VLT Diagnostics. Click on the button above your Keypad. VLT 5000/2800 Must use LCP-2 keypad with VLT 2800. The Drive is NOT running! Press the Display/Status key Read the bottom line Click on button for your Display LCP STOP UNIT READY STANDBY RUN OK RUN JOG LOCAL

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'VLT Diagnostics' - jana-bryant


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
vlt diagnostics
VLT Diagnostics

Click on the button above your Keypad

vlt 5000 2800 must use lcp 2 keypad with vlt 2800
VLT 5000/2800Must use LCP-2 keypad with VLT 2800

The Drive is NOT running!

Press the Display/Status key

Read the bottom line

Click on button for your Display

  • LCP STOP
  • UNIT READY
  • STANDBY
  • RUN OK
  • RUN JOG
  • LOCAL

My problem is not shown

Start Over

lcp stop
LCP STOP
  • Main Display 0.0Hz is FLASHING
  • Press the START key on the keypad.
  • Still doesn’t Run? – go back to VLT 5000 page.
unit ready
UNIT READY
  • Remove cover just under keypad – These are Control Terminals
  • If wire attached to terminal 27, Close the switch between terminal 27 (Digital Input) and terminal 12 or 13 (+24Vdc).
  • If no wires is attached to terminal 27 – place a jumper between terminal 27 and 12 or between 27 and 13
  • Go back to VLT 5000 page -
standby
STANDBY
  • Standby means there is no “START” command.
  • Remove cover just under keypad – These are Control Terminals
  • Close the switch attached to terminal 18.
  • Go back to VLT 5000 page -
run ok
RUN OK
  • Display Status says RUN OK but output frequency stays at zero Most likely Reference is at zero.
  • Press the + key until “Reference” appears. If it is zero find reference and change it to a number above 0.
  • No GO! Go to Phone Call
  • Go Back to the first page -
run jog
RUN JOG
  • Remove cover just under keypad – These are Control Terminals
  • Open the switch attached to terminal 29.
  • No GO. Go to Phone Call
  • Go back to the VLT 5000 page -
local rem
LOCAL/ REM
  • Drive ignores all external commands
  • Press “Quick Menu” key then the “+” key – until 12 of 13 apear on top line, parameter 002 appears near bottom. Press “Change Data” key, then “+” key until bottom line says “REMOTE”
  • No GO. Go to Phone Call.
  • Go back to VLT 5000 page
vlt 6000 8000 diagnostics
VLT 6000/8000 Diagnostics

The Drive is NOT running!!!

Press the “Display Mode” key

Read the bottom line

Click on button for your Display

  • OFF LOCAL STOP
  • UN. READY
  • STANDBY
  • RUNNING
  • JOG

My problem is not shown

Start Over

hand local
HAND LOCAL
  • Drive ignores all commands
  • “Hand Local” means Keypad is in control
  • Press “Auto Start” key – “Auto Rem.” appears.
  • No GO. Go to Phone Call
  • Go back to VLT 6000 page
off local stop
OFF LOCAL STOP
  • OFF/STOP key on keypad overrides all commands both Hand and Auto.
  • Main Display (0.0Hz) starts to Flash
  • To remove - press Auto/Start key
  • No GO. Go to Phone Call.
  • Go back to VLT 6000 page
running
RUNNING
  • “Running” has both Start command but no reference
  • If you can not find the reference, go to
  • Phone Call
  • Go back to VLT 6000 page
un ready
UN. READY
  • Remove cover just under keypad – These are Control Terminals
  • If wire attached to terminal 27, Close the switch between terminal 27 (Digital Input) and terminal 12 or 13 (+24Vdc).
  • If no wires is attached to terminal 27 – place a jumper between terminal 27 and 12 or between 27 and 13
  • Go back to VLT 6000 page
standby1
STANDBY
  • Standby means there is no “START” command.
  • Remove cover just under keypad – These are Control Terminals
  • Close the switch attached to terminal 18.
  • Go back to VLT 6000 page
slide15
JOG
  • Remove cover just under keypad – These are Control Terminals
  • Open the switch attached to terminal 29.
  • No GO. Go to Phone Call
  • Go back to VLT 6000 page
phone call needed

Catalog Number

Phone Call Needed

Phone 210-9411744 (Danfoss Drives GRSC) ask for Service Technician

Find label on drive – be ready to give Catalog Number

Sales Number and Serial Number.

Serial Number

Sales Number

Start Over