An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CBGS 0 - “Simplicity, reliability, safety, at low costfor indoor substations up to 36 kV”

  2. Index • General characteristics • Field of application • Gis technology • Advantages of CBGS-0 • References • CBGS-0 cubicles: description

  3. Internal ARC 20kA-0,5s / 31,5kA-1s General Characteristics • Metal enclosed GIS (SF6 insulated) CONFIGURATION Shot Circuit Current Configuration Rat.Voltage Rated Current Single Busbar 24 kV – 36 kV 1250 / 1600 A 25 / 31,5 kA

  4. Field Of Aplication • Primary distribution substations • Utilities • Windfarms • Airports • Traction substations • Heavy load industries • Etc.....

  5. Main Technical Characteristics • Main differences with AIS (air insulated switchgear): • Circuit Breaker: • GIS: fixed • AIS: withdrawable • Dimensions (isolating distances): • GIS: smaller • AIS: bigger • Access to the MV parts: • GIS: no possible (insensitivity to atmospheric conditions) • AIS: possible • GIS maximizes: • Service Continuity • Operation Security • Space Savings

  6. Advantages Service continuity Maximun security Minimun cost Simple design

  7. Service Continuity • Extended endurance (mechanical & electrical): • Lower distances/dimensions due to SF6 insulation • Minimum Energy Required • Insensitivity to ambient conditions: • Sealed for life SF6 compartment: Routine tested • Service live >30 years • Minimum maintenance needed High reliability => extended service life

  8. Maximum Savety • No access to MV parts: “Safe to Touch” • Secure access to cables: • Front access • Voltage Presence Indication • Avoided without earthing • Front access to all mechanisms and LV compartment • False manoeuvres are avoided (interlockings): • Impossible to act on the disc. with CB in closed position • To finish up disc. manoeuvres is a must • Position indicators are totally reliable (IEC) • Internal arc tested ...31,5 kA/1s • Minimum fire risk

  9. Simplicity – Installation • No need of specially qualified staff for installation: • No SF6 handling on site • Busbar installation: similar to cable connectors • Cable connectors installation: similar to well known RMU Simplicity => Security Simplicity => Reliability => Continuity

  10. Simplicity – Operation • Synoptical indication: • Front of the panel • Easy to read • Totally reliable • Simple and secure operation • Interlockings to avoid false manoeuvres Simplicity => Security Simplicity => Reliability => Continuity

  11. Simplicity – Mainteineability & Repairability • Maintainability: • Free of maintenance in MV parts • Just low maintenance is recommended for operating mechanisms • Operating mechanisms are easily accessible from the front • Reparability: • In case of mayor failure: • Quick change of one cubicle (<4 hours) • Service is quickly restablished Simplicity => Security Simplicity => Reliability => Continuity

  12. 600 600 1250 1250 1950 2300 1000 1000 Minimum Cost – Space Savings CBGS-0 24 kV 0,75 m2 AIS cubicle 24 kV 1,95 m2 CBGS-0 36 kV 0,75 m2 AIS cubicle 36 kV 2,30 m2 • Additional space savings: • Only front access required • Possible installation close to the back wall

  13. Minimum Cost – Summary • Direct cost of each cubicle: Higher Reliability / Continuity Maximum Safety Space and Civil Works Savings Savings in Maintenance Works Savings in Installation Works Maximum value for user

  14. References • CBGS: More than 5000 units already installed • Some end users: • Utilities: Endesa, Iberdrola, Vattenfall,… • Wind: Gamesa, Vestas,… • Railways: RENFE, METRO BCN, MAD, BIO,… • Airports: AENA BCN, MAD, BIO, TNF,... • Industry: Renault, Mercedes Benz,…

  15. Description • Architecture: • Busbar compartment • Isolating and/or Breaking compartment: • Circuit Breaker • Disconnector • Load Break Switch • Fuse-Switch • Cable compartment • Cubicle

  16. Achitecture Low voltage comp. Busbar Isolating and/or breaking Power cable comp.

  17. Achitecture • LV Compartment: • 1 - LV compartment • 2 - LV cable tray • 3 - Protection relay • Busbar Compartment: • 4 - Busbar system • 5 - Busbar compartment enclosure • 6 - Current transformers • 7 - Voltage transformers 7 2 5 1 6 3 4

  18. Achitecture • Isolating and Breaking Sw Comp.: • 8 - Sealed for life tank – SF6 insulated • 9 - Gas exhausting flap • 10 - 3 Position disconnector • 11 - Circuit breaker • 12 - Operating mechanism of the disconnector • 13 - Operating mechanism of the CB • Cable Compartment: • 14 - Cable connection bushings • 15 - Power cable connectors • 16 - VT connection cable • 17 - Current transformers • 18 - Voltage transformers • 19 - Front access door 8 10 12 13 11 9 18 14 16 17 19 15

  19. Busbar Compartment • Insulation system: • Fase by fase • Solid • Screened • Earthed • “Safe to Touch” • Possibility of installing VT-S and CT-S: • Directly on busbar system • No need of specific measuring cubicle

  20. Breaking And Insulating Switchgear Compartment • Tank: • Stainless steel • Sealed for life • SF6 low relative pressure (0,3 bars) • Operating mechanisms: • Accessible from front • Out of SF6 atmosphere • Possible configurations: • 3 position disconnector + circuit breaker • 3 position disconnector • Load break switch - disconnector + fuses • Load - seccionador

  21. Circuit Breaker • Breaking medium: SF6 • Separated poles • Low maintenance operating mechanism • Totally interlocked with the disconnector: no false manoeuvres • Earthing of the incoming circuit: making capacity

  22. 3 Position Disconnector • 3 positions: closed-open-earth • Single operating axle • Separated operating shafts (handles): • Open-closed • Open-earth • Totally interlocked with the circuit breaker: no false manoeuvres • Earthing of the incoming circuit: trough CB (making capacity)

  23. Load Break Switch-disconnector • 3 positions: closed-open-earthed • Separated operating shafts (handles): • Open-closed • Open-earth position • Breaking capacity: up to 630 A • Installations possibilities: alone or associated with fuses

  24. Cable Compartment • Secure access: • From the front • Totally interlocked with the earthing manoeuvre • Standard cable connection bushing: • Type C according to EN 50181 • Standard cable connectors • Up to 3 power cables + VT by fase • Possibilities: • Ring type CT-s on the bushings • Ring type CT-s on the cable (only 1 cable configuration) • VT-s connected by means of isolated MV cable

  25. Current And Voltage Transformers • CT-S: • Types: • Ring type for busbar compartment • Ring type for cable compartment • Several burden and accuracies (consult) • VT-S: • Types: • Connected by means of MV cable • Connected directly to busbar system • Several burden and accuracies (consult)

  26. Cubicle Types CB+disconn. Rising Coupling LBS-disconn. Disconnerctor Aux. services

  27. ¿Any question or comment? Thank you very much

  28. CBGS 0 - “Simplicity, reliability, safety, at low costfor indoor substations up to 36 kV”