building in the estimated costs. • A standard fixed amount for consultancy fees and other expenditure required to obtain an EIA authorisation, etc • The cost of equipment was based on International/South African price levels for delivery in Gauteng. • Incinerators include gas-cleaning equipment, i.e. lime treatment plus a ceramic filter. • The cost of civil works and installation were based on Gauteng prices

  16. Cost Comparison of Selected HCRW Treatment Technologies - 2 • Economic life of civil works and treatment technologies: 12 years • Economic life of storage and transportation equipment: 10 years • The following costs not included: • Infrastructure at the generators site, • Establishment of public utilities used, e.g. landfills • Cost of administration, invoicing, marketing etc. • Cost of training of operators • Cost of PPE/OSH programmes. • Value Added Tax. • Depreciation costs are estimated as 10 years for equipment and 15 years for other capital and a real interest rate of 12% p.a.

  17. Cost Comparison of Selected HCRW Treatment Technologies - 3 • The operational hours for the plants were based on operation for 26 days per month and 12 months per year. However, the maximum operational hours were varied as follows: • Incinerators < 200kg/hr: 12 hrs per day - manual de-ashing • Incinerators  200kg/hr: 20 hours per day - automatic de-ashing • Non-burn Technologies: 24 hours per day • The costs for disposal of residues, such as the ash and gas cleaning waste from incinerators, and sterilised the waste from non-burn technologies, were estimated using current disposal costs. Residues from non-burn are assumed deposited at normal landfill sites, whereas residues from incinerators are assumed deposited at a Hazardous Waste Landfill site. • For non-burn technologies an estimate of the costs of disposal of pathological waste and chemical waste that could not be treated by the technology was included

  18. Costs for HCRW Treatment Technologies

  19. Cost of HCRW Technologies • Treatment cost decreases dramatically as plant capacity increases • For incineration, there is a discontinuity that occurs below 200kg/hr due to the assumptions made • The costs are based on operating the facility at its maximum capacity. • According to the available data, microwaving is relatively expensive but the costs become comparable at higher loads. • The investment costs for incineration appear to be relatively low compared to the other two technologies.

  20. Testing and Monitoring Incineration Plants - 1 Requirements: • Performance Testing – to conform to ROD • Standard Testing – at least over first year of operation • Minimum Programme – once prove conformance • Analysis Required: • Continuous Monitoring of PM, carbon monoxide, oxygen, water vapour, hydrochloric acid and sulphur dioxide • Dioxins: Performance x 1; Standard – 2/yr; Minimum – 1/yr • Metals: Performance x 1; Standard – 2/yr; Minimum – 1/yr • Loss on Ignition for Ash: Performance x 1; Standard and Minimum – 12/yr

  21. Testing and Monitoring Incineration Plants - 2

  22. Testing and Monitoring Incineration Plants - 3

More Related