Exercise Ducting Design. Determine type and number of resisters Decide on the air distribution Decide on velocity and noise criteria Find worst case scenario Duct Sizing method selected: equal Friction. Data. 10m. 7m. Airflow = 3214 m³/h = 896 l/s. H = 3,5 m. Trox Air Distribution.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'Exercise Ducting Design' - jonah-hill


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
slide1
Exercise Ducting Design
  • Determine type and number of resisters
  • Decide on the air distribution
  • Decide on velocity and noise criteria
  • Find worst case scenario
  • Duct Sizing method selected: equal Friction

Daikin Europe, Consulting Sales Section

slide2
Data

10m

7m

Airflow = 3214 m³/h = 896 l/s

H = 3,5 m

Daikin Europe, Consulting Sales Section

slide3
Trox Air Distribution

Daikin Europe, Consulting Sales Section

slide4
Trox Air Distribution

Daikin Europe, Consulting Sales Section

slide5
Trox Quick Selection

Daikin Europe, Consulting Sales Section

slide6
Position and type of resisters

10m

How many resisters?

L < 1,5 * W

10 < (1,5 * 7 = 10,5)

L < 3 * H

10 < 3 * 3,5 = 10,5

in theory, 1 resister could do

but the airflow = 896 l/s is

TOO BIG for 1 resister

7m

For a better air distribution, to avoid draft and noise, we select 8 diffusers

H = 3,5 m

Airflow= 896l/s

Daikin Europe, Consulting Sales Section

slide7
A

C

B

C

Air Distribution

10m

8-off TDF500’s

For 112l/s

7m

Airflow= 896l/s