SpacePak Chiller. Heat exchanger head loss Water onl. SCM -036. SCM -060. I was just checking up on some flow-switch samples we’ll be receiving, and went to the Cole Parmer material compatibility website http://www.coleparmer.com/Chemical-Resistance

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'SpacePak Chiller' - lacey


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
Spacepak chiller

SpacePak Chiller

Heat exchanger head loss

Water onl


Scm 036
SCM-036


Scm 060
SCM-060


  • I was just checking up on some flow-switch samples we’ll be receiving, and went to the Cole Parmer material compatibility website http://www.coleparmer.com/Chemical-Resistance

  • I checked PVC  against ethylene glycol and it received an A, (as did CPVC but that is to be expected), but then checked Propylene glycol, and it received only a C, which states; Moderate Effect, not recommended for continuous use. Softening, loss of strength, swelling may occur.

  • (but with a sidenote that it is satisfactory up to 72ºF/22ºC)

  • This was the same for PVC and CPVC, which I know is commonly used in this application. We should keep this in mind when making recommendations, that PVC/CPVC is not suitable for Propylene glycol (no point splitting hairs and saying okay for cooling but not heating)

  • I will check up on the plastic used inside the SCM chillers, to see what the material is and if there should be concern.

  • Pex was not listed by name, or by it’s generic (cross linked) HDPE, but other websites state it is suitable for EGW or PGW.

  • Just some more information for our reference toolbox.