TECHNICAL TRAINING 2007
3 types program upgrade: • ID PCB • A type OD PCB • B type OD PCB PCB Program Upgrade
ID PCB Upgrade • Short the Jumper JP1, JP3 ~ JP6 on the PCB • Connect the ID PCB and Gateway Turn on the upgrade software in PC and select parameters Upgrade Turn off the ID PCB power Revert the jumpers back to factory default setting after the completion of upgrade Power on
A Type OD PCB Upgrade • Short the Jumper P1, P3 ~ P5 on the PCB • Connect the OD PCB and Gateway Turn on the upgrade software in PC and select parameters Turn off the OD PCB power Revert the jumpers back to factory default setting after the completion of upgrade Upgrade Power on
B Type OD PCB Upgrade • Remove MCU board & short the Jumper P1 ~ P5 on the PCB • Connect the OD PCB and Gateway Turn on the upgrade software in PC and select parameters Turn off the OD PCB power Revert the jumpers back to factory default setting after the completion of upgrade Upgrade Install the MCU board & power on
Starting Up & Monitoring Software • Smart Commander connecting A Series unit • Smart Commander connecting B Series unit
Monitoring Software with A series • Connection of OD and PC • Start Smart Commander, select parameters • Connect communication • Monitor data
Monitoring Software with B Series • Connection of OD and PC • Start Smart Commander, select parameters • Connect communication • Monitor data
Common Problems & Solutions Possibilities of unsuccessful of upgrade: • Monitoring Software is still connecting • Wrong serial port is being selected • Wrong crystal frequency is being selected • Wrong ID & OD jumper setting • Wrong jumper setting of Gateway • The transformer of Gateway is abnormal • The Gateway is abnormal • ID & OD PCB is abnormal
Common Problems & Solutions • Operation of Smart Commander problems: • Wrong serial port is being selected • Wrong baud rate is being selected • Wrong ID & OD jumper setting • Wrong OD address setting • Wrong jumper setting of Gateway • The transformer of Gateway is abnormal • Gateway is abnormal
Common Problems & Solutions Malfunction of ID & OD communication: • Incorrect ID & OD jumper setting • Incorrect polarity of communication wire • JP7 is not shorted for the last ID • No power supply for ID • Incompatible of ID & OD program version • ID or OD PCB is abnormal • Communication wire is too long. Should not more than 1000m
Precaution: • Complete jumper setting before power on, if not the setting will not be changed • Connect the communication wire before power on, don’t insert or pull out it when power on • Pull out the signal output slot when testing • Ensure the pin and socket is corresponded when installing the PCB • Incompatible of ID & OD program version • Ensure the dip-switch setting is correct • Follow the regulations & instructions in IM
Graphic of ID PCB Connect to Gateway Short JP1, JP3 ~ JP5
ID Jumper Setting Factory Default Setting Jumpers being shorted
Gateway Connection 9Vdc power supply RS-485 Connection Open jumper J11 & J13 Serial port Connect to ID PCB
Selection of Parameters • MCU selection. MB89F538/L is being used. • The frequency of ID is 8MHz. • Select ID programming file. • Select serial port. • Click to run full operation.
Upgrade Process Start to upgrade Upgrade in progress Upgrade process complete
Graphic of the A Type OD PCB MCU Connect to Gateway Short P1, P3 ~ P5
A Type OD Jumper Setting Factory Default Setting Jumpers being shorted
Selection of Parameters • MCU selection. MB89F538/L is being used. • The frequency of OD is 4.9152MHz. • Select ID programming file. • Select serial port. • Click to run full operation.
Graphic of B Type OD PCB MCU board MCU Connect to Gateway Short JP1~ JP5
B Type OD Jumper Setting Factory Default Setting Jumpers being shorted
Selection of Parameters • MCU selection. MB89F538/L is being used. • The frequency of OD is 4.9152MHz. • Select ID programming file. • Select serial port. • Click to run full operation.
Wiring Connection (A Series) A type OD PCB ID & OD communication wire * A to A ; B to B Electrical outlet 9Vdc power supply Red & Black pairs connect to A; Yellow & Green pairs connect to B Serial port Communication wires of Monitoring Software Gateway
Selection of Parameters • Select data record cycle • Select the correct serial port • Select baud rate (19200) • Select the numbers of OD • Click the button
Graphic Interface of Monitoring Software Total required capacity Inlet Temp of OD condenser Output % of digital comp. Midlet Temp of OD condenser Discharge Temp Ambient Temp Outlet Temp of OD condenser Suction Temp Opening of OD EXV To check ID
Graphic Interface of Monitoring Software Starting status of compressor OD fan speed 4WV status Defrost parameters To monitor slave unit OD setting parameter
Monitor Data ID selection column Parameters can be observed for ID Single ID required capacity Selection of operating parameters Click “Apply” to operate
Selection of OD Parameters If TH9 ≤ TscA1, target sub-cool is TscT1 If TscA1 < TH9 < TscA2, target sub-cool is TscT2 If TH9 ≥ TscA2, target sub-cool is TscT3 Critical point of defrost curve Connecting pipe compensate coefficient Defrost stop when reach this temp (TH9) Midlet temp setting for all ID (heating) Adjust target super heat. The default value for R22 is 5 whereas 3 for R410A Heating EXV motion coefficient. EXV opening setting
Special Command Button Manual defrost. The master unit will turn into defrost mode All EXV will open to 480 steps.
Selection of Parameters (Slave OD) Change slave unit parameter
Wiring Connection (B Series) ID & OD communication wire * A to A ; B to B B type OD PCB Communication wires of Monitoring Software 9Vdc power supply Serial port
Signal Output Slot Remove the Signal Output Slot when testing